Welcome Customer !

Membership

Help

Changsha Foside Automation Technology Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Changsha Foside Automation Technology Co., Ltd

  • E-mail

    judy.yao@fuside-auto.com

  • Phone

    18175911197

  • Address

    No. 900 Gaojiapo Road, Furong District, Changsha City

Contact Now

Intelligent transmitter (B-type junction box)

NegotiableUpdate on 11/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

■ Two types of thermal resistance signal input (see Table 7401-1) ■ Eight types of thermocouple signal input (see Table 7401-1) ■ 4-20mA analog signal output ■ Optional digital communication HART protocol ■ Low energy consumption, high reliability, strong anti-interference ability ■ Built in cold junction compensation, nonlinear correction circuit ■ Can be combined into an integrated thermocouple and thermal resistance with transmitter function

Product Details

  • Product Application

    ■ Installed inside the B-type junction box of the thermal resistor

    ■ Installed inside the thermocouple B-type junction box

    Resistance (Ω) signal analog transmitter output

    Voltage (mV) signal analog transmitter output for industries such as pharmaceuticals, food, power, metallurgy, glass, chemical, rubber, and textiles

  • Technical data

    input signal Thermistor: Pt100, Cu50
    Thermocouples: B, R, S, K, N, E, J, T
    output signal 4~20mA
    Digital Communication HART protocol (optional)
    output characteristics Linear with temperature
    accuracy class ≤0.1%F·S
    power supply voltage 12~40V DC
    response time ≤1s
    alarm current Damaged or disconnected output 3.9mA or 22mA
    Maximum Load 7.5V (power supply), 0.022A (current output)
    Circuit limitations ≤22mA
    sampling rate continuous measurement
    Condensation allow
    Protection level IP00/IP54 (open/inside junction box)
    Operating Temperature -40~85℃
    relative humidity 5%~95%
    ambient temperature -40~100℃
    mechanical vibration 4g/2~150Hz
    Configuration programming Online adjustment through PAD controller or PC programming
  • Instructions