1、 Description
①MS6902Signal input(HART)Isolation safety barrier, distribution of current signals for two-wire transmitters. The isolation safety barrier provides isolated power voltage to the two-wire intelligent transmitter connected to the hazardous site and converts the voltage generated by the transmitter4~20mAAfter signal isolation conversion, it is transmitted to the safety zone control system or other intelligent instruments.
②This product supportsHARTBidirectional communication of digital signals.
②The isolation safety barrier is powered by an independent DC power supply-input-Isolation between outputs.
2、 Characteristics
●Distribute power to the on-site two-wire transmitter
●Two wire transmitter signal4~20mAIsolation transmission,dual input,dual output
●supportHARTCommunication protocol passed
●coordinateDCS/PLCWaiting for the application of control systems or other unit combination instruments.
●Connect to control system: various modelsDCS/PLCofAICard, receiving active signals4~20mASignal.
●Suitable for connected field devices: two-wire intelligent system( HART)Delivery device.
●Equipment is allowed to be located in hazardous areas:0District1District2District;IIADistrictIIBDistrictIICDistrict.
●Installation and terminal wiring:35mmstandardDINRail card installation; The terminal wiring adopts a spring type compression connection.
3、 Technical specifications
●Product model:MS6902 |
Stable time:≤3s ***High safety voltage (Um): 250VAC/DC (Terminals 2-3, 4-5) Uo: 26.2V Io: 127mA Po: 0.83W Lo: 1.4mH Co: 0.05 μ F (Terminal 1-2) Uo: 7.2V Io: 3.7mA Po: 7mW Lo: 2.4mH Co: 4 μ F
|
4、 Model selection

5、 Dimensions and installation diagram
●install
1.35mmstandardDINRail card installation. Please pay attention to the stability and firmness of the card position during installation.
2.Install vertically as much as possible to facilitate heat dissipation inside the instrument.
●Typical applications
1. Suitable for isolating and converting on-site signal inputs: signaltwoEntering and exiting.
2. Suitable for devices connected to the site: two-wire or three wire non intelligent transmitters, active current signals.
3. The area where the on-site equipment is located:0District1District2DistrictIIADistrictIIBDistrictIICDistrictT4~T6Dangerous zone.
4. Safety barrier output connection: can be connected to unit combination instruments andDCS/PLCWaiting for the system to be used in conjunction.
●External dimensions
Width (thickness)×tall×Deep=16×116×110(mm)
6、 Terminal wiring diagram
●Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed2.5mm2Multiple bundles or single stranded cables.