- Phone
-
Address
No. 16 Xingye West Road, Mawei High tech Park, Fuzhou, China
Fujian Shangrun Precision Instrument Co., Ltd
No. 16 Xingye West Road, Mawei High tech Park, Fuzhou, China
Main features
● Adopting a two-wire international standard current signal output
● Input of arbitrary waveform alternating signal, wide measurement range
● Directly measure 0-500V/0-5A
Measurement Error Comparison Table

Comparison of measurement errors between true effective value method and mean value method:
Peak factor: Kp=Up/Urms
Waveform factor: Kf=Urms/U
For sine waves: Kp=1.414 Kf=1.111
Therefore, Urms=1.111U
Order: Actual value=1.111U; True value=Urms
Then: γ=(actual value - true value)/true value X 100%
Measurement signal:
● AC voltage 0-500V
● AC current 0-5A
Output signal: (4-20) mA DC (two-wire system)
Working voltage: (7.5-36) VDC
Accuracy: 0.2 level
Allowable temperature: (-30~70) ℃
Relative humidity: ≤ 85% RH (no condensation)