1.1. A 10KW water-cooled chiller uses an evaporator to exchange heat between water and refrigerant. The refrigerant absorbs heat from the water, cools it down, and produces cold water. The heat is then carried to a shell and tube condenser by a compressor, where the refrigerant exchanges heat with the water. After the water absorbs heat, it is carried out of the external cooling tower through water pipes for dissipation and cooling.

Product Details

1.1. A 10KW water-cooled chiller uses an evaporator to exchange heat between water and refrigerant. The refrigerant absorbs heat from the water, cools it down, and produces cold water. The heat is then carried to a shell and tube condenser by a compressor, where the refrigerant exchanges heat with the water. After the water absorbs heat, it is carried out of the external cooling tower through water pipes for dissipation and cooling.
SJ-04WS
refrigeration power Kcal / KW 10664 / 12.4
power supply V 3∮ 380~380V- 50HZ(Can be customized)
operating current A 6.6
refrigerant Kind R407C, R404A, R134A
FILLING QUANTIT(kg) 2.3
compressor power KW 3.31
Number of compressors 1
cooling water flow m3/h 3.5
water pump KW 0.55
Freezing flow rate m3/hr 2.3
Standard pipe diameter MM 25
Design dimensions L(mm) 830
W(mm) 460
H(mm) 140
weight kg 102
For more model parameters, please click to enter
1. A 10KW water-cooled chiller has a smaller volume compared to an air-cooled chiller, and overall stable performance. Under the same horsepower, the water-cooled chiller has a cooling capacity about 20% higher than the air-cooled chiller.

2. The main internal configuration of the 10KW water-cooled chiller is:
2.1 Compressor: American Grain Wheel 3HP
2.2 Water pump: Stainless steel southern pump flow rate 2.5m ³/h, pressure 2KG
2.3 Water tank: made of stainless steel material, with a capacity of 50 liters
2.4 Evaporator: Shell and tube type

2. During the operation of water-cooled chillers, there may be dirt or other impurities that can affect the cooling effect if they run for a long time. In order to ensure the extension of service life and achieve high-quality status of the unit, regular maintenance and upkeep should be carried out to ensure the quality of operation of the chiller unit and improve production efficiency.
3. User inspection and maintenance items:
3.1 Regularly check whether the current of the chiller is stable and whether the sound of the compressor operation is normal. When the 10KW water-cooled chiller is working normally, the voltage is 380V and the current is within the range of 6A-9A, which is considered normal.
3.2 Regularly check if there is refrigerant leakage in the chiller: Under normal conditions, the low pressure gauge pointer of the water-cooled chiller should be between 3KG and 3.5KG, and the high pressure should be between 15KG and 18KG. (Protection device: If there is a leak in the refrigeration system, the chiller will alarm and shut down when the low pressure gauge is below 1KG, and the machine cannot be turned on.)
3.3 After 6 months of use, a water-cooled chiller should undergo routine maintenance, which mainly includes cleaning impurities and sludge in the water tray of the cooling water tower, cleaning debris in the cooling water pipes, and cleaning scale on the copper tube wall of the shell and tube condenser.

Schematic diagram of 10KW water-cooled chiller



Q: Can the size of the inlet and outlet ports be customized for this chiller?
Answer: Absolutely possible. It can be customized according to the user's required import and export sizes, and can also be equipped with multiple input and output splitters without additional fees. It is provided free of charge to the user.