| Product Introduction |
The GC-WJ200B series microcomputer comprehensive protection and measurement device is suitable for the protection of transmission lines, bus tie switches, and other voltage levels ranging from 380V to 10kV.
As the basic equipment of power automation system, it has powerful communication function. The device adopts RS485 fieldbus and can optionally add an RJ45 Ethernet interface to ensure real-time and reliable information transmission.
Through the communication network, the GC-WJ200B series microcomputer comprehensive protection and measurement device sends all operational information, including telemetry, remote signaling, protection settings, etc., in real time to the first level SCADA system, and can receive commands such as protection settings modification, realizing the unmanned operation scheme of the substation.
Compliant with standard: DL/T478-2001 General Technical Conditions for Static Relay Protection and Safety Automatic Devices.
| Product characteristics |
|
|
|
|
| Model Selection |
GC-WJ200B1 microcomputer based line protection device
GC-WJ200B2 Microcomputer Transformer Protection Device
GC-WJ200B3 microcomputer capacitor protection device
GC-WJ200B4 microcomputer motor protection device
GC-WJ200B5 Microcomputer PT Monitoring Device
GC-WJ200B6 microcomputer circuit backup automatic switching protection device
GC-WJ200B7 microcomputer based busbar backup automatic switching protection device
| Selection List |

| TECHNICAL INDEX |
| Serial Number | Project/Name | unit | Parameter indicators | notes |
| 1 | ambient temperature |
℃ | 20±5 | |
| 2 | relative humidity |
% | 45~80 | |
| 3 | atmospheric pressure | KPa | 86~106 | |
| 4 | operation temperature | ℃ | -20~+60 | The average temperature within 24 hours shall not exceed+45 ℃ |
| 5 | Relative humidity at work | % | 95 | The maximum monthly average is below 95%, and there is no condensation on the surface of the casing |
| 6 | Rated voltage of AC power supply | V | 220 | -15%~+10% |
| 7 | AC power frequency | Hz | 50 | -1%~+1% |
| 8 | Rated voltage of DC power supply | V | 220/110 | |
| 9 | Allowable deviation of DC power supply | % | -20~+20 | |
| 10 | Ripple factor of DC power supply | % | Not greater than 5 | |
| 11 | Rated AC current | A | 5/1 | |
| 12 | Rated zero sequence current | A | 5/0.2 | Large grounding system 5A, small grounding system: 0.2A |
| 13 | Rated AC voltage | V | 100 | |
| 14 | Rated star voltage 3U0 | V | 100 | |
| 15 | DC circuit power | W | ≤8 | |
| 16 | AC voltage circuit | VA | ≤ 0.8/phase | |
| 17 | AC current circuit | VA | ≤ 0.8/phase | |
| 18 | Accurate working range of current | A | 0.5~100 | |
| 19 | Accurate working range of voltage | V | 1~160 | |
| 20 | DCS DC current range | mA | 4~20 | |
| 21 | Protection device setting error | % | <±3 | |
| 22 | Accuracy of current measurement | % | 0.5 | |
| 23 | Voltage measurement accuracy | % | 0.5 | |
| 24 | Power and electrical measurement accuracy | % | 2.0 | |
| 25 | capacity | A | 8 | Connect DC250V, 8A (pure resistive load) |
| 26 | working life | order | Action 100,00 | |
| 27 | insulation resistance | MΩ | ≥1000 | |
| 28 | dielectric strength | Hz | 50 | 2KV,50HZ,1min |
| 29 | Impulse Voltage | µS | 1.2/50 | 5KV,(1.2/50)µ S |
| Outline dimension diagram |