Thermal resistance input signal isolator
1、 Characteristics
MS7082(1入1出)、MS7920(1入2出 )
·Suitable for thermal resistors such as Pt100 and Cu50
·Isolation output 4-20mA or 1-5V
2、 Technical specifications
|
·Suitable for thermal resistance signal input, after isolation, converted into standard DC signal with circular fixed range output to the control system or other instruments. ·Single channel, one input, one output. DC power supply mode, with isolation between the power supply input and output. ·Adopting standard 35mm DIN rail card installation. Plug and unplug wiring plug terminal spring compression connection. It can be used in conjunction with DCS, PLC and other systems or other instruments, and is widely used in various temperature detection and control systems in industrial production processes. ● Input Input thermistor: P1100; Pt10; Cu50; Cu100 and other types of thermal resistors Allowable wire resistance: ≤ 10 Ω per wire ● Output Output signal: 4~20mA, 1~5V, or other specified signals Load resistance: ≤ 550 Ω when outputting 4-20mA (factory default) When outputting 1-5V, ≥ 100K Ω Output ripple:<10mVp-p |
● Power supply Power supply voltage range: 20-30VDC Rated supply voltage: 24VDC Current consumption (when powered by 24VDC):<30mA (1 in 1 out) <48mA (1 in 2 out) ● Comprehensive parameters Standard accuracy: ± 0.1% (see table for thermal resistance type, range, and measurement error) Temperature drift: Basic error/10 ℃ Response time:<10ms Isolation capability: 2.5KV, 1min, 50Hz between input output power supply Insulation resistance: ≥ 100M Ω/500VDC between input output power supply Working environment temperature: -20~+60 ℃ Storage environment temperature: -40~+80 ℃ Shell material/protection level: PC (polycarbonate) material/IP20 Dimensions: 16 × 116 × 110 (mm) |
3、 Model selection

![]()
![]()
4、 Dimensions and installation diagram
● Installation
1.35mm standard DIN rail card installation. Please pay attention to the stability and firmness of the card position during installation.
2. Install vertically as much as possible to facilitate heat dissipation inside the instrument.
● Typical applications
1. Used to provide distribution voltage to on-site transmitters and isolate and convert input signals.
2. Devices connected to the site: Active electrical signals from two-wire or three wire non smart transmitters.
3. Connect to the control system (or other unit combination instruments): The AI card of each DCS/PLC receives current or voltage signals.

● External dimensions
Width (thickness) x height x depth=16 x 116 x 110 (mm)

5、 Terminal wiring diagram
Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed 2.5mm2Multiple bundles or single stranded cables.