| Product Features |
High reliability, certified by the National Relay Protection and Automation Equipment Quality Supervision and Inspection Center;
Integrated embedded installation, eliminating the need for cables, more reliable, and easier to install;
The following functions can be selected in any combination:;
Can provide 16 types of protection, with accurate and reliable protection actions;
High precision measurement of various power parameters;
It has multiple startup control functions and multiple control modes;
Up to 2 analog outputs, with programmable output objects;
1-channel analog input measurement and protection;
Up to 11 switch inputs;
Up to 5 relay tripping, alarm, and control outputs;
Event recording function with a resolution of 2ms;
No need to equip with anti shaking module, achieve shaking self starting function;
Motor statistical information;
Equipped with dual RS485 communication interfaces, MODBUS-RTU communication protocol, and Profibus DP protocol (conversion);
Large LCD backlit display;
Multi button panel for data query, protection parameter setting, and motor start/stop operation;
Equipped with a small through core current transformer;
The product with ultra compact design and the ability to achieve the above functions has a depth of only 56mm;
| Selection List |

remarks:
1. The standard function of GC-DB400 is full measurement, with standard protection, 1 switch input, 3 relay outputs (trip and alarm), and no communication.
2. Standard protection: Short circuit protection, locked rotor protection, timed overload protection, inverse time overload protection, light load protection, grounding protection, current imbalance protection, long start-up time protection, phase loss protection, process interlock protection, overvoltage protection, undervoltage protection, and phase sequence protection.
3. ② Optional. If the suffix option is not specified, it means that the function is not needed. For example, if only GC-DB400 is specified, it means that only the standard functions of GC-DB400 are selected.
4. When selecting, indicate the voltage level, with 380V and 690V options available.
5. When selecting the - K start control function, 5 switch inputs are required 4-channel relay output; Only one of analog input and leakage protection can be selected.
6 GC-DB400-60-TQKS-5DI-4DO-C1-AO-380, Indicating that it comes with standard functions, split display, tE protection, self starting due to shaking, 5-way switch input, 4-way relay output, 1-way 485 communication, and 1-way analog output. It needs to be started for control, and a 60A through core transformer with S0E event recording is selected. The line voltage is connected to 380.
| TECHNICAL INDEX |
| Installation method | Embedded installation with integrated display opening, opening 90 * 90mm. |
| INPUT | Current 1A, 5A, 7A, 10A, 25A, 60A, 110A, 160A; Voltage 220V/380V, 380V/1660V |
| Standard protection | Short circuit, locked rotor, timed overload, reverse time overload, undervoltage, overvoltage, phase sequence, underload, grounding, three-phase current imbalance, phase failure, protection against excessive starting time, and process interlock tripping. |
| Extended protection | Leakage, tE time protection, analog input protection. |
| Action time |
Quick break time: < 60m. Time limit: 0s~3s < 60ms; Within the range of 3s to 99.9s, not exceeding 2% of the set value; Inverse time limit: 0s~2s < 100ms; Do not exceed 5% of the theoretical value after 2 seconds. |
| Action fixed value | Current: ± 50mA or ± 3% of the fixed value; Voltage: ± 2V or ± 3% of the fixed value. |
| Measurements | Various parameters such as current, voltage, power, power factor, frequency, and electrical degree. |
| accuracy class | Current and voltage level 0.5, power level 1, active energy level 1. |
| Switching input | Maximum 11 channels, internal power supply, used for starting, stopping/resetting, local/remote, process interlocking, and general switch status display. |
| Relay | Up to 5 channels, optional normally open or with a set of normally closed nodes, used for tripping, alarm, and remote control output, with a capacity of 250Vac/5A and 30Vdc/5A. |
| Event record | 64 records with time stamps, expandable recording quantity, and a resolution of up to 2ms. |
| start control | Direct start, bidirectional start, star/delta start, and self coupling voltage reduction start. |
| control mode |
Panel control, local control, DCS remote control, communication control. The shaking self starting function does not require an anti shaking module. |
| analog output | Up to 2 4-20mA outputs, internally active, with an output load of 500 ohms. |
| analog input | 1 channel 4-20mA input. |
| display | Chinese LCD displays measurement data, protection status, on/off status. |
| Communication Port | Up to 2 RS485 communication channels, MOBUS-RTU protocol, Profibus DP protocol. |
| Baud rate | 2400~19200bps。 |
| Working power supply | 85- 265VAC 100-300VDC。 |
| Overall Power Consumption | <5VA。 |
| power-frequency withstand voltage | Input output power supply AC2kV/1min. |
| insulation resistance | > 50M Ω. |
| Impulse Voltage | 5kV (peak), 1.2/50uS. |
| Electrical fast transient burst immunity | GB/T 14598.10(IEC60255-22-4)。 |
| Surge immunity | GB/T 14598.18(IEC60255-22-5)。 |
| electrostatic discharge | GB/T 14598.14(IEC60255-22-2)。 |
| Radio frequency electromagnetic field radiation immunity | GB/T 14598.9(IEC60255-22-3)。 |
| Immunity to Conducted Disturbances Induced by Radio Frequency Fields | GB/T 14598.17(IEC60255-22-6)。 |
| Power frequency immunity | GGB/T 14598.19(IEC60255-22-7) 。 |
| Vibration wave immunity | GB/T 14598.13(IEC60255-22-1) 。 |
| Conducted emission limit test | GB/T 14598.16(IEC60255-25)。 |
| Radiation emission limit test | GB/T 14598.16(IEC60255-25)。 |
| operation temperature | -20-70 ° C. |
| storage temperature | -40-80 ℃. |
| Relative temperature | 5-95%RH, No condensation. |
|
Outline dimension diagram |

| Wiring Terminal Diagram |