Split type high-temperature wind speed transmitter for hot press tank

NegotiableUpdate on 05/16
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

HXWD818 series wind speed and air volume sensor Overview: The HXWD818 series thermal wind speed and air volume sensor is developed specifically for measuring wind speed and air volume in ducts. It solves the problem of turbulent airflow in ducts, ensures high-precision measurement even at low wind speeds, has strong anti pollution capabilities, low maintenance costs, and high cost-effectiveness. It is an ideal replacement for hot film wind speed sensors and NTC thermal wind speed sensors, suitable for wind speed measurement in high temperature and high humidity environments. $r $n cans

Product Details

HXWD818 series wind speed and air volume sensor
Overview:HXWD818Series thermal wind speed and volume sensorIt is developed specifically for measuring wind speed and air volume in ducts, solving the problem of turbulent airflow inside ducts. It can still ensure high-precision measurement at low wind speeds, has strong anti pollution ability, low maintenance costs, and high cost-effectiveness. It is an ideal replacement product for hot film wind speed sensors and NTC thermal wind speed sensors, suitable for wind speed measurement in high temperature and high humidity environments.
Features:split-type designAccurate measurement can still be made at low wind speedsConvenient verification and good long-term stability

Application fields:Ventilation for tape casting machines, tunnel ovens, hot press tanks, textile air supply, coating machine air supply, process exhaust high-temperature ventilation systems, etcfieldoccasion
Installation:Make holes according to the length of the sensor probe or through holesPlastic flange fixed installation. When adjusting the angle to match the wind direction of the sensor and controlling the total air supply volume, when installing the control air valve behind the static pressure box, the distance between the branch air duct or air valve installed in front of the air supply valve should not be less than 1.5m. When measuring the air supply volume in the room, the measurement method should be adjusted according to the actual situation.
Technical Specifications

model

HXWD81805

HXWD81830

HXWD81870

measurement range

0-5m/s

0-30m/s

0-70m/s

measurement accuracy

2%

3%

5%

resolution

0.01m/s

0.01m/s

0.01m/s

working power supply

DC13...24V

DC13...24V

DC13...24V

frequency

50/60HZ

50/60HZ

50/60HZ

output signal

0…10V 4-20mA

0…10V 4-20mA

0…10V 4-20mA

power consumption

10W

10W

10W

Probe working environment conditions

temperature-40…+180℃

temperature-40…+180℃

temperature-40…+180℃

humidity5%-95%

humidity5%-95%

humidity5%-95%

Probe length

standard:80mm

standard:200mm

standard:250mm

Selection Table

content

Code and Description

HXWD818-

Split type high temperature(-40-180℃)

range

05

0-5M/S

10

0-10M/S

30

0-30M/S

length

100

100MM

200

200MM

250

250MM

output signal

I

4-20MA

V

0-10V

display

E

LED