Welcome Customer !

Membership

Help

Shanghai Huazhu Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Shanghai Huazhu Electric Co., Ltd

  • E-mail

  • Phone

  • Address

    Jing'an District, Shanghai

Contact Now

Transformer three-phase ratio tester

NegotiableUpdate on 05/13
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The ATRT-03 transformer three-phase ratio tester automatically calibrates before each measurement to ensure measurement accuracy, without the need for regular adjustments or temperature compensation The result also displays the turn to turn ratio Winding polarity Percentage values of excitation current and turn ratio error

Product Details

变压器三相变比测试仪

ATRT-03Transformer three-phase ratio testercharacteristic

large-scale4×20character,backlightLCDdisplay screen.

Automatic calibration before each measurement,Ensure measurement accuracy,No need for regular adjustments or temperature compensation.

The result also shows the turn to turn ratio.Winding polarity.Percentage value of excitation current and turn ratio error.

Can be paired67Automatic testing of intermediate transformer type,No need to change the wiring method.

Confirm the wiring condition with the bottom voltage first,To avoid accidents caused by misconnecting wires,Add test voltage again.

4.5Inch thermal printer

storable200Complete Transformer Test Record with Pen,Maximum per record99group data.

Can be stored128Test Plan Setting for Pen Transformer.

RS232The interface can be accessed throughPCControl and browse stored results,ASCIIThe format can be automatically analyzed.

ATRT-03Transformer three-phase ratio testertechnical indicators

model

ATRT-03

ATRT-03B

ATRT-03A

measurement method

ANSI/IEEE-C57.12.90

Turn ratio measurement range

0.8~15,000(5Bit resolution)

匝比精度

0.8~1999:±0.1%,2,000~3,999:±0.25%,4,000~15,000:±1%@8Vac

0.8~1999:±0.1%,2,000~3,999:±0.20%,4,000~15,000:±1%@40Vac

0.8~1999:±0.1%,2,000~3,999:±0.15%,4,000~15,000:±1%@100Vac

test voltage

8Vac@1A , 40Vac@0.6A , 100Vac@0.1A

excitation current

0~2A

current accuracy

±1m A,±2%Read value(±1digit)

Phase angle measurement

0~360degree

相位角精度

±0.2degree(±1digit)

printer

4.5Inch thermal sensing type

Nothing

4.5Inch thermal sensing type

display screen

4×20character,backlightLCD

Calculator interface

RS-232C,19,200B aud

Test record storage

128Group setting/200Group test results(Nameplate voltage.匝比.Excitation current.phase angle)

PCsoftware

Window 95/98/NT/2000/XPcompatible.Standard Appendix

Safety Regulations

UL61010A-1 . CSAcertification(C22.2Nc.1010.1-92)





变压器三相变比测试仪

Japan Gongli High Voltage Megohmmeter312131223123

1Very suitable forCVInsulation testing of cables, electrical equipment, and high-voltage machines;

2Waterproof structure that can withstand even a small amount of rain;

3Dual scale display panel with automatic range mode;

43121High voltage megohmmeter DC test voltage2500Vmeasurement range(automatic conversion) 2GΩ/100GΩ(auto-ranging)

Main effective measurement range

precision0.1~50GΩ ±5%reading value

3121Japan Gongli High Voltage MegohmmeterAccuracy in other ranges ±10%Read numerical values or0.5%Scale value length output voltage and voltage setting indication---Voltage resistant communication5000V 1minute

power supplyR6P(AA)(1.5V)×8

Overall dimensions200(L)×140(W)×80(D)mm

weight approximately1Kg

Attachment7085(test line) 9039(Hard Carrying Case) R6P(AA)×8

User Manual

option8019(Structural probe) 8020(Recorder adapter)

3121/3122/3123Technical parameters of pointer type high-voltage megohmmeter:

Model

Functional Parameters

Kyoritsu3121

Kyoritsu3122

Kyoritsu3123

test voltage

2500V

5000V

5000V

10000V

measurement range

2G/100GΩ
(auto-ranging)

5G/200GΩ
(auto-ranging)

5G/200GΩ

(auto-ranging)

10G/400GΩ
(auto-ranging)

Once effective
Measurement range accuracy

0.1-50GΩ
±5%rdg

0.2-100GΩ
±5%rdg

0.2-100GΩ
±5%rdg

0.4-200GΩ
±5%rdg

Other range accuracy

±10%rdgor

0.5%The scale length

±10%rdgor0.5%The scale length

±10%rdgor0.5%The scale length

pressure resistance

5000V ACone minute

5000V ACone minute

5000V ACone minute

battery

R6P(AA)(1.5V)×8

R6P(AA)(1.5V)×8

R6P(AA)(1.5V)×8

volume

200(long)×140(wide)
×80(deep)mm

200(long)×140(wide)
×80(deep)mm

200(long)×140(wide)
×80(deep)mm

weight

about1kg

about1kg

about1kg

option

8019tester
8020Recorder adapter

8019tester
8020Recorder adapter

8020Recorder adapter





























变压器三相变比测试仪

Co branding3124High voltage insulation resistance meter

Product Introduction:

1Variable mode of rated test voltage(1kV~10kV)

2Automatic discharge function

3Double scale

4Low voltage use1000V/100MΩ Insulation resistance meter

53Various power supply methods(Built in batteryAC100VCar batteries)

6Recorder output port

Technical Indicators:

Specification Model

Functional Parameters

3124

DC test voltage

1K-10KVadjustable

1000V

measurement range(automatic conversion)

1.6GΩ/100GΩ(auto-ranging)

100MΩ

Main effective measurement range

0.05-50GΩ

1-100MΩ

precision

±10%reading value

Accuracy in other ranges

±1%Scale value length

Output voltage and voltage setting indication

direct current0-10KV±2%Reading value ±2bit

pressure resistance

communication5000V 1minute

power supply

nickel-Chromium rechargeable battery(1.2V)×8

Overall dimensions

200(L)×140(W)×80(D)mm

weight

approximately1.5Kg

Attachment

7082(test line)7083(test line)7084(test line)
8079(120V) or 8080(220V)90698Save battery
































变压器三相变比测试仪

5408Leakage switch tester(日本共立KYORITSU)

Product Introduction:

Easy to operate(Remote control testing)By using the remote control testing function, the test can be automatically performed by simply connecting the test line to the terminal. The initial display is the circuit voltage,1Start testing the action time or sensitivity current to automatically determine the voltage in seconds. Due to the ability to automatically distinguish100Vand200VThe measurement of circuit voltage does not require manual switching of different voltage action times. ×1/2When measuring the range, conduct a rated non operating current test. ×1、 ×5When measuring range, the action time can be testedSensitivity current test. Automatically increase the test current, indicating the current value at the time of trippingAutomatically detect contact voltage. When using a grounding wire for testing, in order to prevent electric shock caused by poor grounding, the voltage of the grounding electrode or protective conductor will be automatically detected when the test current flows. Once it reachesAC50VStop testing and issue a warning.

Dustproof and waterproof function

Backlight function

Technical Indicators:


model

5408

Fault state setting

×5

×1

×1/2

Sensitivity current(mA)

Rated operating current

15/30/50/100mA

15/30/50/100/200/500mA

Fault action time

0-200ms

0-2000ms

0-2000ms

300ms×15return

precision

Rated operating current

+2%~+8dgt

+2%~+8dgt

-8%~-2dgt


Fault action time

1%rdg±3dgt

1%rdg±3dgt

1%rdg±3dgt

Working Voltage

100V±10%The200V±20%The50/60Hz

endure press

3700Vper minute

IP

IEC60529-IP54

body accumulate

186(L) x 167(W) x 89(D)mm

heavy quantity

about960gram(Contains battery)

Appendix document

71287129TheR6P(Sum-3)User Manual

option







































变压器三相变比测试仪


Fluke1625Grounding resistance tester

Fluke 1623and1625It is an excellent grounding resistance tester that can measure all four types of grounding resistance. especiallyFluke 1623and1625The measurement of grounding resistance can be completed using only one current clamp - no auxiliary pole method. This method does not require the use of auxiliary grounding electrodes or the disconnection of grounding rods.

test mode

3Jihe4 Polar potential drop method - a standard grounding resistance testing method using two grounding electrodes.

Selection method test - without disconnecting the grounding rod, the grounding resistance can be measured using a combination of grounding electrode and current clamp.

Non auxiliary pole method - a highly innovative testing solution that does not require the use of grounding electrodes and can measure the resistance of the grounding loop using only current clamps.

Fluke 1625It also provides the following advanced features

Automatic frequency control(AFC)Automatically identify interference and select measurement frequency to minimize the impact of interference and provide more accurate grounding resistance values.

R*Measurement - Calculation in55 HzThe grounding impedance below more accurately reflects the true grounding resistance when a grounding fault occurs.

Adjustable limit value - can quickly check test results.

Fluke 1625 GEOCharacteristics of grounding resistance tester:

3Jifa and4Measurement of Polarized Grounding Resistance

4Polar method for measuring soil resistivity

2Polar method for measuring AC resistance

2Jifa and4Polar method for measuring DC resistance

Selection method test, no need to disconnect the grounding connection(1Current clamp)

Without auxiliary pole method, quickly test the grounding loop(2Current clamp)

measurement55 HzGround impedance below

Automatic frequency control(AFC)(94105111The128 Hz

Voltage measurement switchable20/48V

Programmable limits and settings

On/off test with buzzer sound prompt

Fluke 1625/1623 GEOGrounding resistance tester


RA 3Measurement of Polarized Grounding Resistance(IEC 1557-5)



measure voltage

Fluke 1623

Vm = 48 V ac

Fluke 1625

Vm = 20/48 V ac




short-circuit current

Fluke 1623

> 50 mA

Fluke 1625

250 mA ac




measurement frequency

Fluke 1623

128 Hz

Fluke 1625

94105111The128Hz




resolution

Fluke 1623

0.001Ω10 Ω

Fluke 1625

0.001Ω100 Ω




Measurement range

Fluke 1623

0.001Ω19.99 k Ω

Fluke 1625

0.001Ω299.9 k Ω




Basic error

Fluke 1623

±(2 %reading+ 3a character)

Fluke 1625

±(2 %reading+ 2a character)




working error

Fluke 1623

±(5 %reading+ 3a character)

Fluke 1625

±(5 %reading+ 5a character)



RA 4Measurement of Polarized Grounding Resistance(IEC 1557-5)

measure voltage

Fluke 1623

Vm = 48 V ac

Fluke 1625

Vm = 20/48 V ac


short-circuit current

Fluke 1623

> 50 mA

Fluke 1625

250 mA ac


measurement frequency

Fluke 1623

128 Hz

Fluke 1625

94105111The128Hz


resolution

Fluke 1623

0.001Ω10 Ω

Fluke 1625

0.001Ω100 Ω


Measurement range

Fluke 1623

0.001Ω19.99 k Ω

Fluke 1625

0.001Ω299.9 k Ω


Basic error

Fluke 1623

±(2 %reading+ 3a character)

Fluke 1625

±(2 %reading+ 2a character)


working error

Fluke 1623

±(5 %reading+ 3a character)

Fluke 1625

±(5 %reading+ 5a character)









RA 3Polar method for measuring grounding resistance, using current clamps

measure voltage

Fluke 1623

Vm = 48 V ac

Fluke 1625

Vm = 20/48 V ac


short-circuit current

Fluke 1623

> 50 mA

Fluke 1625

250 mA ac


measurement frequency

Fluke 1623

128 Hz

Fluke 1625

94105111The128Hz


resolution

Fluke 1623

0.001 Ω10 Ω

Fluke 1625

0.001 Ω10 Ω


Measurement range

Fluke 1623

0.001 Ω19.99 k Ω

Fluke 1625

0.001 Ω29.99 k Ω


Basic error

Fluke 1623

±(7 %reading+ 3a character)

Fluke 1625

±(7 %reading+ 2a character)


working error

Fluke 1623

±(10 %reading+ 5a character)

Fluke 1625

±(10 %reading+ 5a character)


RA 4Extreme selection method for measuring grounding resistance, using current clamps

measure voltage

Fluke 1623

Vm = 48 V ac

Fluke 1625

Vm = 20/48 V ac


short-circuit current

Fluke 1623

> 50 mA

Fluke 1625

250 mA ac


measurement frequency

Fluke 1623

128 Hz

Fluke 1625

94105111The128Hz


resolution

Fluke 1623

0.001 Ω10 Ω

Fluke 1625

0.001 Ω10 Ω


Measurement range

Fluke 1623

0.001 Ω19.99 k Ω

Fluke 1625

0.001 Ω29.99 k Ω


Basic error

Fluke 1623

±(7 %reading+ 3a character)

Fluke 1625

±(7 %reading+ 2a character)


working error

Fluke 1623

±(10 %reading+ 5a character)

Fluke 1625

±(10 %reading+ 5a character)


No auxiliary pole method

measure voltage

Fluke 1623

Vm = 48 V ac

Fluke 1625

Vm = 20/48 V ac


measurement frequency

Fluke 1623

128 Hz (Provided upon request125 Hz)

Fluke 1625

94105111The128Hz


Noise current(Iext)

Fluke 1623

Max. Iext = 10 A (ac) (RA < 20 Ω)


Max. Iext = 2 A (ac) (RA < 20 Ω)

Fluke 1625

Max. Iext = 3 A


resolution

Fluke 1623

0.001 Ω0.1 Ω

Fluke 1625

0.001 Ω10 Ω


Measurement range

Fluke 1623

0.001 Ω199.9 k Ω

Fluke 1625

0.001 Ω29.99 k Ω


Basic error

Fluke 1623

±(7 %reading+ 3a character)

Fluke 1625

±(7 %reading+ 2a character)


working error

Fluke 1623

±(10 %reading+ 5a character)

Fluke 1625

±(10 %reading+ 5a character)


Environmental parameters:

Operating Temperature


-10 °C+50 °C


Operating Temperature


0 °C+35 °C


Nominal temperature


+18 °C +28 °C


Storage temperature

Fluke 1623

-20 °C +60 °C

Fluke 1625

-30 °C +60 °C


climate type


C1 (IEC 654-1)-5 °C+ 45°C5 %95 % RH


protection level


The shell isIP56The battery compartment cover isIP40, followEN 60529


Safety technical parameters

security level


CAT II300 V


Mechanical and general parameters

display

Fluke 1623

1999 One wordLCDDisplay Screen - Can display special symbols/Identification, with a numerical height of25 mmFluorescent backlight illumination

Fluke 1625

2999 One wordLCD 7 Segmented LCD display screen, capable of displaying special requirements/Marking, backlit illumination


size


133 mm×187 mm×250 mm


weight

Fluke 1623 + 1625

1.1 kg (Contains battery)


warranty period


2 year


battery life

Fluke 1623

typical value> 3000sub-measurement

Fluke 1625

typical value 3000 sub-measurement(RE+RH1 kΩ)


typical value 6000 sub-measurement(RE+RH10 kΩ)



Fluke 1625 GEOGrounding resistance testerGEOGrounding resistance tester

Fluke 1625tester

2 Test line

battery

User Manual

Fluke 1625 kit GEOGrounding resistance testerGEOGrounding resistance tester

Tool kit, advancedGeoGrounding resistance tester

Fluke 1625tester

2 Test line

4 Root grounding rod

3 Rolling wire(2 roll 25 Mi,1 roll 50 Rice)

2 A clamp table (one for induction and one for detection)

battery

User Manual

Durable and sturdy portable bag

变压器三相变比测试仪





DigiTMRCircuit breaker time mechanical characteristic tester

characteristic

Analysis of complete operation of circuit breaker contacts:

Open, close, open-Close, close-Open, open-close-open

Analyze contact time,stroke,speed

3A dry contact input channel:

Can detect the main contact and insertion resistance contact time

2A voltage input channel:

A monitoringDCPower supply or coil resistance(0-300Vdcorpeak ac),The second monitoringA/BSwitching voltageON/OFFBuilt in status

CT:Recordable jumps/Closing current level and duration

1A digital stroke sensor channel:Measure stroke,Overshoot and bounce back

No calibration or setting required,Computable speed

storable100Pen result recording and99Group testing setup

Built in thermal printer

model

DigiTMR

Dry contact input

3A dry contact input;Can detect the main contact and insertion resistance contact time

Timing length

1sThe10sThe20s(optional)

Timing resolution

1During the second period, it is ±100Ms; 10During the second period, it is ±1.00ms; 20During the second period, it is ±2.00ms

Timing accuracy

±0.05%Reading value ±0.1ms@1During the second period

Dry contact channel protection

Fuses protect all isolated power sources;All contact inputs are grounded before testing;

TVSHejina diode protection

Contact detection range

Closed:<20Ω,Open:>5000Ω

Resistance detection range

50~5000Ω

Trigger input voltage

open/Closed:30~300Vdcorpeak ac

Voltage sensing input range

V1:Analog input;0-255Vdcorpeak ac,sensitivity:±1V

V2:Voltage Sensing(have/Nothing)input;30-300Vdcorpeak ac

Circuit breaker operation

Open, close, open-Close, close-Open, open-close-open

Initial capacity of circuit breaker

30A/250Vac/dc max

Initial current range

1A non-contact Hall effectCT,scope0-20A,dc~5kHz

Stroke sensor input

1A digital stroke sensor channel;Linear range:0-60in(±0.005in)

Rotation range:0~360°(±0.006°)

Point difference value of contact stroke

Measurement "Slow-close”Distance between contact points

display screen

4lineX 20character,backlightLCD

printer

4.5Inch thermal printer,Printable contact stroke graphics and numerical table

Test data storage

100Pen result recording and99Group testing setup

computer interface

RS-232C, 19,200 Baud

PCsoftware

Windows® 95/98/NT/XPStandard attachments

Safety Regulations

Design complies withUL 61010A-1TheCAN/CSAcertification(C22.2 No. 1010.1-92)





























变压器三相变比测试仪


CBPS-300Circuit breaker DC power supply

characteristic

Adjustable voltage DC power supply controlled by microprocessor

Can replace substation batteries when testing circuit breakers

Can be easily based onANSI C37.09orIEC 56Test the minimum tripping voltageOverload current protection.

2×16Character, backlightLCD.

Can be used for testing circuit breakers,Operate open and closed line diagrams in full voltage mode or minimum voltage condition.

can be paired withCT-6500S2/7000S2/7500S2/8000Used in combination.

display screen

2×16Characters, backlightLCD

DCvoltage value

0300VDC,±1V

coilDCpower supply

DCoutput

current

Adjustment degree

24Vdc

10A

<6%

48Vdc

10A

<3%

120Vdc

6A

<2%

250Vdc

3A

<2%

The interval between opening and closing is only1second

Starting circuit

Built in solid-state initial circuit for opening and closing

Charging motorDCpower supply

No load voltage

load current

Load interval

Full load voltage

48Vdc

12A

60s

40Vdc

48Vdec

18A

20s

30Vdc

120Vdc

12A

60s

90Vdc

120Vdc

18A

20s

70Vdc

240Vdc

6A

60s

200Vdc

240Vdc

9A

20s

185Vdc

Output protection

All DC outputs are protected against overcurrent

Safety Regulations

UL 61010A-1TheCAN/CSA(C22.2 No. 1010-92)

conductor

10Three sets of inch wires, one set of grounding wire and one set of power wire, and one wire carrying bag






























变压器三相变比测试仪


LM 2000portableSF6Gas leak detector

application:

Factory gas or on-siteSF6Leakage detection of gas insulated power equipment,for example:Power circuit breakers, enclosed switchesSF6Insulated transformers, etc. UV lamp ionization method,Oxygen andSF6in the air,Will ionize due to ultraviolet radiation,Therefore, taking advantage of its mobility differences,It can easily and quickly measure small amounts in the airSF6The concentration.

characteristic:

Gas flow sampling,It can be controlled by the flow controller on the front panel to increase the sampling flow rate in windy conditions,To maintain accuracy.

Large LCD display screen: SF6concentration(ppm),Leakage rate(ml/s),Annual leakage rate(g/y)Directly displayed on the screen with high stability and sensitivity,Not affected by environmental temperature or humidity.

The built-in calibration software can perform single point self calibration and multi-point standard calibration.

storable50Pen test results

specification


Measuring gases

SF6gas

measurement range

0 ~ 100 ppm

detection sensitivity

1 ppm

Reproducibility accuracy

±5 %Full scale

response time

4second(Depending on gas flow rate and pipeline length)

Traffic rate

0 ~ 30 L/H










变压器三相变比测试仪


DP99-IIIDigital dew point meter

Portable instruments designed for on-site and factory use,Used to measure industrial gases,for example: SF6, N2,The water content inside.

high precision,Short term measurement,And it is easy to operate.

characteristic:

Short term measurement:Using digital control to significantly reduce measurement time,Generally, on-site measurements only require an average of3-5minute.

Save gas:Due to short-term measurement,The gas consumption required for a single measurement is significantly reduced.

ppmRead value:Equipped with a large screen displaying dew point temperatureppmNumerical values, graphs of equilibrium processes, flow rates, etc.

Built in printer.

working principle:Principle of Frozen Mirror Surface-Composed of four parts:lighting system,cooling system,Gas system,Control and Measurement System

specification




-55

At ambient temperature23At ℃

precision

±0.2°C,± 1 digit(typical)

reproducibility

±0.1°C,± 1 digit

Read value

Dew point temperatureppmVBalance process graphics, flow velocity

Measuring principle

Dew point mirror, electroplated rhodium(rhodium)Optical detection

cooling

ThermoelectricPeltier-Battery4step

Sampling gas flow rate

15 ~ 60 l/h,rated30 ~ 40 l/h

Sampling gas pressure

minimum10 mbar,reachable10 bar (1 kPa ~ 1 MPa)

response time

2/second

Mirror inspection

Choose 'CHK”Menu-button,Perform manual inspection

alarm

No gas/The flow rate is too high/照明太暗/unbalanced














变压器三相变比测试仪


Single phase relay protection testerSverker 780/760/750/650

characteristic

Test all single-phase protection and automatic reclosing tests

Output up to250A

Can communicate with computers

Output up to200A

Can communicate with computers

It can also measure impedance(Z)Resistance(R)Reactance(X), meritorious service(p)Visual power(S)Reactive power(Q)Power factor(cosBoth current and voltage can be used as benchmarks, such as ф, etc

10Group testing storage, automatic testing of different types

Reading lock (hold) function. Easy to record

Integrated design integrates voltage, current sources, and meters for easy use

Technical Specifications

AC current output:

scopeA

No load voltage(V

Full load voltage(V

Full load current(A

Carrying load/Recovery time (minutes)

0-10

90

75

10

2/15

0-40

25

20

40

1/15

0-100

10

8

100

1/15

0-100

10

--

250

1second/15minute

communication/DC voltage output:

scope

No load voltage(V

Full load voltage(V

Full load current(A

Carrying load/Recovery time (minutes)

0-250V AC

290

250

3

10/45

0-300V AC

320

250

2

10/45

Assisted communication/DC voltage output:

Voltage range(V

No load voltage(V

Full load voltage(V

rated current(A)

0-60VAC

70V

60V

0.25A

60-120VAC

130V

120V

O.25A

20-130VDC

130V


O.4A

130-220VDC

220V


O.4A

Other parameters
timer:LEDdisplay0.000-999.9S,The accuracy is:1ms
Ammeter: Internal0.00-200.0A;外部0.000-6.000A
Accuracy: Internal Range:0.5%External range:AC 0.5% / DC 0.5%
Voltage meter: Range0.00-600.0V; AccuracyAC 0.5%DC 0.5%
Phase angle: Range0-359°, accuracy1°;
volume350×270×220mm
weight: 18kg.


变压器三相变比测试仪


S8000Cold mirror dew point meter

Range:-60-- +40dp

The dual path system has good sensitivity and automatic compensation for changing gas temperatures

Measurement resolution:0.001

Articulated sensors make monitoring and cleaning of mirrors easy

All real-time measurement results are displayed

Multiple units display:dp + temp°C +°F

%rh, g/m3, g/kg

ppm(v), ppm(w) SF6

ml/min,

psia, Bar, Kpa

Quick measurement display

pressure20bara

throughSDCard andUSBInterface for data collection of pressure, humidity, and flow rate

high-resolutionLCDdisplay screen

The menu operation is simple and convenient

变压器三相变比测试仪

TAP-4On load voltage regulating switch analyzer

The first instrument that uses vibration acoustic analysis to detect faults in on load voltage regulating switches.

Non invasive testing of transformers in operation (testable)800kVTransformer)

TAP-4Can identify various electrical and mechanical issues:

Contact wear

Driver and synchronization issues

Brake failure

Abnormal arc

This non-invasive testing method immediately diagnoses on load voltage regulationThe status of the switch and the issues it has.

New means of status maintenance

Transformer on load tap changer(OLTC)It is a component with heavy workload for transformers,He moves several times a day,According to statistics,Transformer malfunction40%Caused by on load voltage regulating switch. The on load voltage regulating switch needs maintenance, and lack of maintenance may cause problemsThe consequences of fear and significant property damage.

Vibration Acoustic Analysis

Thanks to the innovative testing method based on recording vibration acoustic signal analysis,TAP-4Conduct a complete inspection of the interior of the on load voltage regulating switch,And there's no need to open him.

Vibration acoustic analysis has a history of more than ten years in the development and testing of hydropower in Quebec, Canada. This diagnostic method has been usedGuidelines for maintenance of two transformersIEEE. PC57.143andCigreA2,34Recognized.

DIACThe core of problem-solving

DIACSoftware driven from a simple interfaceTAP-4Thanks to the vibration signal analysis technology,DIACexplanationRecord the events and report them to the operator in a color chart.

This makes it possible to quickly diagnose and accurately and efficiently maintain on load voltage regulating switches.


Advantages:

Applicable to all on load voltage regulating switches(ABBRheinhausen,GEWestinghouse

Fast, automated testing sequence (less than)10Minutes)

Simple and minimal operational testing(+1TAPEvery test)

Automatically create easy to understand Colorful report

For the majorityOLTCThe testing plan

Based on exceeding1000Taiwan's accumulated experience

Statistical analysis of distribution and types

Provide the result of a single tap

Fast, online diagnosis

trend analysis

Recording data is easy to classify

Comparison of different test results