1、 Scope of application
The DZ47-63 miniature circuit breaker is mainly suitable for circuits with AC 50/60Hz, rated working voltage of 230V/400V and below, and rated current up to 63A. This circuit breaker is mainly used for overload and short circuit protection of electrical lines and equipment in modern buildings, and is also suitable for infrequent operation and isolation of lines. structural characteristicsThe electric scooter circuit breaker consists of a plastic casing, an operating mechanism, a contact arc extinguishing system, a trip mechanism, etc. The shell is made of high flame retardant and high-strength special plastic, with strong impact resistance and light weight. The components of the electric scooter circuit breaker operating mechanism are made of high-strength plastic products, which ensure sensitivity and reliability while obtaining the lowest moment of inertia, making the time from the start of a short circuit fault to the action of the trip mechanism very short. The trip mechanism consists of two parts: a bimetallic overload inverse time trip mechanism and a short-circuit instantaneous electromagnetic mechanism. The contact arc extinguishing system adopts special arc angles and aisle extinguishing chambers, and has significant current limiting characteristics. This product is mainly used for overload and short circuit protection of lighting, distribution lines, and equipment in office buildings, residential buildings, and similar structures. It can also be used for infrequent conversion of lines under normal conditions. It meets the requirements of standards such as IEC60898 and GB10963.1. Has passed the national CCC certification and CE certification.2、 Model and specifications

3、 Normal working conditions
The upper limit of the surrounding air temperature shall not exceed plus forty degrees Celsius; The lower limit generally does not exceed minus five degrees Celsius. Used under conditions above positive 40 degrees Celsius or below negative 5 degrees Celsius4、 Main parameters and technical performance
Main specifications:| Shell level rated current lnm (A) | Rated current ln (A) | Polar number (P) | Rated voltage Ue (V) | Rated short-circuit breaking capacity lcn (A) |
| 63 | 6. 10, 16, 20, 25, 32, 40 | 1. 2 | 230 | 4500~6000 |
| 2. 3, 4 | 400 | |||
| 50, 63 | 1. 2 | 230 | 3000~4500 | |
| 2. 3, 4 | 400 |
| experiment | type | test current | Initial state | Tripping or non tripping time limit | expected result |
| a | B、C、D | 1.13ln | cold state | t≤1h | Do not release |
| b | B、C、D | 1.45ln | Immediately following item a | t<1h | trip |
| c | B、C、D | 2.55ln | cold state |
1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) |
trip |
| d | B | 3ln | cold state | t≤0.1s | Do not release |
| C | 5ln | ||||
| D | 10ln | ||||
| e | B | 5ln | cold state | t<0.1s | trip |
| C | 10ln | ||||
| D | 16ln |
5、 Appearance and installation dimensions