Instructions and methods for using waterproof membrane impermeability meter
Date: 2025-08-21Read: 6

Waterproof material impermeability testerInstructions for Use

1.Sample preparation

•Cut the waterproof membrane into circular test pieces with a diameter greater than 150 mm, ensuring a smooth and wrinkle free surface.

•Check if the surface of the sample is clean and dry. If there is dust or oil on the surface, it should be cleaned thoroughly.

2.Install the sample

•Open the sample fixture and place the sample on the lower flange sealing ring.

•Ensure that the sample covers the entire test port and that the testing surface faces the water pressure side.

•Install the upper flange and tighten it evenly with bolts to ensure good sealing.

3.Add water and exhaust

•Fill the test chamber with clean water through the water inlet while releasing air to avoid affecting pressure stability.

4.Pressure test

•Set the test pressure according to standard requirements (such as 0.3 MPa);

•Start the pressure pump and slowly increase the pressure to the set value to avoid pressure shock;

•Start timing (usually 120 minutes) and maintain stable pressure during this period.

5.The test is over.

•After reaching the specified time, slowly release the pressure to prevent damage to the sample due to sudden changes in force;

•Disassemble the sample, observe for any signs of leakage, and record the results.


Waterproof material impermeability testerUsage method (simplified process)

1.Cut and prepare the sample;

2.Correctly clamp the sample in the testing chamber;

3.Inject water into the test chamber and exhaust air;

4.Slowly increase the pressure to the set value;

5.Maintain pressure and observe for leaks according to the prescribed time;

6.Record the results and disassemble the sample.