- Phone
-
Address
Building 3, Jibang Technology Park, No. 8 Jishan New Road Street, Tianhe District, Guangzhou City
Guangzhou Dongyi Automation Technology Co., Ltd
Building 3, Jibang Technology Park, No. 8 Jishan New Road Street, Tianhe District, Guangzhou City
Intelligent manipulator with forward and reverse control continuous output typeDivided into Q-type manipulator and D-type manipulator. The Q-type operator operates in analog continuous output mode and can also set positive and negative effects; The D-type manipulator has forward and reverse switch output modes, which can be manually positioned or directly controlled for forward and reverse rotation. Suitable for manual positioning control of various actuators. One input signal used for measuring process signals or measuring valve opening position. Can be equipped with DC current, DC voltage, thermistor, thermocouple, etc. Dual display windows display measurement/feedback signals and operational output values respectively. Welcome to consult with all users.
Dimensions
1. 160 × 80 × 125mm horizontal opening size: 152 × 76
2. 80 × 160 × 125mm vertical opening size: 152 × 76
3. 96 × 96 × 112mm hole size: 92 × 92
4. 96 × 48 × 82mm horizontal opening size: 92 × 45
5. 48 × 96 × 82mm vertical opening size: 92 × 45
Intelligent manipulator with forward and reverse control continuous output typeproductIntroduction
Operators are divided into Q-type operators and D-type operators. The Q-type operator operates in analog continuous output mode and can also set positive and negative effects; The D-type manipulator has forward and reverse switch output modes, which can be manually positioned or directly controlled for forward and reverse rotation. Suitable for manual positioning control of various actuators.
One input signal used for measuring process signals or measuring valve opening position. Can be equipped with DC current, DC voltage, thermistor, thermocouple, etc. Dual display windows display measurement/feedback signals and operational output values respectively.
Signal output can be directly operated through button operation. The operation output has upper and lower limit limiting functions.
Optional external power supply.
Optional alarm output function
Optional measurement feedback transmission output function.
Optional communication interface for reading data.
Basic specifications
project |
specification |
|
power supply voltage |
ACpower supply |
100~240 V AC 50/60 Hz |
AC/DCpower supply |
10~24V AC 50/60 Hz;10~24V DC |
|
power consumption |
ACpower supply |
7 VAbelow |
AC/DCpower supply |
AC:6 VAfollowing;DC:5Wbelow |
|
Allowable voltage variation range |
The voltage of the power supply90%~110% |
|
insulation resistance |
≥100MΩ(500V DC MEGABenchmark) |
|
insulation strength |
2000V AC (Test conditions:50/60Hz,1Minutes) |
|
anti-interference |
IEC61000-4-2(Electrostatic discharge))Grade III IEC61000-4-4(Electric Fast Transient Pulse Group), Level III IEC61000-4-5(Surge), Level III |
|
Protection level |
IP65(Product front panel protection)(GB/T42-2008) |
|
runtime environment |
ambient temperature |
-30~60℃(Save:-40~65℃) |
ambient humidity |
35~85 %R•HNo condensation |
|
Installation location |
Indoor, height<2000m |
|
■ Enter specifications
project |
specification |
Measure and control speed |
0.1second |
basic error |
±0.2 %F•S |
display range |
-1999~9999 |
Display specifications |
double4bitLEDDisplay (Main Display Window)+Second display window) |
Æ Note:Please refer to the input signal type description for details Input signal and display explain.
■SVOperation output specifications
project |
specification |
|
D1 |
relay output(Single normally open)(250V AC/3A) |
DType operator |
D2 |
OCGate output (voltage should be less than)24V DCThe current should be less than20mA) |
|
Q1 |
current output(4~20)mAThe(0~10)mAThe(0~20)mA |
QType operator Photoelectric isolation, Resolution:1/10000Load capacity:600Ω |
Q2 |
voltage output(0~5)VThe(1~5)V |
|
Q3 |
Voltage output(0-10)V |
|
■ Optional specifications
project |
specification |
||||
|
alarm output |
160×80size |
T1~T2 |
1~2The output of the alarm relay is normally open+Normally closed dual contacts |
250V AC/3A resistive load |
|
96×96size |
T1~T2 |
1~2Point alarm relay output, all with normally open contacts |
|||
96×48size |
T1~T2 |
1~2Point alarm relay output, all with normally open contacts |
|||
PVtransmitter output |
A1 |
current output(4~20)mAThe(0~10)mAThe(0~20)mA |
Photoelectric isolation, Resolution:1/10000Load capacity:600Ω |
||
A2 |
voltage output(0~5)VThe(1~5)V |
||||
A3 |
Voltage output(0-10)V |
||||
|
communication interface |
MS1 |
RS232interface |
Photoelectric isolation, Response time: less than500μS(Measurement value) Communication protocol selected through software |
||
MS2 |
RS485interface |
||||
|
External supply power supply |
B1 |
24V±5% 50mAbelow |
|||
B2 |
12V±5% 50mAbelow |
||||