- Phone
-
Address
1118 Jintong Road, Shanghai
Shanghai Zhengyuan Electric Technology Co., Ltd./Shanghai High Voltage Tester
1118 Jintong Road, Shanghai
Introduction
High voltage voice wireless phase analyzerThe main advantage is the removal of the leads connecting the two power grids (power sources) at both ends, which can pass through walls and partitions (boards) at a distance of up to 20m, without being restricted by any terrain or facility structure, thus improving safety,
For convenience, only one person needs to operate and one person needs to supervise.
The instrument sends digital signals to the receiving end through a wireless transmission module during operation, thereby reducing interference and errors, greatly improving the performance of the instrument.
In use, first operate the receiving device on the conductor of the tested power grid, and then operate the receiving device on another conductor of the tested power grid. If the phases of the two tested power grids are the same, repeat the language prompt: "Phase is the same". If the phases of the two tested power grids are different, repeat the language prompt: "Attention, phase is different".
The insulation operation tube (material) is selected from the three ball brand moisture-proof insulation tube produced by the military industry enterprise, which meets the EC/1C78 standard and has the characteristics of moisture-proof, high voltage resistance, impact resistance, bending resistance, etc
High voltage voice wireless phase analyzerTechnical Parameters and Component Function Description
1. Technical parameters
Scope of use: Voltage levels such as 6-35kV, 110KV, 220KV, 500KV, etc
Test condition: Live parts of the circuit or equipment
Ground clearance: less than 15 meters
Large distance between transmitters: less than 30 meters
Equipment operating frequency: 1.2GHz
2. Transmitter
The external dimensions of transmitter N0.1 and transmitter N0.2 are Φ 60 × 120mm, with a power supply of 8.4V (nickel hydrogen rechargeable battery)
3. Receiver dimensions: 235 × 130 × 43mm
Power battery: 12V nickel hydrogen rechargeable battery
The functions of each component of the receiver
4. When using 2 insulation rods with a total of 4 sections, connect the two sections together for use
Scope of application: Voltage levels such as 6-35kV, 110KV, 220KV, 500KV, etc
The insulation rod is made of epoxy resin, with a length of 2 meters per rod (each rod consists of two sections). It is a professional manufacturer of insulation rods, and its length and test voltage comply with the IEC 60855 and GB113398-92 "General Technical Conditions for Insulated Rod Used in Live Working" of the Electrotechnical Commission.
Reference Table for Power Frequency Withstand Voltage Test of Insulated Rod
Voltage level insulation rod effective insulation length 1 minute power frequency withstand voltage
10kV and below 700mm 45kV
35kV 900mm 95kV
110kV 1300mm 220kV
220kV 2100mm 440kV
Insulated rods should undergo regular power frequency withstand voltage tests and visual inspections, and should be free of scratches, fractures, and other abnormalities. Store in a dry and ventilated place