E-mail
cqytdq@163.com
- Phone
-
Address
4F, Unit 2, Phase I Standard Factory Building, No. 98 Xiyong Xiyuan 2nd Road, Shapingba District, Chongqing City
Chongqing Yueteng Electric Appliance Co., Ltd
cqytdq@163.com
4F, Unit 2, Phase I Standard Factory Building, No. 98 Xiyong Xiyuan 2nd Road, Shapingba District, Chongqing City

Each unit provides 30 branch insulation resistance detection functions, with a measurement accuracy of ± 0.3K Ω.
Detect the ground voltage of the busbar (combined busbar, control busbar, and busbar negative) with a measurement error of ± 0.4V.
Determine insulation resistance by detecting branch leakage current.
The ratio of the leakage current sensor should be selected as ± 10mA/± 5V, and the power supply can be directly output from the ± 12V point source on the board; The maximum capacity of the insulation detection unit output for sensor power supply is ± 12V/450mA.
In the absence of a mother, the HM+and KM+of JP3 should be short circuited.
RS485 communication interface.
Working power supply: DC85-320V.
Appearance dimensions: W230 * H95 * D240 (mm).

Note: JP5-JP10 are 30 input interfaces for branch insulation.