1、 Characteristics
●Two sets of intrinsically safe devices with graded control commonly used to drive hazardous sites, with loads up to750Ω.
● 4~20mAInput, isolated output4~20mA.
●Modular core design, with digital calibration internally, eliminating the need for zero and full adjustment potentiometers, and automatic compensation for temperature drift.
●Equipped with a working power indicator light.
●Dual channel, two isolated inputs and two isolated outputs, intrinsically safe output circuit[Exia]IICOutput circuit short circuit protection.
●Plug and unplug terminal block,DINRail card installation.
2、 Description
①MS6049Signal output isolation safety barrier is a device that uses two independent input channels to connect signals from regulators or operators located in the safety zone4~20mAThe signal is transmitted through this isolated safety barrier to reproduce and drive two sets of electrical systems located at the hazardous site(I/P)Transformers, valve positioners, various linear actuators, display devices, and other intrinsic safety instruments.
②This isolated safety barrier requires independent power supply, with electromagnetic isolation between the power supply input circuit output circuit.
3、 Technical specifications
●Product model:MS6049 |
Temperature drift:±0.015%/℃ ***High safety voltage (Um): 250VAC/DC (1-2, 4-5) Uo: 24V Io: 151mA Po: 0.91W Lo: 1.1mH Co: 0.09μF
|
4、 Model selection

5、 Dimensions and installation diagram
●install
1.35mmstandardDINRail card installation. Please pay attention to the stability and firmness of the card position during installation.
2.Install vertically as much as possible to facilitate heat dissipation inside the instrument.
●Typical applications
1. Suitable for isolating and converting on-site signal inputs: signaltwoEntering and exiting.
2. Suitable for devices connected to the site: two-wire or three wire non intelligent transmitters, active current signals.
3. The area where the on-site equipment is located:0District1District2DistrictIIADistrictIIBDistrictIICDistrictT4~T6Dangerous zone.
4. Safety barrier output connection: can be connected to unit combination instruments andDCS/PLCWaiting for the system to be used in conjunction.
●External dimensions
Width (thickness)×tall×Deep=16×116×110(mm)
6、 Terminal wiring diagram
●Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed2.5mm2Multiple bundles or single stranded cables.