Sulfur hexafluoride gas leakage alarm device

NegotiableUpdate on 05/07
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The display area of the sulfur hexafluoride gas leakage alarm device adopts a large screen LCD display with clear text, and uses LED backlight, which increases the brightness and prolongs the service life compared to LED backlight; Adopting embedded high-performance microprocessing, supplemented by various compensation measures in software and hardware, the consistency and temperature drift problems of sensors are solved, thereby ensuring the accuracy and stability of measurements.

Product Details

Product Name:Sulfur hexafluoride gas leakage alarm device
Device features
1Sulfur hexafluoride gas leakage alarm deviceThe display area adopts a large screen LCD display, which displays clear text and uses LED backlight, which increases the brightness and prolongs the service life compared to LED backlight.
2. The device adopts embedded high-performance microprocessing, supplemented by various compensation measures for software and hardware, to solve the problems of sensor consistency and temperature drift, thereby ensuring the accuracy and stability of measurement.
3. The system host has human infrared detection and voice alarm prompt functions, ensuring the safety of personnel entering.
4. The gas probe adopts a boundary current oxygen sensor and a new SF6 gas semiconductor sensor as core components, and is composed of a high-performance embedded microcontroller and a high-performance amplifier to form a signal processing unit, which has significant characteristics of high accuracy, stability, reliability, and long life.
装置功能
1. SF6 gas concentration exceeding standard detection
Display the SF6 gas content at each gas sensor alternately. When the SF6 gas concentration exceeds 800ppm, the display shows that the content exceeds the standard.
2. Oxygen concentration detection
Display the oxygen concentration values at each gas sensor in the switch room alternately.
3. Temperature and humidity display
The system can detect and display the temperature and humidity values in the current switch room
4. Display the last start and stop time of the fan
The staff can determine whether forced ventilation is necessary before entering the switch room based on this information.
5. Infrared detection function
The system can detect personnel who want to enter the switch room and provide voice prompts for ventilation when the fan is not working, until the personnel leave or the fan is started.
6. Forced ventilation
When the fan is in a stopped state, press the forced button and the system can perform forced ventilation for 15 minutes.
7. Absolute oxygen alarm
When the oxygen concentration is below 19.6%, an electric shock alarm signal is output and an on-site voice alarm is triggered.
8. Fan control time
When the SF6 gas content exceeds the standard (800ppm) or the oxygen concentration is too low (≤ 19.6%), control the fan to start ventilation, and each ventilation time should be at least 15 minutes.
9. Timed ventilation
The system can set the start and stop times of the fan every day to ensure that the switch room is ventilated at least once a day.
10. Voice function
The system can provide voice prompts for ventilation and report the current oxygen concentration and SF6 gas content in the switch room after ventilation is completed, to remind staff whether it is safe to enter the switch room.
11. LCD display automatic turn on/off backlight
When a patrol personnel approaches, the system automatically lights up the LCD background lighting. About 40 seconds after the personnel leave, the LCD rear static lighting automatically turns off.
Technical specifications
1. Rated working power supply: AC Ac: 85V to 265V
DC: 110V to 340V
2. Rated power consumption: Host stone 25VA sensor ≤ 6VA
3. Control fan capacity: AC220V/15A (passive conversion)
Alarm contact capacity: AC220V/5A
Technical performance indicators of sulfur hexafluoride gas leakage alarm device
1. Probe detection accuracy: Oxygen concentration ≤ ± 1% F.S SF6 ≤ ± 20% threshold
2. Probe detection range: Oxygen 1.0%~25.0% SF6>800ppm
3. Temperature display range: -55 ℃~+125 ℃
4. Humidity display range: 10% to 95% RH
5. Probe stability: Oxygen ± 0.5% F.S
6. Probe repeatability: Oxygen ± 0 5 % F.S
7. Oxygen concentration alarm point: 19.6%
8. Fan starting concentration point: Oxygen ≤ 19.6% SF6 ≥ 8OOppm
9. Minimum time for each non timed start of the fan: 15 minutes
10. Communication interface: RS-485 (MODBUS protocol)
environmental conditions
1. Working atmospheric conditions:
Temperature: -25 ℃~+50 ℃
Humidity: ≤ 93% RH or no condensation
Atmospheric pressure: 86Kpa to 106Kpa
Environmental conditions: (1) Severity level I;
(2) The environment must not contain acidic, alkaline, or other corrosive or explosive gases such as oil, smoke, dust, etc;
(3) The environment should have facilities to defend against rain, wind, snow, sand, and other factors.
2. Storage atmospheric conditions:
Temperature: -40 ℃ to+60 ℃
Humidity: 5% to 98% RH or no condensation
Atmospheric pressure: 86Kpa to 106Kpa
Appearance and structure
The host of the JLK-2004 SF6 switchgear environment intelligent monitoring system adopts a wall mounted chassis. The wiring method adopts rear wiring, and the device uses flame-retardant small crimping terminals. The external dimensions and installation opening dimensions are shown in Figure 1.
System wiring diagram
Precautions
1. The temperature control for the host usage should be between -50 ℃ and 50 ℃
2. The probe should avoid the intrusion of a large amount of dust and chemicals during use.
3. The service life of the probe shall not be less than 3 years. If it exceeds 3 years, it is necessary to contact the manufacturer for calibration or replacement.
4. At least one gas probe needs to be installed below each SF6 switch.
5. The infrared probe in the basic configuration is ceiling mounted. If wall mounted installation is required, please specify it when ordering.
6. When ordering this product, the length of the connecting cable for the infrared probe that matches the host should be specified
7. This product comes with a "three guarantee" policy for one year from the date of purchase, with lifetime maintenance.