- Phone
-
Address
No. 4, Third Street, Cuizhu Industrial Zone, Qianshan, Zhuhai City, Guangdong Province
Zhuhai Guoce Electric Energy Instrument Technology Co., Ltd
No. 4, Third Street, Cuizhu Industrial Zone, Qianshan, Zhuhai City, Guangdong Province
|
Product Features |
Ultra compact design, the size of the entire protective device is 95 * 50 * 52mm, which is more suitable for miniaturized drawer unit cabinets;
Dot matrix Chinese character wave crystal display, intuitive display, easy operation;
Provide 9 standard protections, expandable with 2 standard protections, ensuring accurate and reliable protection actions;
High precision measurement of three-phase current and three-phase voltage;
Equipped with one analog output and programmable output objects;
2-channel switch input;
Up to 3 relay trips, alarms, and control outputs;
No need to equip with anti shaking module, achieve shaking self starting function;
Equipped with RS485 intelligent communication interface and MODBUS-RTU communication protocol;
Multi button panel for data query and protection parameter setting;
Equipped with a small through core current transformer;
| TECHNICAL INDEX |
| Installation method | Embedded installation with integrated display opening, opening 90 * 45mm |
| INPUT |
Current 1A, 5A, 7A, 10A, 25A, 60A, 110A, 160A Voltage 220V/380V, 380V/1660V |
| Standard protection | Short circuit, locked rotor, overload, underload, grounding, three-phase current imbalance, phase failure, protection for long starting time, process interlock tripping |
| Extended protection | Undervoltage and Overvoltage |
| Action time |
Quick break time: < 60ms; Time limit: 0s~3s < 60ms; Within the range of 3s to 99.9s, not exceeding 2% of the set value; Inverse time limit: 0s~2s < 100ms; Do not exceed 5% of the theoretical value for more than 2 seconds; |
| Action fixed value | Current: ± 50mA or ± 3% of the fixed value; Voltage: ± 2V or ± 3% of the fixed value |
| Measurements | Current and voltage parameters, with an accuracy level of 0.5 |
| Switching input | 2 channels, internal power supply provided |
| Relay | Maximum of 3 channels, used for tripping, alarm, and remote control output, with a capacity of 250Vac/5A, 30Vdc/5A |
| Self starting function of shaking electricity | No need to equip anti shake electrical module to achieve self starting |
| analog output | 1 channel 4-20mA output. Internally active, with an output load of 500 ohms |
| display | 4-line dot matrix Chinese character LCD screen with backlight display for measurement data, protection status, on/off status |
| key | Press the six buttons to query data and set parameters |
| Communication Port | 1 RS485 communication channel, MOBUS-RTU protocol, baud rate of 2400-19200bps |
| Working power supply | 85- 265VAC 100-300VDC |
| Overall Power Consumption | <5VA |
| power-frequency withstand voltage | Input output power supply AC2kV/1min |
| insulation resistance | >50MΩ |
| Impulse Voltage | 5kV (peak), 1.2/50uS |
| Electrical fast transient burst immunity | GB/T 14598.10(IEC60255-22-4) |
| Surge immunity | GB/T 14598.18(IEC60255-22-5) |
| Electrostatic anti-interference seat | GB/T 14598.14(IEC60255-22-2) |
| operation temperature | -20-70℃ |
| storage temperature | -40-80℃ |
| Relative temperature | 5-95%RH, Undoubtedly exposed |
| Selection List |

remarks:
1. The standard function of GC-DB200 is to measure three-phase current, with standard protection, 1 relay output, 1 switch input, and no communication. Standard protection is described in the performance indicators.
2. If the above options are not specified, it means that the function is not required. For example, if only GC-DB200 is specified, it means that only the standard features of GC-DB200 are selected.
3. When selecting, indicate the voltage level, with 380V and 690V options available, and specify the voltage range of the power supply.
4. If the - A function option is selected, the protection function will add overvoltage protection and undervoltage protection.
5. GC-DB200-60-A-2DI-2DO-380, with standard functions, voltage protection, 2-channel switch input, 2-channel relay output, 60A through core transformer, line voltage connection of 380V.
| Product Structure Diagram |

| Wiring Terminal Diagram |