E-mail
664688125@qq.com
-
Phone
18255085484
-
Address
23rd Floor, Unit 2, Building 16, Binhu City, Tianchang City, Anhui Province
Anhui Maoshu Instrument Co., Ltd
664688125@qq.com
18255085484
23rd Floor, Unit 2, Building 16, Binhu City, Tianchang City, Anhui Province
Resistance signal input isolator
1、 Characteristics
MS7083( 1入1出)、MS7084(1入2出)、MS7085(2入2出)
·Resistance value input
·DC signal output
2、 Technical specifications
|
·Connect the resistance signal input, isolate and linearize it, convert it into a standard DC signal output to the control system or other instruments. ·Powered by an independent DC power supply, with isolation between the power supply input output. ·Standard 35mm DIN rail card installation. Plug and unplug terminal block with spring compression connection. ● Input Input resistor type: 2-wire or 3-wire resistor Resistance range: 0~10K Ω (Special resistance potentiometer, specified by the user when ordering) ● Output Output signal: 4-20mA, 1-5V, or other specified signal Load resistance: ≤ 550 Ω when outputting 4-20mA (factory default) When outputting 1-5V, ≥ 100K Ω |
● Power supply Power supply voltage range: 20~30VDC Rated supply voltage: 24VDC Current consumption (when powered by 24VDC):<30mA (1 in 1 out) <40mA (1 in 2 out) <60mA (2 in 2 out) ● Comprehensive parameters Standard accuracy: ± 0.2% Temperature drift: ± 0.015%/℃ Response time:<10ms Isolation capability: 2.5KV, 1min.50Hz between input output power supply Insulation resistance: ≥ 100M Ω/500VDC between input output power supply Working environment temperature: -20~+60 ℃ Storage environment temperature: -40~+80 ℃ Shell material/protection level: PC (polycarbonate) material/IP20 Dimensions: 16 × 116 × 110 (mm) |
3、 Model selection

![]()
![]()
4、 Dimensions and installation diagram
● Installation
1.35mm standard DIN rail card installation. Please pay attention to the stability and firmness of the card position during installation.
2. Install vertically as much as possible to facilitate heat dissipation inside the instrument.
● Typical applications
1. Used to provide distribution voltage to on-site transmitters and isolate and convert input signals.
2. Devices connected to the site: Active electrical signals from two-wire or three wire non smart transmitters.
3. Connect to the control system (or other unit combination instruments): The AI card of each DCS/PLC receives current or voltage signals.

● External dimensions
Width (thickness) x height x depth=16 x 116 x 110 (mm)

5、 Terminal wiring diagram
Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed 2.5mm2Multiple bundles or single stranded cables.