1、 Characteristics
●Input the DC signals of various intrinsic safety devices at hazardous sites.
●Standard analog signal electrical isolation.
●Linearization conversion output, selectable4~20mAperhaps1~5VSignal and other required DC signals.
●Modular core design, with digital calibration internally, eliminating the need for zero and full adjustment potentiometers, and automatic compensation for temperature drift.
●Equipped with a working power indicator light.
●Dual channel, two isolated inputs and two isolated outputs, intrinsic safety input circuit[Exia]IICInput circuit short circuit protection.
●Plug and unplug terminal block,DINRail card installation.
2、 Description
①MS6054DC signal input isolation safety barrier is used to isolate and limit the DC signal input connected to hazardous areas, convert it into standard process signals, and output them to the control system or other intelligent instruments in the safety zone.
②This isolated safety barrier requires independent power supply, with electromagnetic isolation between the power supply input circuit output circuit.
3、 Technical specifications
●Product model:MS6054 |
●performance index ***High safety voltage (Um): 250VAC/DC (Terminals 1-2, 4-5) Uo: 7.2V Io: 3.7mA Po: 7mW Lo: 2.4mH Co: 4 μ F
|
4、 Model selection

5、 Dimensions and installation diagram
●install
1.35mmstandardDINRail card installation. Please pay attention to the stability and firmness of the card position during installation.
2.Install vertically as much as possible to facilitate heat dissipation inside the instrument.
●Typical applications
1. Suitable for isolating and converting on-site signal inputs: signaltwoEntering and exiting.
2. Suitable for devices connected to the site: two-wire or three wire non intelligent transmitters, active current signals.
3. The area where the on-site equipment is located:0District1District2DistrictIIADistrictIIBDistrictIICDistrictT4~T6Dangerous zone.
4. Safety barrier output connection: can be connected to unit combination instruments andDCS/PLCWaiting for the system to be used in conjunction.
●External dimensions
Width (thickness)×tall×Deep=16×116×110(mm)
6、 Terminal wiring diagram
●Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed2.5mm2Multiple bundles or single stranded cables.