Welcome Customer !

Membership

Help

Beijing Chuangyu Electromechanical Equipment Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Beijing Chuangyu Electromechanical Equipment Co., Ltd

  • E-mail

  • Phone

  • Address

    Liulihe Town, Fangshan District, Beijing

Contact Now

18 cubic meter gas top pressure fire water supply equipment

NegotiableUpdate on 05/11
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Gas top pressure device: usually using a nitrogen cylinder group (high-pressure inert gas), the pressure is controlled by a pressure reducing valve to maintain the pressure of the pipeline network. $r $n fire water tank (18m): stores fire water, and can be made of stainless steel/carbon steel anti-corrosion materials, which must comply with the GB50974 standard. $r $n pressure water tank: Buffer pressure fluctuations, volume needs to be calculated based on the system pressure curve (recommended 1 2m #179; ). $r $n control cabinet: linked fire alarm system, automatically starts gas source and water replenishment pump

Product Details

18 cubic meter gas top pressure fire water supply equipment


target, aim at, address, focus on, in response to18Cubic gasTop pressureFirefighting is providedWater equipmentThe demandHere isprofessionalThe technologyplanAnd precautions


1systemComposition andworking principle
1.corecomponent
Gas topPressure deviceusuallyUsing nitrogengas cylinderGroup(high pressureinertiaGas),By reducing pressureValve controlAir pressure,maintainpipeline networkpressure
fire water tank18m³)Storage fire protection用水,materialoptionalstainless steel/carbon steelanticorrosive,needCompliant with GB50974 standard.
atmospheric pressurewatercan: Bufferpressure fluctuation, volumeneedaccording to the systempressurecurveCalculate(suggestion1 2m³)。
controlcabinet: Linkagefire alarmsystem, AutomaticstartqiSource andsupplementWater pump.
2. workflow
Normal statenitrogenQi maintenancepipeline networkoftenPressure(as if0.6MPa)The water tankfullWater.
During a firefire pumpStart up,Gas topPressure systemQuick SupplementPressure,Ensure 10Within minutesInitial fire extinguishing用水(18meet the specificationsRequirement).
Post production water supplyfire pumpfrommunicipal pipe networkOr a pool of waterContinuous water supply.

18立方气体顶压消防给水设备



twoKey pointsdesignparameter
1.pressurecalculate
Top pressureInitial gasStress≥1.2timessystemwork pressure(such asdesignPressure 0.8MPa,thenqiBottle pressureneed≥1.0MPa)。
voltage stabilizationpumpStart-stopStressaccording tomostDisadvantage pointfirefightingBolt pressure(Usually)≥0.15MPa)set up.
2. Volume verification
18Water tank needsSatisfy《firefightingwater supplyAnd consumptionFire boltSystem TechnologyStandard "(GB50974)CorrectInitial firewaterQuantity requirementsLike lightDanger levelvenue10Minute water usageQuantity).

threeChooseType andInstallation key points
1. Equipment selectiontype
priority choicebeltintelligenceleakpressure valveThe air pressurecan, 防止superPressure.
pump flow rate18m³/hheadBy buildingHeight calculation(such as100M buildingNeed to YangCheng ≥1.4MPa).
2.Installrequirement
Gas topPressure deviceWith the water tankdistance≤5m,reduce stressLoss.
nitrogengas cylinderGroup needsIndependent defenseExplosive RoomCompliant with《qiBottle safetytechnologyregulations》(TSG23).
3.acceptancestandard
systemneedthrough1.5Double workPressure testPressure(Continuously 30minuteleak-free).
simulationFire linkageTesting,Ensure 30Within secondsstarttopPressure.

fourCommonproblem solving
atmospheric pressurefluctuationbig: CheckAir pressure tankairbagwhetherruptureOr decompressionValve regulationimproper.
water tank replenishmentslowAdd doubleRoad water supplyOr increase itsupplement水管径(Suggestion)DN80above).