Single phase power parameter tester
Main indicators
>Voltage 0-500V>Current 0.5A-50A
>Phase 0-360 degrees>frequency 45-65Hz
>Accuracy level 0.5/0.2
Main functions
1. Adopting a 65X50 LCD display screen with high backlight for intuitive and clear display;
2. Direct button operation, easy to learn and use;
3. Direct measurement of voltage (U), current (I), power (P, Q, S), power factor (PF), frequency (F), and energy (kWh) parameters for single-phase systems, three-phase three wire systems, or three-phase four wire systems can be achieved without the need to switch switches;
4. The energy accumulation function can assess the electricity consumption of electrical equipment during a certain period of time, providing a calculation basis for energy conservation and consumption reduction of electrical equipment;
5. The instrument is powered by a built-in rechargeable lithium battery, which can work continuously for 18 hours when the backlight is turned off and 8 hours when the backlight is turned on. It does not require an external power supply and has a low power indicator;
6. It can store 1000 sets of detection data, making it convenient to query and store data sets;
7. The instrument is equipped with a built-in clock chip that can accurately record the detection time for future reference;
8. Data can be uploaded to a PC and converted into a database for storage by the accompanying management software;
9. Ultra small streamlined structure, anti drop wristband design, handheld, small size, light weight.
Product Usage
1. Electrical parameter measurement (U/I/Φ/P/Q/S/PF/Hz);
2. Discrimination of load characteristics between inductive and capacitive circuits;
3. Check the power consumption of electrical equipment;
4. Used as a leakage current meter, etc.
Technical indicators
1. Voltage measurement: 30V-500V, resolution 0.001V, accuracy 0.2%
2. Current measurement: 0.2A-50A (clamp meter connected), resolution 0.0001A, accuracy 0.5%
3. Active power: 25kW, resolution: 0.0001 (expandable to 50kW or 250kW or 500kW), accuracy 0.5%
4. Reactive power: 25kVar, resolution: 0.0001 (expandable to 50kVar or 250kVar or 500kVar), accuracy 1.0%
5. Apparent power: 25kVA per phase, resolution: 0.0001 (expandable to 50kVA or 250kVA or 500kVA), accuracy 0.5%
6. Frequency measurement: 45-65Hz, resolution 0.01 Hz, accuracy 0.02Hz
7. Phase measurement: 0-360 degrees, resolution of 0.1 degrees, accuracy of 1.0 degree
8. Power factor: 0.0001 (0.0001-1.0000)
9. Electricity measurement: 0~99999kwh, accuracy 0.5%
10. Working power supply: Built in lithium battery power supply, 1700mAh/3.7V (with adapter)
11. Working environment: temperature -15-45 ℃, humidity: ≤ 95%
12. Dimensions: 185X85X41mm, Weight: 260g
Configuration Details
1. Standard configuration details:
1) 1 host
2) One 50A clamp current transformer
3) 1 set of voltage testing line
4) 1 set of data management software and data cable
5) 1 copy of user manual
6) 1 copy of factory inspection report
7) 1 copy of factory certificate of conformity
8) 1 aluminum alloy chassis
2. Optional accessories:
1) 500A current clamp
2) 1000 A current clamp
3) Backup lithium battery