XING ZHOU Instrument Xingzhou brand: Ultrasonic open channel flowmeter won the bid for the selection of sewage treatment delta weir in a Jiangsu Environmental Protection New Energy Co., Ltd.
Product Details

Ultrasonic open channel flowmeter


XING ZHOU, developed and produced by Wuxi Xingzhou Instrument Co., Ltd ® Xingzhou brand:Ultrasonic open channel flowmeterIn the bidding process for the sewage treatment triangular weir of a certain environmental protection new energy limited company in Jiangsu, we won the bid in one fell swoop.






XZ6000CMG Manual

1、 Basic overview and functional purpose introduction:
Originally known for its economic practicality, it is mainly used for measuring open channel discharge. Its basic functions include querying the liquid level, instantaneous flow rate, and cumulative flow rate of flowing liquids, as well as displaying various parameters in a cyclic manner The FM3.14 series produced by our company has automatic recording function, with daily, monthly, and annual cumulative flow reports, and various historical data curve record queries
1. This instrument is suitable for: Pachet trough, rectangular weir, equal width weir, triangular weir
2
This instrument can choose the following flow measurement units: kg, m3, L, T
3
Input signal → Ultrasonic probe → Specially equipped or compatible with 4-20mA input by our company


2、 Familiarize yourself with your instrument panel
1
The distribution and function of the main interface content and various function keys:
2
Introduction to operation key functions:
1) Left and right arrow keys ->Move the cursor to select the size you want to change
2) Reduce and increase keys → Use them to change the size of numbers And change the content of different attributes of the instrument
3) Page turning and viewing keys → Press this key continuously to view the basic parameters of the instrument in sequence You can also press this key once after completing the operation to return to the previous menu until the main screen or exit the settings program
4) Confirm and enter key → After modifying each parameter, press this key to confirm. This key also enters the settings menu key. For example, when a parameter needs to be modified after the instrument is powered on, hold down this key until the password interface appears, and the interface prompts (please enter password)


3、 View important parameters of the instrument panel (continuously press the page up button)
1
When selecting an ultrasonic probe:
By continuously pressing the page keys, the following parameters can be viewed:
(1) Instantaneous flow rate (2) Cumulative flow rate (3) Flowing liquid level (4) Air distance → Distance from probe to water surface
(5) The distance between the high water level and the probe in the instrument blind zone must be greater than the value of the blind zone
(6) Weir tank name → The current selected weir tank name → Menu options (7) Query of communication connection status and communication parameters
2
TheWhen selecting an output 4-20mA transmitter input:
You can view the following parameters by continuously pressing the page keys:
(1) Instantaneous flow rate (2) Accumulated traffic (3) Flowing liquid level (4) Input current → The current input from the transmitter to the instrument
(5) Liquid level range → Range of liquid level transmitter (6) Weir tank name → The current selected weir tank name → Menu options
(7) Communication connection status and parameter query

4、 How to enter the user's main menu
Press and hold the confirm button until the password interface appears (please enter the password), and change the size of the number by pressing the increase and decrease keys. Press the left and right shift keys to select the number of digits you want to change Password 0000, then press the confirm button to display the following menu settings

5、 Menu
A
When selecting an ultrasonic probe:
1
Traffic →
(1) Select channel ->Paxie channel, rectangular weir, equal width weir, triangular weir
(2) Probe selection → Ultrasonic transducer or 4-20mA input (3) Compensation → (Internal compensation)
2
Parameters →
(1) Current water level → Check that the distance between the air and the transducer to the water surface is equivalent, install correctly, and then modify the current water level number to the actual water depth number
(2) Flow upper limit → large instantaneous flow → commonly known as range (large flow of weir)
(3) Lower limit of traffic → set to 0.0000
(4) Water level cut-off → small water level cut-off, recommended 0.005-0.02m, adjusted according to actual situation

3System → (1) Password → Remember to remember after changing (2) Patrol display → Patrol display → Multiple options for automatic patrol display with 8 parameters (3) reset → Accumulated reset, power outage reset (4) Recovery → Verify recovery, generally not necessary → Press and hold the confirm button until OK. (5) Backlight → Control the backlight to stay on or off
4
Communication → (1) Local address (2) Baud rate → optional 1200240048009600 Verify that n is not present


BWhen using a 4-20mA transmitter:
1
Flow → (1) Channel selection → Pachet channel, rectangular weir, equal width weir, triangular weir
(2) Liquid level channel → ultrasound → transducer or 4-20mA. (3) compensation → (internal compensation)


2Parameters →
(1) Upper limit of water level ->select 1.00m, which is the range of the liquid level transmitter (2) Lower limit of water level → select 0.000
(4) Traffic limit → large instantaneous traffic → commonly known as range (5) Lower limit of traffic → select 0.0000
(6) Water level cut-off → small water level cut-off, recommended 0.005-0.02m, adjusted according to actual situation


3System → (1) Password → Remember to remember after changing (2) Patrol display → Multiple options to select 8 parameters for automatic patrol display
(3) Zeroing → Accumulated zeroing, power outage zeroing (4) Restore → Verify Restore → Press and hold the confirm button until OK appears, not commonly used
(5) Backlight → Control the backlight to stay on or off


4Communication → (1) Local address (2) Baud rate → optional 1200, 2400, 4800, 9600 Verify that n has no verification

6、 Key points and steps for installation and debugging:
1
Select probe from the menu: Ultrasound → Ultrasonic transducer Or 4-20mA input

2Choose weir channel and flow measurement unit:
(1) Paxie slot, rectangular weir, equal width weir, triangular weir, and input the corresponding weir slot size into the instrument. After selecting the weir slot, press and hold the confirm button to display the size interface

(2) Flow measurement units: KG, m3, L, T


3Flow level measurement:
Flow level measurement is a necessary condition for the normal operation of instruments Emphasizing the importance of "air distance", only when the air distance is accurate, it indicates that the instrument is normal, and the rest of the work is much simpler

4If there is still instantaneous flow display without sewage flow, increase the number of "water level cut-off" and decrease the number of water level cut-off

7、 Analysis of reasons for abnormal instrument:
A
Liquid level display → "echo loss" or "FFFFFF" → indicates that the instrument has not received an echo
1
There are abnormalities in the wiring between the probe and the instrument: carefully check whether the connecting wires are reliable, whether there are any broken wires inside the wires, and if necessary, temporarily replace the external wiring and try it out
2
The surface condition of the measured liquid is complex (for example, there are a lot of foam and floating objects on the liquid surface), which leads to the poor reflection ability of the water level surface → clear the foam and floating objects


BWhen the liquid level changes, the air distance (liquid level) display number does not change
1
The liquid level height enters the blind zone of the transducer → raise the position of the ultrasonic transducer
2
The diameter of the static water well is too small or there is dirt or poor edge flatness inside the static water well → Increase the size of the static water well, clean the dirt or use a static water well material with smooth inner walls Change the installation position until the air distance stabilizes


CDisplay numbers with regular back and forth movements (characteristic: one of the numbers is fixed and unchanged)
1
There are relatively weak false targets above the measured sewage, which generate false echoes (sometimes absent), such as uneven height inside the static water well, and serious scaling on the inner wall of the clean water well after long-term use
2
We can determine whether the digital jitter interference comes from the outside or the instrument itself by using the following method: facing the ultrasonic transmitter towards the open sky, theoretically speaking, the instrument will not receive any echo at this time, and the instrument water level will prompt "echo loss" or "FFFFFF", indicating that the interference is from outside On the contrary, the digital jumping comes from the instrument itself and needs to be returned to the manufacturer for maintenance

8、 Wiring, external dimensions, and accompanying drawings:



6000CMG wiring instructions:
Using a four core shielded wire, the shielding layer is connected to the instrument ground GND at one end.

Wuxi Xingzhou Instrument Co., Ltd. and Wuxi Hudai (dAi) Instrument Factory are professional manufacturersManufacturers, morePlease contact our company for the information, thank you!