- Phone
-
Address
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
Wuhan Ultra High Voltage Power Technology Co., Ltd
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
| Power input voltage | 220V±10% 50Hz |
| Console output voltage | 0-250V |
| Console output current | 12A |
| Rated output voltage | 100kV |
| Rated output capacity | 5kVA |
| maximum range | 29.9mA |
| Range of leakage current with trip system | ≥12mA |
| Voltage measurement error | ± 1%+3 words |
| Leakage current measurement error | ± 1%+3 words |
| Leakage current resolution | 0.01mA |
| Digital display timing | 99 minutes of free setting |
| ambient temperature | -10℃-40℃ |
| humidity | ≤90%RH, No condensation, instrument does not flicker |
| External dimensions of control box | 400×300×550mm3 |
| External dimensions of the test bracket | 1000×800×1000mm3 |
| Control box weight (kg) | 25 |
| Test bracket weight (kg) | 20 |
1Insulating boots and gloves testing equipmentIt is possible to conduct tests on 8 insulated boots or gloves simultaneously and measure the leakage current of each sample.
2. The insulation shoe test adopts a dry test method with small steel balls placed inside, which eliminates the traditional practice of pouring water into the shoe for testing and making it difficult to dry after the test is completed.
3. High and low voltage separation, leakage current is transmitted back to the control box using anti-interference wireless transmission technology, greatly protecting personal safety.
4. Each test sample has a breaking mechanism. When any one of the circuits breaks down or exceeds the set leakage current value, the test sample will automatically detach from the test without affecting the testing of other samples.
5Insulating boots and gloves testing equipmentAdopting a 7-inch TFT touch screen LCD Chinese character display, it displays a large amount of information. One screen simultaneously displays parameters such as test voltage, 8-channel high-voltage leakage current, perpetual calendar, timing time, and Chinese character prompt content.
6. Adopting a DC motor to control the voltage regulator's boosting process, fully automatic voltage withstand test is conducted. After the start of the experiment, the instrument automatically closes and boosts the voltage at the required speed according to the national standard. When the predetermined voltage is reached, the timer starts and the test voltage is maintained. When the timer reaches, the voltage automatically drops, and when it reaches zero, the power is automatically turned off, indicating the end of the experiment. At the same time, the leakage current of each test sample is displayed, and the test results are automatically saved.
7. The insulation boot test has a dedicated stainless steel grounding tray, and the insulation glove test has a dedicated stainless steel container for easy operation.
8. The transformation ratio of the test transformer can be freely set, and it can also be matched with the customer's existing transformer.
9. It has overcurrent protection function.