1feature
· 1enter1go out
·Intrinsic safety input
·Applicable toKTheETheSTheBWaiting for thermocouple
·Can be programmed to set input type and range
·isolated output4~20mAor1~5V
II. Overview
1、This isolation safety barrier is suitable for thermocouple signal input in hazardous areas on site,After isolation,Convert into standard current or voltage signals and output them to the control system or other instruments in the safe zone.
2、It is an intelligent temperature transmission isolation safety barrier,can be passed throughPCThe machine and control software are programmed to set the input thermocouple type and range.
3、single channel,One way input,Output all the way. The isolation safety barrier is powered by an independent DC power supply-input-Isolation between outputs.
4、The temperature transmission isolation safety barrier can be connected to the unit combination instrument andDCSThePLCWaiting for the system to be used in conjunction,Widely used in various temperature detection and control systems for industrial production processes.
5、standard35mmDINRail card installation. Plug and unplug terminal block,Spring compression connection.
3、 Technical specifications
●input(intrinsically safe)
Input type:KTheETheSTheBTheRTheTTheNTheWTheJWaiting for various types of thermocouples
Temperature range: depends on the type of sensor used(Refer to the range table)
Millivolt signal: -10~+100mVscope
***Small millivolt range:5mV
●output
Output signal:4~20mA,1~5V,Or other designated signals
Load resistance: current4~20mAor4~20mAwhen outputting≤550Ω
voltage1~5VThe0~5Vor0~10Vwhen outputting,load≥100KΩ
●power supply
Supply voltage range:20~30VDC
Rated supply voltage:24VDC
***High current consumption:<35mA
●Conventional comprehensive parameters
Standard accuracy:±0.1%(Refer to the thermocouple range and measurement error table)
Cold end compensation accuracy:±1℃ (Compensation scope-15~+75℃)
(The cold end compensation resistor has been installed inside the isolation safety barrier)
Temperature drift: basic error/10℃
Response time:<1s
Isolation ability: Input-output-Between power sources2.5KV,1min ,50Hz
Insulation resistance: input-output-Between power sources≥100MΩ / 500VDC
Shell material:PC(Polycarbonate)material
Overall dimensions:16×116×110(mm)
Working environment temperature: -20~+60℃
Suitable for connecting on-site equipment and hazardous areas: thermocouple temperature sensor
0District1District2District;IIATheIIBTheIIC
●Explosion proof certification parameters
Explosion proof grade mark:IIC
***Great safety voltage(Um):250VAC/DC
(terminal1-2) Uo: 4.6V Io: 40mA Po: 0.05W Lo: 14 mH Co: 100μF
(terminal2-3) Uo: 4.6V Io: 290mA Po: 0.34W Lo: 0.21mH Co: 100μF
4Model code

5、 Terminal wiring diagram