- Phone
-
Address
203 Hongyun Road, Wuxi City, Jiangsu Province
Wuxi Guanya Intelligent Equipment Co., Ltd
203 Hongyun Road, Wuxi City, Jiangsu Province



model |
SUNDI-125 SUNDI-125W |
SUNDI-135 SUNDI-135W |
SUNDI-155 SUNDI-155W |
SUNDI-175 SUNDI-175W |
SUNDI-1A10 SUNDI-1A10W |
SUNDI-1A15 SUNDI-1A15W |
|||||||
Medium temperature range |
-10℃~+200℃ |
||||||||||||
control system |
Feedforward PID, Model free Self Building Algorithm, PLC Controller |
||||||||||||
Temperature control mode selection |
The material temperature control and equipment outlet temperature control modes can be freely selected |
||||||||||||
temperature difference control |
The temperature difference between the equipment outlet temperature and the reaction material temperature can be controlled and set |
||||||||||||
program editing |
5 programs can be developed, each program can be programmed with 40 steps |
||||||||||||
communication protocol |
MODBUS RTU protocol RS 485 interface |
||||||||||||
External temperature feedback |
PT100 or 4-20mA or communication given (default PT100) |
||||||||||||
temperature feedback |
Three temperature points: inlet temperature, outlet temperature, and reactor material temperature (external temperature sensor) of the thermal conductive medium of the equipment |
||||||||||||
Temperature control accuracy of thermal conductive medium |
±0.5℃ |
||||||||||||
Temperature control accuracy of reaction materials |
±1℃ |
||||||||||||
Heating power kW |
2.5 |
3.5 |
5.5 |
7.5 |
10 |
15 |
|||||||
Cooling capacity kW |
200℃ |
2.5 |
3.5 |
5.5 |
7.5 |
10 |
15 |
||||||
20℃ |
2.5 |
3.5 |
5.5 |
7.5 |
10 |
15 |
|||||||
-5℃ |
1.5 |
2.1 |
3.3 |
4.2 |
6 |
9 |
|||||||
|
Flow pressure max L/min bar |
20 |
35 |
35 |
50 |
50 |
75 |
|||||||
2 |
2 |
2 |
2 |
2 |
2.5 |
||||||||
compressor |
Hai Li |
Emerson Valley Wheel/Danfoss Vortex Compressor |
|||||||||||
expansion valve |
Danfoss/Emerson Thermal Expansion Valve |
||||||||||||
evaporator |
Danfoss/High Power Plate Heat Exchanger |
||||||||||||
control panel |
7-inch color touch screen, temperature curve display and recording |
||||||||||||
safety protection |
Having self diagnostic function; Refrigerator overload protection; High pressure switch, overload relay, thermal protection device and other safety protection functions. |
||||||||||||
Closed loop system |
The entire system is a fully enclosed system, which does not produce oil mist at high temperatures and does not absorb moisture from the air at low temperatures. The system does not increase pressure due to high temperatures during operation, and automatically replenishes the heat transfer medium at low temperatures. |
||||||||||||
refrigerant |
R-404A/R507C |
||||||||||||
interface dimensions |
G1/2 |
G3/4 |
G3/4 |
G1 |
G1 |
G1 |
|||||||
|
Water cooled type W Temperature 20 degrees |
600L/H 1.5bar~4bar G3/8 |
800L/H 1.5bar~4bar G1/2 |
1000L/H 1.5bar~4bar G3/4 |
1200L/H 1.5bar~4bar G3/4 |
1600L/H 1.5bar~4bar G3/4 |
2000L/H 1.5bar~4bar G3/4 |
|||||||
Dimensions (Water) cm |
45*65*120 |
50*85*130 |
50*85*130 |
55*100*175 |
55*100*175 |
70*100*175 |
|||||||
Dimensions (Wind) cm |
45*65*120 |
50*85*130 |
55*100*175 |
55*100*175 |
70*100*175 |
70*100*175 |
|||||||
Explosion proof size (wind) cm |
45*110*130 |
45*110*130 |
45*110*130 |
55*120*170 |
55*120*170 |
55*120*170 |
|||||||
Positive pressure explosion-proof (water) cm |
110*95*195 |
110*95*195 |
110*95*195 |
110*95*195 |
110*95*195 |
120*110*195 |
|||||||
Regular weight kg |
115 |
165 |
185 |
235 |
280 |
300 |
|||||||
Power supply 380V 50HZ |
AC 220V 50HZ 3.6kW |
5.6kW |
7.5kW |
10kW |
13kW |
20kW |
|||||||
Optional air-cooled size cm |
/ |
50*68*145 |
50*68*145 |
50*68*145 |
/ |
/ |
|||||||




Temperature control unit TCU for the reaction kettle of the refrigeration and heating integrated machine
Temperature control unit TCU for the reaction kettle of the refrigeration and heating integrated machine
Facing the overwhelming market demandHow to choose a suitable device for the needs of chiller hot and cold integrated machine products has become a difficult problem for users. The following key points can be referred to:
(1) Temperature range
The first thing to consider isDoes the temperature control range of the chiller's integrated cold and hot machine match its own business needs. The temperature requirements vary greatly among different industries and application scenarios. It is essential to ensure that the selected chiller integrated cold and hot machine can cover the required low and high temperature limits, avoiding situations of "small horses pulling big cars" or "overusing talents".
(2) Temperature control accuracy
If you are engaged in industries that require high temperature accuracy, such as biopharmaceutical research and development, electronic manufacturing, etc., then temperature control accuracy is of utmost importance. Carefully compare the temperature control accuracy indicators of different products and choose the one that can meet or even exceed your accuracy requirementsThe chiller integrated cold and hot machine model ensures that the production and experimental processes are not affected by temperature fluctuations.
(3) Cooling and heating power
The cooling and heating power is directly related to the heating and cooling speed of the equipment and whether it can meet the needs of large-scale production or high-intensity experiments. Reasonably evaluate the required cooling and heating power based on the actual application scenario's heat load, ensuringThe chiller integrated cold and hot machine can "fully activate" at critical moments and quickly reach the set temperature.

The principles and parameters of various equipment from Wuxi Guanya are for reference only. The equipment actually received by different customers is designed and produced according to their own working conditions and parameters. There are certain differences in equipment configuration, price, and model, and the specific details are subject to sales contact and communication.