Welcome Customer !

Membership

Help

Beijing Eklens Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Beijing Eklens Electric Co., Ltd

  • E-mail

  • Phone

  • Address

    Room 593, Building A, No. 9 Fengxiang East Street, Yangsong Town, Huairou District, Beijing

Contact Now

Supply of energy-saving automatic control system for central air conditioning

NegotiableUpdate on 05/14
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The rated working voltage of the central air conditioning energy-saving automatic control system is 12VDC, with 16 thermistor input channels, of which 12 are used to detect 10K Ω thermistors and 4 are used to detect 100K Ω thermistors; 12 12V DC input switch channels and 15 24V DC/220V AC relay output channels; 4-channel electronic expansion valve (Sanhua, Lugong, etc.) drive interface.

Product Details

Central air conditioning energy-saving automatic control systemThe rated working voltage is 12VDC, with 16 thermistor input channels, of which 12 are used to detect 10K Ω thermistors and 4 are used to detect 100K Ω thermistors; 12 12V DC input switch channels and 15 24V DC/220V AC relay output channels; 4-channel electronic expansion valve (Sanhua, Lugong, etc.) drive interface.




Central air conditioning energy-saving automatic control systemProduct performance


  • Body I/O: 12 channels of 12V DC input

  • 15 relay outputs, relay rated current is 10A (AC220V)

  • Storage capacity: 120K bytes in the program area; 10K bytes in data N area and 5K bytes in data M area; Power down hold area 2K bytes

    Timer: 1 hardware timer, 0.1ms~500ms, software timer unlimited point (minimum unit 1ms)

  • Counter: 16 bits, unlimited points

  • Calculation speed: 0.06 μ s (Boolean operation instruction)

  • Communication interface: 1 RS232, 2 RS485

  • Communication protocol: MODBUS RTU protocol, free protocol








  • Power parameters


Power parameters


power supply voltage

12V DC


permissible range

11~13VDC


Maximum current

2000mA







  • Digital input and output


Digital input


input type

prototype


input signal

Rated voltage 12V DC


Allowable range 0-13V DC


Input ON signal

8~13V DC, Allow a minimum current of 3mA


Input OFF signal

0~5V DC, Maximum allowable current 1mA





digital output


output type

relay


output voltage

0-24V DC or 24-230V AC


Total output current of the common terminal

<10A


Switch delay

<10ms


Isolation voltage between coil and contact

3000VAC, 1 minute, leakage current 1mA


Isolation voltage between contacts

750VAC, 1 minute, leakage current 1mA


Mechanical lifespan of relay

When there is no load, it can reach more than 10000000 times

When the rated resistive load is 10A, it can reach more than 100000 times









  • Analog input


Analog input


number of channels

16 way NTC


input type

Thermistor, B value optional

At R25 ℃, 12 channels are 10K Ω and 4 channels are 100K Ω


Input accuracy

0.2% FS@25 ℃ (voltage) (FS represents full scale, @ 25 ℃ represents at 25 ℃)


Temperature resolution

0.1℃


Sampling refresh time

100ms (full channel)







  • Electronic expansion valve drive


Electronic expansion valve drive


Output channel

4 routes


Scope of application

5-core 12V series electronic expansion valve