Object of use:
liquid
Gas or steam
Range: 2:0-0.02MPa to 0.1MPa
3:0-0.1MPa ~ 0.5MPa
4:0-0.2MPa ~ 1MPa
5:0-1MPa ~ 5MPa
6:0-2MPa ~ 10MPa
7:0-10MPa ~ 50MPa
Output: 4-20mA DC
Working power supply: 12-36V DC
Output indication accuracy: ± 2%
Migration:
The transmitter can be used as a zero shift of 50% of the calibration range, but the upper limit of the calibration range must not exceed the upper limit range. Negative transfer is not allowed
Overvoltage:
Twice the range limit
(Except for the range of 7:0-50MPa, which is 1.5 times)
Working temperature range: -25 ℃ to+80 ℃
Storage temperature range: -40 ℃ to+120 ℃
Humidity range: 0-100% relative humidity
Start time: 2 seconds, no preheating required
Accuracy:
± 0.20% of the measuring range
Including linearity, variation, and repeatability
Temperature effect: The zero position temperature error is 0.75% of the maximum range/55 ℃
The comprehensive temperature error is 1.1% of the maximum range/55 ℃
Vibration impact:
The vibration error caused by the vibration frequency up to 200Hz in any direction is 0.25%/g of the maximum measurement range
Time response: less than 0.2 seconds
Isolation membrane: 316SST
Sensor housing: 1Cr18Ni9Ti
Filling fluid: Silicone oil
Process connection port: optional according to selection information
Electrical connection: The connection holes for the electronic box are 1/2-14NPT taper tube screw holes,