Kt171/170 phase sequence table

NegotiableUpdate on 03/25
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
KT171/170 Phase Sequence Table | Common 171/170 Phase Sequence Table Technical Parameters:
Product Details

Kt171/170 phase sequence table|KyoritsuCharacteristics of 171/170 phase sequence table:

1. Innovative design: Large bright backlight for easy use in dark places; Ergonomic design
2. Two major functions: measurement without battery; Self testing function
3. Automatic shutdown function
4. Capable of measuring in low-temperature environments
5. Beep warning
6. Pen light function suitable for dark places
7. Design in accordance with international safety standards IEC61010 and IEC61243

KT171/170 Phase Sequence Table | Common 171/170 Phase Sequence Table Technical Parameters:

This parameter table is provided byKyoritsuFlukeTESTODeltaTRAKcemDistrict General AgentProvided by Shenzhen Haixu Instruments and Meters

voltage
voltage range
12~690V AC/DC
test
rated voltage
12/24/50/120/230/400/690V AC(16~400Hz). DC(±)
 
Allowable value
Illuminates when the following values are exceeded:
(Boundary voltage)
7±3V(12V LED) 18±3V (24V LED)
 
37.5±4V (50V LED)75% of rated voltage±5%(120/230/400/600V LED)
response time
<0.6 seconds at 100% of each rated voltage
lcd(kt171)
 
 
 
Range/Resolution (Automatic Range)
300v ac/dc(6.0-299.9)/0.1v 690v ac(270-759)/1v 690v dc(270-710)/1v
accuracy
±1.5v(7-100v) ±1%±5dgt(100-690v) ac(16-400Hz)
Out of range prompt
“ol”
response time
<2 seconds at 90% of each rated voltage
peak current
Is<3.5mA (690VWhen)
BATTERY LIFE
About 2500 operations (30 seconds ON/240 seconds OFF)
Monopolar phase test
voltage range
100-690v ac(50/60Hz)
Phase sequence test
system
Three phase four wire system 200-690V phase to phase AC (50/60Hz)
phase measurement
120±5 °
continuity test
detection range
0~400kΩ+50%
Test Current
About 1.5µA(Battery 3V, 0Ω)
Operating temperature and humidity range
-15-55℃, maximum 85% RH (no condensation)
Storage temperature range
-2~60ºCMaximum 85% RH (no condensation)
Safety specifications
IEC61010-1 IEC61010-031 IEC61557-7 IEC61243-3 CAT.III 690V/CAT.IV 600VPollution level 2 IP65 (IEC60529)
Using batteries
Battery LR03 (1.5v) x2
External dimensions
246(L)X64(W)X26(D)mm
weight
195g(Including battery)