| Product Introduction |
GC-XB200 protector is suitable for voltages below AC660V; The low-voltage system with current ranging from AC5A to 800A adopts advanced design concepts and manufacturing processes, combined with the needs of domestic users for low-voltage circuit protection, measurement, and control, to develop low-voltage line protectors suitable for domestic users.
This protector provides a complete set of specialized solutions for low-voltage circuits, integrating control, protection, measurement, metering, and communication. It also offers functions such as remote automatic control, on-site direct control, panel indication, signal alarm, operation record, trip alarm record, and switch quantity record. It is widely used in many industries such as power, petrochemical, light industry, coal, paper, steel, metallurgy, etc.
| Product Features |
Rich measurement data, including phase voltage, line voltage, phase current, current phase angle, total active power, total reactive power, total apparent power, power factor, forward and reverse active/reactive energy, total active/reactive energy, etc;
Equipped with residual current protection function, it can provide more sensitive ground fault detection, fully ensuring safe operation and personal safety in low-voltage circuits;
Up to 9 active or passive switch inputs are provided for the connection of opening and closing signals, circuit breaker status signals, contactor status signals, and fault signals;
Equipped with AO output function, it can easily convert the measured quantities (three-phase voltage, three-phase current, power, power factor, frequency) in the low-voltage circuit into 4-20mA DC current, achieving the function of a conventional fully isolated transmitter;
Having the management and maintenance function of low-voltage circuits, recording the opening and closing time, frequency, and cumulative tripping times;
Equipped with SOE function, it can record up to the last 100 protection action information with time stamps;
Support optional Profibus DP protocol communication interface;
Equipped with remote communication function, supporting optional 2-channel RS-485 communication interface, using standard Modbus RTU communication protocol; Easy maintenance and management, displaying fault parameters, alarm information, status indicators, circuit breaker opening and closing times, tripping times, etc., facilitating fault analysis, production efficiency statistics, and selective and reasonable maintenance.
| TECHNICAL INDEX |
| environmental condition | ambient temperature | -20℃~+55℃ |
| storage temperature | -25℃~+70℃ | |
| atmospheric pressure | 70kPa~106kPa | |
| relative humidity | 5% to 95% (no condensation or freezing inside the product) | |
| Rating | Protective device working power supply | AC85~265V/DC110~370V。 |
| Current/voltage input |
Current circuit (external current transformer (MTA): 5A, 25A, 50A, 100A, 200A, 400A, 600A, 800A). |
|
| AC voltage (phase voltage): 220V, 380V, 660V | ||
| Frequency: 50Hz/60Hz | ||
| Switch node input | The switch quantity can be selected as active (AC/DC220V) node or passive dry node. |
|
| Relay contact output capacity | DO1~DO4: normally open relay, AC 250V/DC 30V, maximum allowable current for disconnection: AC/DC 5A; long-term allowable closing current: 5A |
|
DO5: normally open/normally closed relay, AC 250V/DC 30V, maximum allowable current for disconnection: AC/DC 5A; long-term allowable closing current: normally open point 5A, normally closed point 3A | ||
| AO output | Output range: (4-20) mA |
|
Load capacity: 500 Ω | ||
| Power consumption | AC voltage circuit: less than 0.75VA/phase (rated 220V) | |
| Protector power circuit: less than 5W | ||
| Overload capacity | AC current circuit: 2 times rated current, continuous operation | |
| 10 times the rated current, allowing for 10 seconds | ||
40 times the rated current, allowing 1 second | ||
AC voltage circuit: 1.2 times rated voltage, continuous operation | ||
1.4 times the rated voltage, allowing for 10 seconds | ||
| measurement accuracy | Measurement range of phase voltage | Measurement range 5V~660V |
| Current measuring range | (0.1-10) times the rated current; Remaining current: 10mA~1000mA | |
| measurement accuracy | Three phase current: ± 1% | |
| Three phase voltage: ± 1% | ||
Active power: ± 1.0% | ||
Power factor: ± 2.0% | ||
Active energy: ± 2.0% | ||
| Remaining current: ± 2.0% | ||
| Analog output (AO): ± 2.0% | ||
| Protection of fixed value error | Action value | Current: ± 200mA or ± 5% of the fixed value |
| Voltage: ± 2V or ± 3% of the fixed value | ||
| Action time | Within the range of 0s to 3s (including 3s), not exceeding 60ms | |
Within the range of 3s to 99.9s, not exceeding ± 5% of the set value | ||
| Within the range of 0s to 3s (including 3s), not exceeding ± 100ms | ||
3 seconds or more, not exceeding ± 5% of the calculated value |
| Outline dimension diagram |
Host module: standard TS-3 rail installation
Host module size: 125 × 90 × 62.5mm

Display module: external dimensions 100 × 70 × 38mm
Adopting embedded installation, with a hole size of 91 × 61mm
The display module and the host module are connected using a 1-meter standard Ethernet cable

| Wiring Terminal Diagram |

Conventional wiring terminal diagram

2-channel RS485 communication wiring terminal diagram