Suitable for pressure difference measurement in explosion-proof and non explosion-proof areas, high and low limit alarms can be achieved by comparing the measured pressure difference with the set value. The output signal is a passive dry contact signal (SPDT). It is commonly used for: 1. Filter anti blocking control; 2. Differential pressure balance control between two containers; The pressure switch directly outputs the dry node signal, which can achieve the function of pressure transmitter+PLC/control instrument output switch control. The structure is simple, highlighting its advantages in on-site control in small-scale control. This product has the following features: ● Fully welded diaphragm, zero leakage ● Mechanical principle, no need for power supply ● High quality micro switch, small dead zone ● Diverse process interfaces, flange threads can be customized
Product Details
product overviewProduct overview
The LPS-C1 series differential pressure switch adopts a diaphragm type differential pressure sensing element. The ordinary type can be used to control the pressure difference between the same pressure source or different pressure sources of gas, liquid or steam media that have no corrosive effect on the sensing element. Explosion proof type can be used to control the pressure difference between the same pressure source or different pressure sources in explosive gas mixtures of Class IIA/IIB/IIC gases T1~T6 that have no corrosive effect on pressure sensing components. The fully welded stainless steel diaphragm structure is designed to be simple and easy to use, with few fault points, and can effectively prevent liquid leakage and misoperation; The set value is adjustable, no separate power supply is required, and the contact capacity is large, which greatly facilitates on-site application for users. It is widely used in various industries such as petroleum, chemical, metallurgy, power, sugar, and pharmaceuticals that require differential pressure control.
measuring principleprinciple
Diaphragm pressure switch is a mechanical pressure switch that uses the mechanical deformation of the diaphragm to achieve the function of controlling contact closure and disconnection. When the pressure of the measuring medium changes, the diaphragm will produce corresponding displacement. The displacement of the diaphragm is transmitted to the micro switch through the transmission component. When the displacement stroke reaches the set value, the micro switch will be pushed, causing the contacts of the micro switch to close or open as a state variable. Adjustable pressure switches can control pressure within a fixed value or range by adjusting the stroke relationship between transmission components and micro switch contacts, in order to achieve control objectives.
performance indexTECHNICAL PARAMETERS
Measurement medium: gas or liquid (in highly corrosive environments, communication is required) Measurement range: 0-2.0~2500kpa Working viscosity: ≤ 10E3 m2/S Shell material: die cast aluminum, epoxy resin coating, outer cover with sealing gasket NEMA protection level: meets NEMA 4X requirements Set value accuracy: ± 0.5% Repeatability accuracy:<1% Pressure interface: standard 1/2NPTF internal thread, M20 * 1.5 external thread; Special interfaces can be customized Electrical interface: M20 * 1.5 internal thread; Special interfaces can be customized Switch output: a single pole double throw (normally open+normally closed) output; Switching element: Micro switch Environmental temperature: -40 ℃ to+70 ℃ Environmental humidity: 5% to 95% Cycle life: 1 million cycles Protection level: IP67 Explosion proof rating: Exde IIC T6 Gb Dust explosion-proof: ExtD A21 IP66 T80 ℃; Contact capacity: Conventional type: 380V, 15A; Explosion proof type: 380VAC, 5A;