电能表现场校验仪

Main functions

Verify the error, accuracy, creep, and start-up of the electricity meter on site without disassembling the meter or disconnecting the power supply; Measure the voltage, current, active power, reactive power, power factor, etc. of the power supply grid. This product is an ideal instrument for measuring electricity and verifying energy meters. It is an essential tool for detecting electricity theft, measuring meters, and resolving electricity disputes. The on-site verification instrument for three-phase electric energy meters can also determine whether there are wiring errors.

Main Features

1. Verify the accuracy of the electric meter on site without dismantling it, suitable for verifying various types of energy meters such as mechanical, electronic, IC card, etc.
2. On site measurement of voltage, current, active power, reactive power, and power factor.
3. Adopting a large screen LCD display, it can simultaneously display various electrical parameters and meter errors at a glance.
4. There are two measurement methods available: automatic sampling and manual sampling using a photoelectric sensor.

Technical specifications of single-phase energy meter calibrator

1. Verify the accuracy level of the electricity meter: 0.2 level
2. Voltage testing range: 176-300V, accuracy: level 0.5.
3. Current testing range: 0-120A (no need to replace clamp transformers), accuracy: 0.5 level
4. Active power testing range: 0-36000W, accuracy: Level 0.5
5. Reactive power test range: 0-3600Var, accuracy: Level 1.0
6. Power factor testing range: 0.1-1.0, accuracy: Level 1.0
7. Impact of temperature changes:<0.005%/℃ within the range of -10 ℃ to 40 ℃
8. Power consumption: 2.5VA
9. Volume: 200mm × 90mm × 25mm
10. Weight: 0.8Kg

Technical specifications of three-phase energy meter calibrator

accuracy Basic error Measurement range
Voltage (R.M.S) ± 0.1 level ±0.05% 1-450V
Current (R.M.S) ± 0.1 level ±0.05% 0-600A
phase angle ± 0.1 level ±0.005% 0-360°
frequency ± 0.1 level ±0.005% 45-55HZ
active power ± 0.1 level ±0.05%
active energy ± 0.1 level ±0.1%
reactive power ± 0.2 level ±0.1%
Reactive energy ± 0.2 level ±0.2%