Shanghai Laiyang Electric Technology Co., Ltd
No. 8 Wenshui Road, Zhabei District, Shanghai

OneLYWHX-9900Phase detectorIntroduction
is aFully intelligent wireless high and low voltage voice phase analyzerBreaking through the voltage level limitations of traditional nuclear phase meters, nuclear phase can be detected in extremely low voltage lines, achieving10VAutomatic phase detection at voltages of up to 550kV (such as 400V, 10kV, 35kV, 66kV, 110kV, 220kV) eliminates the need to purchase multiple phase detectors or configure high and low voltage detectors separately based on voltage levels, saving costs, reducing portability, and saving time and speed. For high-voltage line phase detection (voltage exceeding 400V), the metal probe hook of the detector can be gradually brought closer to the wire. When an electric field signal is induced, phase detection can be completed without direct contact with the high-voltage wire, which is safe!When the voltage exceeds 35kV, non-contact core phase must be used.This nuclear phase analyzer also has functions such as testing phase, frequency, phase sequence, electrical verification, and transformer group determination.
fromdetector、receiver(host)TheTelescopic insulating rod、monitoring software、USB communication cableThe wireless transmission of test data can penetrate through wall obstacles, with a straight-line transmission distance of about 100 meters. Host selection: 4.3 inches65K色LCD color screen, which can display phase, frequency, phase sequence, and nuclear phase results on the same screen,Dynamic Vector Graph IndicationClear and intuitive; Having voice prompts such as "X signal normal, Y signal normal, in-phase, out of phase" will make testing simple and easy; The host is also designed with a USB interface, and the data saved during on-site testing can be imported into the computer through monitoring software for easy access and management of historical data. The insulating rod is made of alkali free glass fiber cloth as the base material, and is heated, rolled, baked, and cured with epoxy phenolic resin as the adhesive. It has the characteristics of high insulation, stretchability, moisture resistance, impact resistance, bending resistance, and lightweight.
Due to the fact that some users may not use this instrument frequently, and may only use it once every six months, if they do not forget to charge the battery for a long time, it may cause the battery to not work properly. Users may also find it inconvenient to purchase rechargeable batteries of the same specifications. Therefore,LYWHX-9900Two battery power supply methods have been designed. When the rechargeable battery is damaged, it can be replaced with a regular battery (the host uses 6 1.5V LR6 batteries); The detector uses two pieces of 6F22 9V.
Also known as“Nuclear phase analyzer, nuclear phase analyzer, wireless high-voltage nuclear phase analyzer, wireless high and low voltage voice nuclear phase analyzerHigh voltage digital voice phase detector, wireless high-voltage intelligent phase detector”Wait a minute.
IILYWHX-9900Phase detectorelectrical symbol

3、 Technical specifications
Function |
High and low voltage wireless voice core phase, phase testing, phase sequence judgment, electrical verification, frequency testing, etc |
Power supply |
Detector: 7V~9VDC(built-inLarge capacity rechargeable lithium battery, 7.4V/1000mAh, Fully charged and continuously working for 40 hours; can also be usedReplace with 1 6F22 9V battery) |
Receiver: 7V~9VDC(AA、 1.2V、 6 sectionsLarge capacity nickel hydrogen rechargeable batteryWith a total capacity of 9000mAh, it can work continuously for 40 hours when fully charged; can also be usedReplace with 6 LR6 and 1.5V batteries) | |
Nuclear phase method |
Contact type core phase: Lines below 400V can contact wire core phase |
Non contact core phase: For lines above 400V, the detector can be gradually hooked closer to the core phase of the wire without directly contacting the high-voltage wire. When the voltage exceeds 35kV, non-contact core phase must be used. | |
transmission distance |
Wireless transmission, with a straight-line transmission distance of approximately 100m |
transmission frequency |
433MHz、315MHz |
Nuclear phase voltage |
10V~550kV |
Differential qualitative analysis |
-20 ° to 20 ° in-phase; 100 ° -140 ° and 220 ° -260 ° out of phase |
Accuracy |
Self calibration error ≤± 3 °; On site in-phase error ≤ ± 7 °; On site out of phase error ≤± 12 ° |
resolution |
1° |
Length of insulation rod |
φ28mm;Shrinkage is 600mm; elongation is 3200mm |
LCD |
4.3 inches;65K color screen;Display area 98mm × 57mm |
Phase indication |
Simultaneous indication of phasor diagram and numbers, clear and intuitive |
Probe hook size |
φ5mm×D50mm |
Probe size |
φ5mm×L40mm |
Voice feature |
Voice prompts such as "in-phase, out of phase, normal X signal, normal Y signal" are available |
Electrical verification prompt |
When there is power, the detector emits a beep beep beep beep sound |
data interface |
USB mini interface |
data storage |
200 groups,pressHOLDkeyMaintain data and automatically number storage, display when storage is full“FULL”Symbol (data will not be lost during power failure or battery replacement) |
data retention |
pressHOLDkeyMaintain data,HOLDSymbol display, and thenpressHOLDCancel keymaintain |
data lookup |
pressREADkeyYou can enter data search mode and then pressarrowKey to browse data |
Backlight |
Yes, suitable for dark places |
Display speed |
3 times per second |
Shift gears |
10V~550kV fully automatic shifting core phase |
Test instructions |
Displayed during testing“During testing --” |
Auto Shutdown |
After about 15 minutes of startup, the instrument panel will automatically shut down |
battery voltage |
When the battery voltage is below 6.5V, the low battery voltage symbol is displayed, reminding that the battery needs to be charged or replaced. |
Instrument quality |
Host: 700g (including battery) Detector: 200g × 2 (including battery) Insulation rod: 430g × 2 Total weight: 6kg (including instrument box and insulation rod) |
Instrument size |
Host: Length, Width, Thickness 195mm × 137mm × 50mm Detector: length, width, and thickness 145mm × 58mm × 50mm |
Instrument box size |
Length, width, and height: 640mm × 310mm × 120mm |
USB cable length |
USB data cable length1.5m |
external interference |
No particularly strong electromagnetic field; No co frequency interference at 433MHz and 315MHz |
Working temperature and humidity |
-20℃~45℃; Below 80% Rh |
Storage temperature and humidity |
-10℃~60℃; Below 70% Rh |
Power consumption |
Detector: 20mA max; Host: 200mA max |
pressure rating |
The safety withstand voltage level of this insulation pole is ≤ 110kV. For high-voltage lines, when the voltage exceeds 35kV, non-contact core phase must be used. Direct contact with high-voltage wires is strictly prohibited, otherwise there is a risk of electric shock, causing physical injury or equipment damage. |
insulation test |
Insulated rod: AC110kV/rms (* stretched between both ends) Host and detector: AC3700V/rms (between exposed metal and shell) |
Protection level |
IP63 |
Safety regulations |
Meets the requirements of GB13398-92, GB311.1-311.6-8, 3DL408-91 standards and the newly issued national power industry standard "General Technical Conditions for 1kV-35kV Portable Nuclear Phasers Used in Live Working DL/T971-2005" |
Compliant with IEC 61481-A2:2004; IEC 61243-1 ed.2:2003 standard |
4、 Structure

5、 LCD Description

6、 Operation method

1. Power on/off
pressPOWERThe key can be used to turn on and off, and the instrument panel will automatically shut down after 15 minutes of power on.
2. Data retention
In test mode, pressHOLDKey, can maintain LCD display“HOLD”Symbol indication. press againHOLDPress the key to unlock the data and return to testing mode“HOLD”The symbol disappears.
3. Data storage
In test mode, pressHOLDWhile holding the data with the key, the instrument automatically numbers and stores the currently held data, and displays when canceling the data hold“SAVE”Symbol, indicating how many sets of data have been stored. This instrument can store 200 sets of data. If the storage is full, it will display the "full" or "FULL" symbol, and the memory must be cleared before it can be stored again.
4. Data retrieval
In test mode, hold downREADEnter the data search mode with the key“READ”Symbol indication. Simultaneously display the 001st set of stored data automatically, and then pressarrowClick to flip through. This instrument is equipped with "+1, -1,+10, -10" quick access to stored data function. Pressup and down arrowsPress the key to query by increasing or decreasing the step size by 1Left and right arrowsUse the key to increase or decrease the step size by 10 to query.
5. Data deletion
In test mode, pressCLEARPress the key to enter the data deletion dialog box, and then press againLeft and right arrowsSelect 'Yes' or' No 'with the key, then press againCLEARConfirm whether to delete and return to test mode with the key. Data cannot be restored after deletion.
6. Data upload
Connect the USB communication cable between the computer and the host, turn on the computer, run the monitoring software, and you can read the stored historical data, upload it to the computer, and manage the data.
7. Superior filtering
In order to improve the accuracy of the test, the instrument has added an upper level filtering function, which means that during the kernel phase, the filter is pressedFILTERThe key can activate or deactivate the filtering function, and the LCD dynamically displays when activated“FILTER……”This way, the results of the nuclear phase will be more accurate, but the testing time will be extended.
8. Self verification
Please perform self calibration before on-site phase verification to confirm that the instrument is functioning properly. Connect the two clips of the self calibration line to the hooks of the two detectors, and then plug the self calibration line plug into a 220V power socket. Perform self calibration on the same live wire. If there is no power, the neutral wire may have been plugged in. Simply plug the self calibration line plug back in.
9. Nuclear phase, electrical verification, frequency, and phase sequence testing

Connect the insulation rod, install the antenna, turn on the device. If the communication between the host and the detector is normal, the red status light will be on; Communication is abnormal, the white status light is on. At the same time, the host will voice prompt "X signal normal" and "Y signal normal".
When nucleating, first bring the X detector close to or in contact with any phase line, and then bring the Y detector close to or in contact with other phase lines to be nucleated. High voltage nuclear phase, the detector does not need to directly contact the high-voltage wire. The detector hook is gradually brought closer to the wire. When an electric field is sensed, the detector will emit a "beep beep beep beep" prompt sound to complete the electrical verification function. Low voltage core phase (400V and below), especially for low-voltage core phase of distribution boxes, please replace the metal probe hook with a metal probe and use the probe to directly contact the low-voltage wire. When the voltage is too low, it is necessary to contact the bare wire for testing.
The nuclear phase is based on the X detector and displays the fixed A phase. If the phase angle of the two detectors is between -20 ° and 20 ° (340 ° and 360 ° are -20 ° and 0 °), the detection result of the Y detector is A, which is classified as in-phase; If the phase angle between two detectors is between 100 ° and 140 ° or 220 ° and 260 °, it is classified as out of phase. At the same time, the host voice prompts "same phase" or "out of phase".
When the phase angle is between 100 ° and 140 °, the detection result of the Y detector is B, which is in sequential order; The phase angle is between 220 ° and 260 °, and the detection result of the Y detector is C, which is the reverse phase sequence.
10. Battery charging or replacement

When the battery voltage is insufficient, the low voltage symbol is displayed. Please charge the battery in a timely manner. If the battery is still low after multiple charges, please replace it with a brand new battery. If users are unable to purchase rechargeable batteries of the same specifications, they can purchase regular batteries instead (the host uses 6 1.5V, LR6 batteries; One 6F22 9V detector is used.
When replacing the battery, make sure the instrument panel is turned off.
Detector battery replacement: Loosen the four screws on the bottom cover of the detector, carefully open the bottom cover, and replace it with a brand new qualified battery. If you continue to use lithium batteries of the same specifications, you need to weld the corresponding wires. The detector is reserved with a 6F22 battery interface. If replacing the 6F22 battery, the original built-in lithium battery needs to be removed and replaced with a 6F22 battery.
Host battery replacement: Loosen one screw on the host battery cover, open the host battery cover, and replace it with a brand new and qualified battery. Pay attention to the polarity of the battery specifications, cover the bottom cover or battery cover, and tighten the screws. The host can use 1.5V and LR6 batteries.
After replacing the battery, pressPOWERPress the key to confirm if the battery replacement was successful. Battery replacement must strictly follow the same performance and parameters as battery replacement.
7、 Packing list
Aluminum alloy instrument box |
1 piece |
X detector |
1 piece |
Y detector |
1 piece |
Host (receiver) |
1 unit |
Telescopic insulating rod |
2 pieces |
external antenna |
3 pieces |
金属探钩 |
2 pieces |
metal probe |
2 pieces |
Self study line |
1 item |
USB communication cable |
1 item |
Monitoring software (CD) |
1 copy |
charger |
1 piece |
Rechargeable lithium battery (inside the detector) |
2 pieces |
Nickel hydrogen rechargeable battery(LR6、 1.2V, hostinside) |
6 pieces |
Instruction manual (including warranty card/certificate of conformity) |
1 book |
Attachment:
*Warranty Registration Card*
Dear user:
First of all, thank you sincerely for purchasing our products. We hope that our products and services can bring you respect and hospitality. Meanwhile, please also pay attention to the following requirements:
1、 Warranty period: One year (calculated from the date of the user's purchase invoice).
2、 Warranty procedures:
1. If users require service, they should present their local warranty card and purchase invoice.
When repairing the instrument, please place it in its original packaging and pack it properly before returning it to our company.
3. For products within the warranty scope, our company provides free repairs and does not charge any component cost fees.
4. Any shipping costs shall be borne by the user themselves.
3: Non warranty scope:
1. Does not comply with warranty procedures.
2. The instrument can be disassembled or assembled by oneself, or repaired by a unit without our company.
3. The battery leaks and corrodes the circuit board.
4. The instrument is damaged due to severe drops, impacts, or other abnormal damages.
5. Failure to install, operate, and maintain according to the instructions in the original factory manual.
4、 For instruments not covered by warranty, our company adheres to the principle of serving customers and only charges reasonable material cost fees.
5、 The free warranty does not include the repair or replacement of accessories such as fuses, batteries, chargers, insulation rods, etc.
6、 Our company will not be responsible for any other losses caused by use.
7、 Maintenance records:
Time |
Problem description (filled in by the user) |
Processing result (filled in by our company) |
Year Month Day |
|
|
Year Month Day |
|
|
Year Month Day |
|
|
Year Month Day |
|
|
Year Month Day |
|
|
Year Month Day |
|
|
*Certificate of Conformity*
Product Name |
|
Manufacturing Date |
|
Product model |
|
Purchase date |
|
Product Number |
|
inspector |
|
distributor |
|
||