Medical Reproductive Center is a medical service institution engaged in reproductive health, genetic eugenics, intervention for birth defects, research on reproductive science, and clinical diagnosis and treatment. Huanyang Future undertakes the purification and decoration project design of the Molecular Genetics Laboratory in the Department of Reproductive Medicine

Product Details

Design of Purification and Decoration Engineering for Molecular Genetics Laboratory in Reproductive Medicine Department

  • Medical Reproductive Center is a medical service institution engaged in reproductive health, genetic eugenics, intervention for birth defects, research on reproductive science, and clinical diagnosis and treatment.


Partition and functional rooms in the medical reproductive center

  • According to the different stages of use, the plane is mainly divided into two areas: the experimental preparation area and the experimental and analysis area. The experimental preparation area mainly completes the preparation work before embryo testing, such as sperm and egg retrieval. The flat room mainly consists of a sperm retrieval room, an egg retrieval room (including one negative pressure room), a laparoscopic operating room, and an anesthesia recovery area.

  • The experimental and experimental analysis area mainly completes the work of the embryo experimental stage, such as the disposal, analysis, and storage of sperm and eggs, the generation, cultivation, frozen storage, and implantation of fertilized eggs. The flat room mainly consists of semen disposal room, embryo laboratory, implantation room, liquid preparation room, cell room, freezing room, liquid nitrogen storage room, reagent room, fluorescence microscope/PCR, and other office auxiliary rooms.


Design of Purification and Decoration Engineering for Molecular Genetics Laboratory in Reproductive Medicine Department

artificial inseminationVenue requirements

The venue includes waiting rooms, consultation rooms, examination rooms, ultrasound rooms, artificial insemination laboratories, insemination rooms, and other auxiliary areas. The total area shall not be less than 100 square meters, of which the dedicated area for artificial insemination laboratory and insemination room shall not be less than 20 square meters each.

In addition, medical institutions must have relevant examination conditions such as gynecological endocrine testing, imaging examination, genetic examination, etc.

In vitro fertilization/embryo transfer and its derivativesVenue requirements

(1) The dedicated area of the institution shall not be less than 200 square meters. The area for in vitro fertilization laboratory and egg retrieval room shall not be less than 60 square meters.

(2) The layout of the venue must be reasonable, meet cleanliness requirements, and the building and decoration materials must be non-toxic. Chemical and radioactive sources that may have adverse effects on work should be avoided.

(3) The workplace must comply with hospital building safety and fire safety requirements, ensure water and electricity supply, and each workspace should have air disinfection facilities.

(4) Ultrasound room: with an area of not less than 10 square meters, the environment meets the Class III standards of the Ministry of Health for medical facilities.

(5) Sperm collection room: adjacent to the semen processing area.

(6) Egg retrieval room: for transvaginal egg retrieval under B-ultrasound guidance. The area shall not be less than 15 square meters. The environment meets the Class II standards for medical facilities set by the Ministry of Health.

(7) In vitro fertilization laboratory: with an area of not less than 20 square meters and equipped with a buffer zone. The environment meets the Class I standards of the Ministry of Health for medical facilities, and it is recommended to set up an air purification laminar flow room. The embryo operation area should meet the Class 100 standard and have temperature control conditions.