WCB-821_ Xuji Microcomputer Factory Transformer Protection Device

NegotiableUpdate on 03/29
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
WCB-821_ Xuji Microcomputer Factory Transformer Protection Device
Product Details

1. Introduction to the device

The WCB-820 series microcomputer factory transformer protection device is mainly suitable for the protection of factory transformers, utility transformers, or grounding transformers in small grounding current systems or small resistance grounding systems with voltage levels of 3-10kV.

1.1. Function configuration: Please refer to Table 1-1

Table 1-1: Functional Configuration


Function Name

WCB-821

WCB-822

protection function

Two stage current protection

Three stage timed composite voltage blocking current protection

non-electrical protection

High voltage side three-stage zero sequence overcurrent protection

Low voltage side three-stage zero sequence overcurrent protection

TV disconnection detection

High voltage side positive sequence reverse time overcurrent protection

Overload protection

Zero sequence overvoltage protection

low voltage protection

Two stage timed negative sequence overcurrent protection

Low voltage side zero sequence inverse time overcurrent protection

Measurement and control function

Remote signaling input acquisition, device remote signaling displacement, accident remote signaling

Normal circuit breaker remote control opening and closing, low current grounding detection remote control opening and closing

Telemetry of analog quantities such as Ia, Ib, Ic, Ua, Ub, Uc, P, Q, f, etc

Statistics of switch accident opening and closing times and event SOE, etc

fault recording

4-channel pulse input


1.2. Main features

1. The reinforced unit chassis is designed to resist strong vibration and interference, and is particularly suitable for harsh environments. It can be installed separately on the switchgear for operation.

2. All integrated circuits are made of industrial products, ensuring high stability and reliability of the device.

3. Using 32-bit DSP as the protection CPU, configured with large capacity RAM and Flash Memory; Strong data operation, logical processing, and information storage capabilities, high reliability, and fast running speed.

4. Using 16 bit A/D as data acquisition, data collection is conducted 24 hours a week to ensure high measurement accuracy.

5. Adopting graphical LCD display and fully Chinese menu style human-computer interaction; It can display various operating statuses and data in real time, with detailed and intuitive information, and easy operation and debugging.

6. It can independently set 8 sets of protection settings, and the switching of the setting area is safe and convenient.

7. Large capacity information recording: capable of storing no less than 100 recent historical reports, with action parameters, power failure maintenance, and easy accident analysis.

Adopting DL/T667-1999 protocol and equipped with RS-485 communication interface; Networking is economical and convenient, and can directly communicate with microcomputer monitoring or protection management machines.