1Laboratory drug warehouse renovationOverview:
The construction standards for hazardous waste rooms shall comply with the "Pollution Control Standards for Hazardous Waste Storage" (GB18597-2001) (revised in 2013).
Specification: The specifications involved in the collection, storage, and transportation of hazardous waste are the "Technical Specifications for the Collection, Storage, and Transportation of Hazardous Waste" (HJ2025-2012).
Guidelines: Guidelines for Environmental Impact Assessment of Hazardous Waste in Construction Projects.
Requirements for hazardous waste transfer management: "Management Measures for Hazardous Waste Transfer Couplets".
Management requirements for hazardous waste generating enterprises: "Standardized Management Index System for Hazardous Waste" (Environmental Office [2015] No. 99).

IILaboratory drug warehouse renovationBasic equipment configuration:
serial number |
Equipment or system name |
unit |
quantity |
1 |
Explosion proof electrical system |
set |
2 |
2 |
Explosion proof temperature and humidity system |
set |
2 |
3 |
Explosion proof ventilation system |
set |
2 |
4 |
Environmental purification system |
set |
2 |
5 |
Automatic fire extinguishing system |
set |
2 |
6 |
Lightning protection and anti-static system |
set |
2 |
7 |
Emergency equipment cabinet |
set |
2 |
8 |
Environmental monitoring linkage system |
set |
2 |
|
9 |
Explosion proof monitoring system (explosion-proof camera, monitoring host, storage hard drive, switch, 55 inch LCD screen, etc.) |
set |
2 |
10 |
Oxygen content detection device |
set |
2 |
11 |
Strong acid and strong alkali corrosion-resistant storage cabinet |
set |
15 |
12 |
Intelligent flammable and explosive storage cabinet |
set |
2 |
13 |
Intelligent Toxic Substance Storage Cabinet |
set |
2 |
14 |
Pull rod reagent transfer box |
a |
6 |
15 |
Ground epoxy resin electrostatic spraying (40m2, coating thickness 2mm) |
item |
2 |
16 |
Including lamp, switch disassembly and assembly, wire replacement, anti-theft door installation, ventilation network installation. |
|
|
3、 Equipment configuration instructions:
serial number |
System Name |
Technical parameters and requirements |
|
1 |
Explosion proof electrical system |
Install explosion-proof distribution box and explosion-proof weak current control box outside the explosion-proof door of the reagent temporary storage warehouse, install OPPO/embedded/aviation vehicle aluminum lamp body indoors, thicken explosion-proof transparent glass cover explosion-proof emergency light 1, explosion-proof emergency exit indicator light 1, explosion-proof socket 12, explosion-proof level EXd Ⅱ BT4Gb. |
|
2 |
Explosion proof temperature and humidity system |
Adopting explosion-proof cabinet air conditioning with cooling and heating capabilities, 3P, energy efficiency level 2 or above, the air conditioning operates within an ambient temperature range of -25 ℃ -55 ℃, ensuring that the temperature inside the storage room is controlled between 18-30 ℃. |
|
3 |
Explosion proof ventilation system |
Equipped with explosion-proof corrosion-resistant fans and sensors, the exhaust system has a linkage function with the control system. Once the TVOC concentration in the room or safety cabinet exceeds the standard, the exhaust system will be immediately activated in conjunction. |
|
4 |
Environmental purification system |
Low noise filtering integrated activated carbon adsorption box, three-layer filtration, pipeline made of high-quality corrosion-resistant PP material. |
|
5 |
Automatic fire extinguishing system |
Configure 2 sets of 4kg hanging heptafluoropropane automatic fire extinguishing devices. When the indoor temperature reaches 68 ℃, the temperature sensing element will automatically explode. |
|
6 |
Lightning protection and anti-static system |
Install a wall mounted electrostatic discharge device on the exterior wall of the warehouse, equipped with an over limit alarm function. Surge protectors (In=20KA, Imax=40KA) are installed inside the distribution cabinet, and all equipment and pipelines are grounded for equipotential connection. The grounding wires of all reagent temporary storage warehouses must be well connected to the grounding system of the room. Strictly follow GB50057 "Code for Design of Lightning Protection of Buildings" and GB50343-2012 "Technical Code for Lightning Protection of Building Electronic Information Systems Standard design and construction. |
|
7 |
Emergency equipment cabinet |
Set up an emergency protective equipment box, which is equipped with personal protective equipment (including 1 set of protective clothing, 2 sets of gas masks, 2 sets of respirators, 4 protective masks, 2 sets of protective gloves, 2 sets of goggles, 2 pairs of chemical resistant rubber boots, 1 cotton swab, 1 adsorption pillow, and 1 waste storage bin); One first aid kit (equipped with bandages, burn medicine, and other emergency supplies); Firefighting equipment (including 2 dry powder fire extinguishers, 2 water-based fire extinguishers, 2 fire extinguishers, 1 firefighting sandbox, and 2 tool shovels). |
|
|
anti-theft door |
1.4 * 2.5 meters double lock/outward opening/1. Steel safety door 2. The thickness of the storefront is 1.0mm, the thickness of the door frame is 1.5mm, the width of the door leaf is 7cm, and the opening angle is 180 degrees 3. Clear hinge, double lock without bottom frame 4. Color wood grain transfer printing 5. Mechanical lock, double lock |
|
8 |
Environmental monitoring linkage system |
The intelligent monitoring platform provides the industry's most advanced software and hardware support, equipped with a touch screen that can display the environmental status inside the temporary storage warehouse and the exhaust emission outlet through the touch screen. |
|
9 |
Explosion proof monitoring system |
Equipped with 3 sets of far-infrared electronic monitors for monitoring, the monitors have high-definition night vision function and can be viewed at any time on mobile phones or computers; The monitoring system has a memory function. |
|
10 |
Oxygen content detection device |
Measurement range: 0-30% VOL, measurement accuracy: 0.01% VOL, power supply: 24V |
|
|
shelf |
1. The external dimensions are 1500mm in length, 500mm in width, and 2000mm in height, with 6 layers and a load-bearing capacity of 200KG per layer. 2. Beam made of p-type steel 40 * 60 * 1.0mm, column made of C-shaped steel 40 * 80 * 1.0mm, and plate frame made of 0.5mm. 3. Surface electrostatic spraying. 4. Durability and strength comply with the national standard GB/T 10357.5-2011. 5. The stability of the cabinet complies with the national standard GB/T 10357.4-2013. |
|
|
※ PP tray |
65.5cm*49.5cm*5cm, Welding of polypropylene sheet, resistant to high temperature, acid and alkali, corrosion, with a thickness of 5mm. Provide third-party testing report for PP sheet. |
|
|
Institutional Listing |
1. Appearance size: 600 * 400mm. |
|
|
Safety warning signs |
PVC waterproof 15 * 20cm |
|
11 |
Strong acid and strong alkali corrosion-resistant storage cabinet |
1. Specification: Reference size (H) 1800 * (W) 900 * (D) 450 mm 2. Overall material: Cabinet: Porcelain white, 8mm PP board. Cabinet door: Four doors, all with observation windows, 15mm PP board. Window: 5mm PVC board. Layer board: Porcelain white PP board, adjustable second board, with vertical edges around. 3. Accessories: Equipped with four safety and anti-corrosion locks. Door handles and hinges: made of PP flame-retardant material that has been injection molded. Screw: Made of stainless steel 304 material. Warning label: The cabinet door is labeled with a prominent "corrosive" warning sign. 4. Provide one MSDS data box, made of polypropylene with a thickness of 1.0mm. |
|
12 |
Intelligent flammable and explosive storage cabinet |
1. The cabinet is yellow in color, with a shell made of 1.20mm first grade cold-rolled steel plate and a base made of 2.0mm first grade cold-rolled steel plate. The inner liner is made of porcelain white PP board, and an adjustable fireproof air inlet is set on the right side of the cabinet bottom. There is a PP polypropylene adjustable air valve, and the bottom layer has a filling chamber (leakage tank) for storing yellow sand. The top of the cabinet has a detachable function. 2. Intelligent control system: LCD touch screen microcomputer control system, real-time temperature and humidity environment monitoring, fan monitoring, VOC concentration environment monitoring system and integrated alarm system, microcomputer time control switch, can automatically turn on and off the fan according to the user's set time. 3. Temperature, humidity and TVOC alarm device: High precision probes are selected to accurately monitor the concentration of harmful gases TVOC and temperature and humidity inside the cabinet in real time. Control range: temperature 0-150 ℃, humidity 0-99.9% RH, VOC concentration 0-500PPM. Digital display settings and measurement values, capable of timed ventilation of the cabinet; If the VOC concentration and temperature/humidity inside the cabinet exceed the set measurement values, an immediate alarm will be triggered and the fan will be started. 4. High strength laminated board: 3 pieces of PP stepped movable laminated board, with PP integrated anti-corrosion leakage tray at the bottom, and a 3cm high leakage movable orifice plate embedded in the leakage tank. 5. Anti static function: It adopts a three-point linkage lock that can be opened 180 degrees and effectively prevents static electricity generation. It is equipped with an anti-static grounding device. 6. Remote monitoring function: The product control system comes standard with RS232 or 485 communication interfaces, which can seamlessly interface with laboratory remote management software such as specialized safety management platforms through communication protocols. It can remotely monitor the concentration, temperature, and humidity of harmful gases TVOC in the safety cabinet in real time, and can be further upgraded to achieve remote real-time transmission of weighing, vibration, authorization records, door opening and closing records, monitoring videos, and dynamic information such as leakage and alarms. It is also capable of providing real-time monitoring of hazardous gas TVOC concentration, temperature, and humidity in the safety cabinet The laboratory equipped with network conditions provides various wireless transmission functions. |
|
|
|
1. The cabinet is blue, the shell is made of 1.20mm first grade cold-rolled steel plate, the base is made of 2.0mm first grade cold-rolled steel plate, and the inner liner is made of porcelain white PP plate. There is an adjustable fireproof air inlet with PP polypropylene adjustable air valve on the right side of the cabinet bottom. The bottom layer has a filling chamber (leakage tank) for storing yellow sand, and the top of the cabinet has a detachable function. |
|
|
|
2. Intelligent control system: LCD touch screen microcomputer control system, real-time temperature and humidity environment monitoring, fan monitoring, VOC concentration environment monitoring system and integrated alarm system, microcomputer time control switch, can automatically turn on and off the fan according to the user's set time. |
|
|
|
3. Temperature, humidity and TVOC alarm device: High precision probes are selected to accurately monitor the concentration of harmful gases TVOC and temperature and humidity inside the cabinet in real time. Control range: temperature 0-150 ℃, humidity 0-99.9% RH, VOC concentration 0-500PPM. Digital display settings and measurement values, capable of timed ventilation of the cabinet; If the VOC concentration and temperature/humidity inside the cabinet exceed the set measurement values, an immediate alarm will be triggered and the fan will be started. |
13 |
Intelligent Toxic Substance Storage Cabinet |
4. High strength laminated board: 3 pieces of PP stepped movable laminated board, with PP integrated anti-corrosion leakage tray at the bottom, and a 3cm high leakage movable orifice plate embedded in the leakage tank. |
|
|
|
5. Anti static function: It adopts a three-point linkage lock that can be opened 180 degrees and effectively prevents static electricity generation. It is equipped with an anti-static grounding device. |
|
|
|
6. Remote monitoring function: The product control system comes standard with RS232 or 485 communication interfaces, which can seamlessly interface with laboratory remote management software such as specialized safety management platforms through communication protocols. It can remotely monitor the concentration, temperature, and humidity of harmful gases TVOC in the safety cabinet in real time, and can be further upgraded to achieve remote real-time transmission of weighing, vibration, authorization records, door opening and closing records, monitoring videos, and dynamic information such as leakage and alarms. It also provides multiple wireless transmission functions for laboratories that do not have network conditions. |
|
14 |
Pull rod reagent Transfer box |
Reference external dimensions H * W * D (mm): 350 * 230 * 300 |