The TD1150 Transformer Winding Temperature Controller Tester is a testing equipment designed by Tianheng Measurement and Control based on customer needs such as power and metering, specifically for detecting transformer winding temperature controllers. Its built-in current standard source is used to output analog signals to the temperature controller, while the current standard meter is used to measure the thermal analog signals of the transformer winding temperature controller. The measurement and output channels are independent of each other and have good electrical isolation and protection functions.
This temperature controller tester is designed by Tianheng Measurement and Control to test temperature controllers for transformer windings based on customer needs such as power and metering. It has a built-in current standard source for outputting analog signals to the temperature controller, and a current standard meter for measuring the thermal analog signals of the transformer winding temperature controller. The measurement and output channels are independent of each other and have good electrical isolation and protection functions. The measurement uncertainty of the product is at level 0.05, which can meet the electrical measurement requirements of JB/T 8450-2016 "Winding Temperature Controllers for Transformers". The product can be widely used in power and metrology institutes, third-party professional testing institutions, and research laboratories in higher education institutions.
TD1150 Transformer Winding Temperature Controller TesterProduct features
ACI output: 0.1 A to 6 A
ACI measurement: 0.5 A to 6 A
F:45 Hz~65 Hz
Current accuracy: 0.05 level
Load capacity: 60 VA
Adjustment fineness: 0.002%
Distortion:<0.5%
Auxiliary power supply: DC24 V
TD1150 Transformer Winding Temperature Controller TesterTechnical Specifications
| AC current output range |
1A、5A |
| Measurement range of AC current |
5A |
| Output/measurement margin |
(0~120 %)*RG |
| Regulating fineness |
0.002%*RG |
| frequency |
45Hz~65Hz, Best measurement uncertainty: 0.01Hz |
| display digits |
6-digit decimal system |
| Output stability |
0.01%/min |
| Measurement uncertainty (k=2) |
300 ppm*RD+ 200 ppm*RG |
| Output load capacity |
60 VA |
| distortion |
<0.5% |
| auxiliary power supply |
DC24V (± 0.5%), output current not less than 200mA |
| Note: RD is the reading value, RG is the range value; The measured AC current must be at the same frequency as the AC current source |
General technical specifications
| power supply |
AC (220±22)V, (50±2) Hz |
| warm-up time |
30 minutes |
| temperature performance |
Working temperature: 0 ℃~45 ℃; Storage temperature: -20 ℃~70 ° C |
| Humidity performance |
Working humidity:<80% @ 30 ° C,<70% @ 40 ° C,<40% @ 50 ° C Storage humidity: (20%~80%) R · H, no condensation |
| altitude |
<3000m |
| Instrument quality |
About 10kg (desktop) |
| communication interface |
RS232 |
| Overall dimensions |
350 mm(W) X 330 mm(D) X 170 mm(H) |