Fixed combustible, flammable and explosive gas explosive detectorChicheng Manufacturer (hereinafter referred to as the detector) is a fixed instrument that can continuously detect the concentration of flammable gases in the working environment.
The fixed flammable and explosive gas explosive detector detects gas concentration through natural diffusion and uses imported catalytic combustion sensors, which have excellent performanceThe sensitivity and excellent repeatability of the LED digital display are suitable for factory applications, which can display the concentration value of leaked gas in real time. Once the preset alarm point is reached, the sound and light alarm signal or exhaust system can be immediately activated; The standard 4-20mA signal can be directly connected to the factory DCS system, and the RS485 digital signal is connected to the factory upper computer; The instrument adopts embedded microcontroller technology, with simple operation, complete functions, high reliability, and overall performance at the domestic level.
2Main functions and technical indicators
2.1Main functions
The instrument used16Low power embedded microcontroller
LED digital display
An's lid free infrared remote control operation
Users can set their own high and low alarm points
Important operations require password verification to effectively prevent accidental operations
Standard 4-20mA signal or RS485 digital signal can be directly connected to the factory DCS system
2.2technical indicators
Measuring range:0-LEL
Applicable gas: Combustible gas
report police Point: Refer to the attached table
Display error: ≤± 5% F. S
Response time:T90<30s
Display mode:LED digital display
Operation mode: infrared remote control
Status indication: green indicates normal operation, yellow indicates fault, red indicates concentration alarm
Alarm point: default values of 20% LEL and 50% LEL, users can change the settings
Signal output:Standard 4-20mA signal
RS485 isolated digital signal
Work environment:-30℃~+50℃;humidity<90%RHno condensation
Working voltage: DC24V ± 15%
Sampling method: natural diffusion
preventExplosive level: Exd Ⅱ CT6
Protection levelIP66
Cable usage: 3 × 1.5mm2Or 4 × 2.5mm2shielded cable
Transmission distance: ≤ 1000m
heavy quantity:About 1000g