Overview

The intelligent single loop digital/light column display controller features a dedicated integrated instrument chip with more reliable anti-interference and stability.

Product Details

Digital display controllerTECHNICAL INDEX

particular sexually

Display mode: arranged in a single row with four digitsLEDDisplay measurement values(PV)Simulate and display the percentage of measured values using a monochromatic light column.
Display range:-19999999Words.
Measurement accuracy: ±0.2%FSperhaps0.5%FS;±0.1%FS(Special customization required).
Resolution: ±1Words.
Alarm method:1-4Road alarm control (lower limit)LLLower limitL, upper limitHUpper limitHHLEDinstructions.
Alarm accuracy: ±1Words.
Protection method: Input circuit disconnection, input signal overload/Under range alarm; Input circuit disconnection, transmission output hold, maximum, minimum optional
Setting method: Panel touch button numerical setting, set value permanently saved after power-off.

Input signal

Thermocouple:KESBJTRWRe3-25Automatic compensation range for cold end temperature050℃, compensation accuracy ±1℃.
Thermal resistance:Pt100Cu100Cu50BA2BA1Compensation range for lead resistance ≤15Ω.
Linear resistance:0400Ω
Remote transmission resistor:30350Ω(Remote pressure gauge)
DC voltage:020mV0100mV05V15V05VOpening the formula15VOpening the formula-5V5V
-10V
10V010V (Please specify when ordering, incompatible with other signals).
Direct current:010mA020mA420mA010mAOpening the formula420mAOpen the door.
Input impedance: current signalRi500KΩ.

output signal

Output accuracy: Same as measurement accuracy.
Current signal:DC 420mALoad resistanceR500Ω;DC 010mALoad resistanceR750Ω.
Voltage signal:DC 05VDC 15VLoad resistanceR250KΩ, otherwise the output accuracy after connecting external instruments cannot be guaranteed.
Alarm output: Relay control output---relayON/OFFBring back the difference,CONTACT CAPACITY---AC220V/1ADC24V/3A(Resistive load)
Communication output: baud rate---240048009600bpsInternally customizable, usingMODBUS RTUCommunication protocol.
Distribution output:DC24±1VLoad current ≤30mA.

Usage environment

Environmental temperature:-1055℃;
Environmental humidity: ≤85%RHAvoid strong corrosive gases.
Pressure resistance strength: input/output/power supply/Communication between each other ≥1000V.AC/minute.
Insulation impedance: input/output/power supply/Communication between each other ≥100MΩ.
AC power supply:90265V(Switching power supply), frequency:50Hz/60Hz.
DC power supply:24V±2V(Switching power supply).
work Consumption:<5W.