Overview

Product model: GC-WJ200B

Product Details

Product Introduction

The GC-WJ200B series microcomputer comprehensive protection and measurement device is suitable for the protection of transmission lines, bus tie switches, and other voltage levels ranging from 380V to 10kV.

As the basic equipment of power automation system, it has powerful communication function. The device adopts RS485 fieldbus and can optionally add an RJ45 Ethernet interface to ensure real-time and reliable information transmission.

Through the communication network, the GC-WJ200B series microcomputer comprehensive protection and measurement device sends all operational information, including telemetry, remote signaling, protection settings, etc., in real time to the first level SCADA system, and can receive commands such as protection settings modification, realizing the unmanned operation scheme of the substation.

Compliant with standard: DL/T478-2001 General Technical Conditions for Static Relay Protection and Safety Automatic Devices.


Product characteristics
  • Mother charger protection

  • current quick-break protection

  • Time limited current quick break protection

  • Definite time overcurrent protection

  • Inverse time overcurrent protection

  • overload protection

  • Zero sequence overcurrent protection

  • Zero sequence overvoltage alarm

  • Low voltage load shedding protection

  • Low cycle load reduction protection

  • Three phase coincidence at once

  • post-acceleration

  • PT disconnection discrimination

  • CT disconnection discrimination

  • Control circuit disconnection alarm

  • Measurement function

  • monitoring function

  • control function

  • communication function

  • Event record




Model Selection
  • GC-WJ200B1 microcomputer based line protection device

  • GC-WJ200B2 Microcomputer Transformer Protection Device

  • GC-WJ200B3 microcomputer capacitor protection device

  • GC-WJ200B4 microcomputer motor protection device

  • GC-WJ200B5 Microcomputer PT Monitoring Device

  • GC-WJ200B6 microcomputer circuit backup automatic switching protection device

  • GC-WJ200B7 microcomputer based busbar backup automatic switching protection device


Selection List


选型列表.png



TECHNICAL INDEX
Serial Number Project/Name unit Parameter indicators notes
1 ambient temperature
20±5
2 relative humidity
% 45~80
3 atmospheric pressure KPa 86~106
4 operation temperature -20~+60 The average temperature within 24 hours shall not exceed+45 ℃
5 Relative humidity at work % 95 The maximum monthly average is below 95%, and there is no condensation on the surface of the casing
6 Rated voltage of AC power supply V 220 -15%~+10%
7 AC power frequency Hz 50 -1%~+1%
8 Rated voltage of DC power supply V 220/110
9 Allowable deviation of DC power supply % -20~+20
10 Ripple factor of DC power supply % Not greater than 5
11 Rated AC current A 5/1
12 Rated zero sequence current A 5/0.2 Large grounding system 5A, small grounding system: 0.2A
13 Rated AC voltage V 100
14 Rated star voltage 3U0 V 100
15 DC circuit power W ≤8
16 AC voltage circuit VA ≤ 0.8/phase
17 AC current circuit VA ≤ 0.8/phase
18 Accurate working range of current A 0.5~100
19 Accurate working range of voltage V 1~160
20 DCS DC current range mA 4~20
21 Protection device setting error % <±3
22 Accuracy of current measurement % 0.5
23 Voltage measurement accuracy % 0.5
24 Power and electrical measurement accuracy % 2.0
25 capacity A 8 Connect DC250V, 8A (pure resistive load)
26 working life order Action 100,00
27 insulation resistance MΩ ≥1000
28 dielectric strength Hz 50 2KV,50HZ,1min
29 Impulse Voltage µS 1.2/50 5KV,(1.2/50)µ S




Outline dimension diagram


外形尺寸图.png




Definition diagram of wiring contacts