HWL2 (Q) - J2-30 Enhanced Parallel Constant Power Electric Tracing BeltProduct Usage
Special electric heat tracing cable for antifreeze of instrument pipelines in chemical plants
All electric tracing cables for lime water, gypsum water, process water, and other gas heating pipelines in the gas vacuum chamber heating engineering system, as well as tracing insulation, anticoagulation, antifreeze, heating, and tracing cables for industrial enterprise pipelines and storage tanks.
3、 Construction of electric heating cable
(1) Design drawings
Before construction, there should be a complete design drawing, which should include the following information:
1. The line number and power supply point are represented by rectangular grids.
2. The required heating cable model and length for the circuit. (Unit: meters)
3. The required length of heating cable per meter of pipeline length (unit: meter) is the winding coefficient.
4. The length of heating cable required for each valve. (Unit: meters)
5. List of supporting materials and accessories for the heat tracing system.
6. List of accessories for temperature control system.
7. List of materials required for construction.
8. Design considering parameters and specifications of insulation materials used.
(2) Preparation work before construction
(A) Pipeline system
1. The pipeline system and equipment have been constructed.
2. The anti rust and anti-corrosion coating has dried completely.
3. The construction specifications for pipeline systems are consistent with those shown in the design drawings.
4. File off all burrs and sharp corners.
(B) Heating cables and accessories
1. Is there any damage or breakage on the surface of the heating cable.
2. The insulation performance of the heating cable is good (the insulation resistance is required to be 20M when tested with a shaking table at 1000VDC).
3. The model and design requirements of the electric heating belt and all accessories are consistent
HWL2 (Q) - J2-30 Enhanced Parallel Constant Power Electric Tracing BeltBasic Parameters
1. Maximum maintenance temperature: refers to the process temperature that the medium inside the pipeline needs to maintain, and generally should not exceed the values specified in this table.
2. Rated voltage: 220VAC
3. Normal insulation resistance: ≥ 20M Ω/100 meters
4. Dielectric strength: 2000VAC/50HZ/1min
5. Long term maximum temperature resistance: 205 ℃
6. Explosion proof mark: Exe Ⅱ T4
7. Protection level: IP56 IP65;