Welcome Customer !

Membership

instrumentb2bShanghai Xuji supplies a large amount of TE9200 lightning arrester comprehensive test bench lightning arrester test bench

TE9200 lightning arrester comprehensive test bench

The comprehensive test device for lightning arrester characteristics meets the requirements for measuring the AC/DC characteristics of lightning arresters in the "DL/T 596 Preventive Test Code for Power Equipment". Used to measure the AC characteristics of lightning arresters: leakage current, resistive current, capacitive current, phase angle, peak resistive current, peak full current, fundamental active power, harmonic active power, third harmonic, fifth harmonic and other AC characteristics under power frequency reference voltage; It can also be used to measure the DC characteristics of lightning arresters: the reference voltage U1mA at 1mA DC and the leakage current I0.75U1mA at 0.75 times the reference voltage; It can also be used for AC and DC withstand voltage testing of various other devices. The device consists of a comprehensive control device for lightning arrester characteristics, a test transformer, an AC/DC voltage divider, a DC voltage doubler, a microampere meter, and other equipment.
The device displays test values on a large LCD screen and uses a true effective value measurement circuit to obtain more accurate measurement data; Equipped with overvoltage and overcurrent setting protection functions, built-in timing function, and built-in data storage function; This device has powerful functions and is versatile, making it a necessary replacement equipment for lightning arrester manufacturers and power supply departments.

TE9200 lightning arrester comprehensive test bench

Product Features

(1) Multi functional in one
It can be used for testing the AC and DC characteristics of lightning arresters, as well as for conducting AC and DC withstand voltage tests on other equipment.
(2) Large screen LCD digital display measurement values
Using a true effective value measurement circuit, the measurement data is more accurate and reliable, and displayed in Chinese characters.
(3) Complete protection functions
Voltage and current setting functions provide more convenient, sensitive, and rapid protection; Equipped with timing function, making the experiment more accurate and reliable.
(4) The product design is beautiful and atmospheric, with a desktop structure that is more suitable for laboratory use.
(5) High and low voltage measurement, high and low voltage current measurement, high voltage side AC/DC voltage measurement, high voltage measurement DC current measurement, multiple voltage and current measurements, which are conducive to horizontal comparison of data.

TE9200 lightning arrester comprehensive test bench

Technical Specifications

(1). function

Used for measuring the AC characteristics of lightning arresters, as well as for measuring the DC characteristics of lightning arresters, and for conducting AC and DC withstand voltage tests on various other equipment. Meet the requirements of DL/T596-2005 "Preventive Testing Code for Power Equipment".

(2). Main technical parameters

1Parameters of AC high voltage regulating control device:

a) Measurement accuracy: current: 2% x reading+1A, voltage: 2% x reading+1kV;

b) Protection accuracy: Current: ± (5% x reading+1A), Voltage: ± (5% x reading+1kV);

c) Output voltage (V): adjustable from 0 to 250;

2Test transformer parameters:

a) Rated capacity (kV): 10;

b) Output voltage (kV): 100;

c) Output current (mA): 100;

d) Measurement output (V): 100;

3Voltage divider parameters:

a) Measurement range: AC: 0-150kV; DC:0~210kV;

b) Measurement accuracy: AC: 1.5 level; DC: Level 1.0.

4Communication characteristic device parameters:

a) Leakage full current (mA): 0-10;

b) Resistive current (mA): 0-10;

c) Capacitive current (mA): 0-10;

d) Phase angle (°): 0-360.

e) Measurement accuracy: ± (2%+1 word)

f) Measurement range (mA): 0-10;

5DC characteristic device parameters:

a) Output current (mA): 2;

b) Output voltage (kV): 120;

c) Ripple washing: ≤ 1%;

d) Measurement accuracy: 2%.

Latest News