JUMO Jiumao Controller AQUIS touch S 202581
Features: 5.5 'touch screen; 14 inputs and outputs as basic devices; 13 slots for input and output modules; Modular structure; Customer specific process images; Data monitor and registration function; A web browser with online visualization capabilities; Timer function; Mathematical and logical functions; Set up programs, PC evaluation software (PCA3000), PCA communication software (PCC); Calibration program, calibration log, calibration timer; Can also connect up to 6 JUMO DigiLine sensors

| category | key parameters |
|---|---|
| Basic model | 202581 (AQUIS touch S, wall mounted, IP67 protection) |
| Analyze input | 4 expansion slots, supporting direct connection of pH/ORP, conductivity (contact/sensing), NH3, dissolved oxygen and other sensors |
| Extended measurement | 21 universal inputs (4-20 mA/0-10 V, Pt100/Pt1000/NTC), 2 pulse frequency inputs (≤ 300 Hz/10 kHz) |
| output capability | Up to 17 configurable switch outputs (relays/transistors), supporting control, alarm, and timing outputs |
| control function | 4-channel independent PID control loop, supporting P/PI/PD/PID and two-state/tri state control, with parameter self-tuning |
| Display and Record | 5.5-inch TFT color touch screen, paperless recording (data storage/trend playback), USB export |
| communication interface | USB host/slave Modbus - RTU、PROFIBUS - DP、 Ethernet (web server, email alarm) |
| Power supply and installation | 100–240 V AC, Wall mounted, protection level IP67 (front panel) |
Modular expansionFour analysis input slots can be flexibly matched with modules such as pH, conductivity, and NH3. The universal input is compatible with almost all industrial standard signals and is suitable for multi parameter parallel monitoring.
Intelligent control and recording4-channel PID control supports complex process closed-loop, paperless recording of traceable measurement data, alarm support for email push, meeting compliance traceability requirements.
High adaptability communicationEthernet supports web remote configuration and data reading, Modbus RTU/PROFIBUS-DP is compatible with factory SCADA systems, and USB interface facilitates local parameter backup/recovery.
Anti interference and ease of useIP67 protection is suitable for harsh industrial environments, with pure text touch operation and built-in calibration wizard, reducing the threshold for operation and maintenance.
sceneMonitor the DO (2-4 mg/L), pH (6.5-8.0), temperature (15-35 ℃), and reflux flow rate of the biochemical tank, and link the aeration fan, dosing pump, and reflux pump to ensure the efficiency of nitrogen and phosphorus removal.
configuration
Controller: 202581 (pH/ORP, conductivity, dissolved oxygen module, 4-channel PID).
Sensors: JUMO dissolved oxygen electrode, pH electrode, Pt100 temperature transmitter, electromagnetic flowmeter (pulse output).
Executors: Aeration fan (PID1), alkali dosing pump (PID2), reflux pump (flow interlock).
control logic
DO<2 mg/L → PID1 increases fan frequency; PH<6.5 → PID2 starts alkaline dosing; Temperature>35 ℃ → Alarm and linkage cooling.
Paperless recording of DO/pH/temperature trends, Ethernet upload to SCADA, email push of over limit alarms.
effectThe effluent compliance rate has been increased to 99.5%, aeration energy consumption has been reduced by 22%, and maintenance manpower has been reduced by 60%.
sceneMonitor the conductivity (≤ 1 μ S/cm), pH (5.0-7.0), temperature, and tank level of RO reverse osmosis and EDI modules to ensure GMP compliance and water quality stability.
configuration
Controller: 202581 (conductivity, pH module, 2-channel PID).
Sensors: JUMO inductive conductivity sensor, pH electrode, input type liquid level transmitter.
Executors: RO flushing valve (triggered by conductivity exceeding the standard), EDI power supply (PID regulation), liquid level interlock water replenishment valve.
control logic
RO water conductivity>1 μ S/cm → automatic flushing; EDI effluent pH deviates from 5.0-7.0 → PID regulates power supply current.
Paperless recording of key parameters, supporting data export for GMP audit tracking.
effectThe water quality qualification rate is 100%, the flushing frequency is reduced by 18%, and the audit traceability efficiency is improved by 80%.
sceneThe CIP station of the dairy factory monitors the temperature of the cleaning solution (60-80 ℃), alkali concentration (2% -5%), and tank liquid level, and links heating, dosing, and inlet valves to ensure cleaning effectiveness and equipment safety.
configuration
Controller: 202581 (conductivity, temperature module, 2-channel PID).
Sensors: Contact conductivity sensor (for concentration measurement), PT100 temperature transmitter, capacitive level switch.
Actuators: heater (PID1), alkali dosing pump (PID2), inlet valve (liquid level interlock).
control logic
Temperature < 60 ℃ → Heating; >80 ℃ → Stop; Concentration<2% → Add medication; Liquid level < 20%/> 90% → Alarm and close valve.
One click switching of cleaning program on touch screen, paperless recording of cleaning curve.
effectCleaning temperature fluctuation ± 1 ℃, concentration control accuracy ± 0.2%, no dry operation/overflow accidents.
Module matchingSelect the analysis module based on parameter requirements (such as pH+conductivity+dissolved oxygen), with universal input covering auxiliary signals such as temperature and pressure.
Communication ExpansionWhen remote monitoring is required, Ethernet and web servers are enabled, Modbus RTU is adapted to PLC/SCADA, and email alarms improve response speed.
Load adaptationWhen the output load is greater than 5 A, an intermediate relay should be added to protect the controller contacts.