Overview

Product model: GC-DB200

Product Details

Product Features
  • Ultra compact design, the size of the entire protective device is 95 * 50 * 52mm, which is more suitable for miniaturized drawer unit cabinets;

  • Dot matrix Chinese character wave crystal display, intuitive display, easy operation;

  • Provide 9 standard protections, expandable with 2 standard protections, ensuring accurate and reliable protection actions;

  • High precision measurement of three-phase current and three-phase voltage;

  • Equipped with one analog output and programmable output objects;

  • 2-channel switch input;

  • Up to 3 relay trips, alarms, and control outputs;

  • No need to equip with anti shaking module, achieve shaking self starting function;

  • Equipped with RS485 intelligent communication interface and MODBUS-RTU communication protocol;

  • Multi button panel for data query and protection parameter setting;

  • Equipped with a small through core current transformer;



TECHNICAL INDEX
Installation method Embedded installation with integrated display opening, opening 90 * 45mm
INPUT

Current 1A, 5A, 7A, 10A, 25A, 60A, 110A, 160A

Voltage 220V/380V, 380V/1660V

Standard protection Short circuit, locked rotor, overload, underload, grounding, three-phase current imbalance, phase failure, protection for long starting time, process interlock tripping
Extended protection Undervoltage and Overvoltage
Action time

Quick break time: < 60ms;

Time limit: 0s~3s < 60ms; Within the range of 3s to 99.9s, not exceeding 2% of the set value;

Inverse time limit: 0s~2s < 100ms; Do not exceed 5% of the theoretical value for more than 2 seconds;

Action fixed value Current: ± 50mA or ± 3% of the fixed value; Voltage: ± 2V or ± 3% of the fixed value
Measurements Current and voltage parameters, with an accuracy level of 0.5
Switching input 2 channels, internal power supply provided
Relay Maximum of 3 channels, used for tripping, alarm, and remote control output, with a capacity of 250Vac/5A, 30Vdc/5A
Self starting function of shaking electricity No need to equip anti shake electrical module to achieve self starting
analog output 1 channel 4-20mA output. Internally active, with an output load of 500 ohms
display 4-line dot matrix Chinese character LCD screen with backlight display for measurement data, protection status, on/off status
key Press the six buttons to query data and set parameters
Communication Port 1 RS485 communication channel, MOBUS-RTU protocol, baud rate of 2400-19200bps
Working power supply 85- 265VAC 100-300VDC
Overall Power Consumption <5VA
power-frequency withstand voltage Input output power supply AC2kV/1min
insulation resistance >50MΩ
Impulse Voltage 5kV (peak), 1.2/50uS
Electrical fast transient burst immunity GB/T 14598.10(IEC60255-22-4)
Surge immunity GB/T 14598.18(IEC60255-22-5)
Electrostatic anti-interference seat GB/T 14598.14(IEC60255-22-2)
operation temperature -20-70℃
storage temperature -40-80℃
Relative temperature 5-95%RH, Undoubtedly exposed




Selection List

选型列表.png


remarks:

1. The standard function of GC-DB200 is to measure three-phase current, with standard protection, 1 relay output, 1 switch input, and no communication. Standard protection is described in the performance indicators.

2. If the above options are not specified, it means that the function is not required. For example, if only GC-DB200 is specified, it means that only the standard features of GC-DB200 are selected.

3. When selecting, indicate the voltage level, with 380V and 690V options available, and specify the voltage range of the power supply.

4. If the - A function option is selected, the protection function will add overvoltage protection and undervoltage protection.

5. GC-DB200-60-A-2DI-2DO-380, with standard functions, voltage protection, 2-channel switch input, 2-channel relay output, 60A through core transformer, line voltage connection of 380V.



Product Structure Diagram

产品结构图.png


Wiring Terminal Diagram



接线端子图.png