Cat brand cable Tianjin Cable Factory Rubber Cable Factory
Langfang Dacheng, Hebei
Kyjvp2-22-7 * 1.5 cable kyjvp2-22-7 * 2.5 control cable
Product Features and Applications
This product is suitable for automatic control or monitoring systems, electrical instrument connections, and other field use transmission lines with AC rated voltage of 450/750V and below.
Low smoke halogen-free polyolefin has a low smoke emission during combustion and no release of halogen acid gas. It belongs to environmentally friendly cables and is suitable for occasions with special requirements for fire protection.
Product execution standards
GB9330-88
Flame retardant performance test shall comply with GB12666-90 standard
Kyjvp2-22-7 * 1.5 cable kyjvp2-22-7 * 2.5 control cableUse characteristics
Rated AC voltage: U0/U 450/750KV
Maximum working temperature: PVC (polyethylene) insulation not exceeding 70 ℃
Cross linked polyethylene insulation at 90 ℃
Low smoke halogen-free flame-retardant polyolefin at 70 ℃
Low smoke halogen-free flame-retardant cross-linked polyolefin at 90 ℃ and 125 ℃
Zui low ambient temperature: PVC sheath: fixed installation -40 ℃, non fixed installation -15 ℃
The temperature for cable installation and laying should not be lower than 0 ℃.
Allowable bending radius for cables: The minimum allowable bending radius for non armored cables is 6 times the outer diameter of the cable
Copper tape shielded or steel tape armored cables with a minimum diameter of 12 times the outer diameter of the cable
Basic model and name
1. PVC insulated and sheathed control cables
KVV |
Copper core PVC insulated PVC sheathed control cable |
KVVP |
Copper core PVC insulated PVC sheathed copper wire braided shielded control cable |
KVVP2 |
Copper core PVC insulated PVC sheathed copper tape shielded control cable |
KVV22 |
Copper core PVC insulated PVC sheathed steel tape armored control cable |
KVVR |
Copper core PVC insulated PVC sheathed control flexible cable |
KVVRP |
Copper core PVC insulated PVC sheathed copper wire braided shielding control flexible cable |
KVVP2-22 |
Copper core PVC insulated PVC sheathed copper tape shielded steel tape armored control cable |
KVVRP22 |
Copper core PVC insulation, copper braided shielding, PVC sheath, steel tape armor controlsoftcable |
2. Cross linked polyethylene insulated polyvinyl chloride sheathed control cable
KYJV |
Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed control cable |
KYJVR |
Copper core cross-linked polyethylene insulated PVC sheathed control flexible cable |
KYJVP |
Copper core cross-linked polyethylene insulated copper wire braided shielding polyvinyl chloride sheathed control cable |
KYJVRP |
Copper core cross-linked polyethylene insulated copper wire braided shielding polyvinyl chloride sheathed control flexible cable |
KYJVP2 |
Copper core cross-linked polyethylene insulated copper tape shielded polyvinyl chloride sheathed control cable |
KYJVRP2 |
Copper core cross-linked polyethylene insulated copper tape shielded polyvinyl chloride sheathed control flexible cable |
KYJV22 |
Copper core cross-linked polyethylene insulated PVC sheathed steel tape armored control cable |
KYJVP22 |
Copper core cross-linked polyethylene insulated copper braided shielding polyvinyl chloride sheathed steel tape armored control cable |
KYJVP2-22 |
Copper core cross-linked polyethylene insulated copper tape shielded polyvinyl chloride sheathed steel tape armored control cable |
3. Low smoke halogen-free flame-retardant polyolefin insulated and sheathed control cables
KYDYD |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed control cable |
KYDYDR |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed control flexible cable |
KYDYDP |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shielded control cable |
KYDYDRP |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shielding control flexible cable |
KYDYDP2 |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded control cable |
KYDYDRP2 |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded control flexible cable |
KYDYD-22 |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed steel tape armored control cable |
KYDYDP22 |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shielding steel tape armored control cable |
KYDYDP2-22 |
Copper core low smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded steel tape armored control cable |
Note: In the basic model, there are insulation, sheath, and YDJ low smoke halogen-free flame-retardant cross-linked polyolefin | |
Note: ZR should be added before the flame-retardant sheath model, and tin plating can be used for the copper wire in the conductor core.
5: Code name and meaning
Table 2
project |
code name |
explanation |
Flame retardant properties |
ZR |
Classified as Class A, B, and C flame retardant |
Series code |
K |
control cable |
insulating material |
V |
Polyvinyl chloride, flame-retardant polyvinyl chloride |
Y |
polyethylene |
|
YD |
Low smoke halogen-free polyolefin (YDJ low smoke halogen-free cross-linked polyolefin) |
|
YJ |
cross-linked polyethylene |
|
Jacket material |
V |
Polyvinyl chloride, flame-retardant polyvinyl chloride |
YD |
Low smoke halogen-free polyolefin |
|
Shielding material |
P |
Copper wire braided shielding |
P1 |
Tin plated copper wire shielding |
|
P2 |
Copper tape wrapped shielding |
|
P3 |
Aluminum plastic wrapped shielding |
|
Armor material |
22 |
Steel belt armored PVC sheath |
23 |
Steel belt armored polyethylene sheath |
|
32 |
Steel wire armored PVC sheath |
|
33 |
Steel wire armored polyethylene sheath |
|
Conductor structure |
A |
Single stranded conductor |
B |
7-stranded conductor |
|
R |
Multi stranded conductor |
Six:Main technical indicators
1. The DC resistance of the finished cable conductor (Ω/km. 20 ℃) shall refer to Table 3 in Appendix A.
2. The insulation resistance and nominal insulation thickness shall comply with the provisions in the following table:
Nominal cross-section (mm)2) |
Insulation nominal thickness (mm) |
Insulation resistance (M Ω/KM) |
|
20℃ |
70℃ |
||
0.5 |
0.6 |
13 |
0.013 |
0.75 |
0.6 |
12 |
0.12 |
1.0 |
0.6 |
11 |
0.011 |
1.5 |
0.7 |
11 |
0.011 |
2.5 |
0.8 |
10 |
0.010 |
4 |
0.8 |
8.5 |
0.0085 |
6 |
0.8 |
7 |
0.0070 |
10 |
1.0 |
6.5 |
0.0065 |
3. The finished cable shall withstand AC 50HZ3.0KV/5min voltage test without breakdown.