- Phone
-
Address
Chanxi Industrial Zone, Liushi Town, Leqing City, Wenzhou, Zhejiang Province
Wenzhou Zhongxuan Instrument Co., Ltd
Chanxi Industrial Zone, Liushi Town, Leqing City, Wenzhou, Zhejiang Province
KFP-1100 signal isolatorThe input is a single channel dual channel linear current or voltage signal, a nonlinear thermal resistance or thermocouple signal, or a frequency signal transmission output isolated single, dual, or triple channel current or voltage signal, providing good electrical isolation between the input, output, and power supply.
KFP-1100 signal isolatorModulation and conversion of signals from transmitters or together through semiconductor devices, followed by isolation and conversion through optical or magnetic sensing devices, and then demodulation and conversion back to the isolated signal. At the same time, isolation processing is performed on the power supply of the isolated signal to ensure independence between the converted signal, power supply, and ground. It is a process of converting input single or dual current or voltage signals into isolated output single or dual linear current or voltage signals, and improving the electrical isolation performance between input, output, and power supply.
KFP-1100 signal isolatorMain performance parameters and technical indicators:
Basic error (accuracy): ± 0.20%.
Output AC component: ≤ 40mV.
Power supply: 24Vd. c. ± 10%, ripple content less than 1%.
Power consumption: The power consumption of a one in two out signal isolator is ≤ 2.5W.
Weight: The meter body of the one in two out type weighs approximately 200g
Isolation characteristics: The input, output, and power supply of the instrument are isolated from each other.
Insulation resistance: ≥ 20M Ω (between the power supply, input, and output terminals).
Insulation strength: 500Va. c./1min (between the power supply, input, and output terminals).
Maintainability: In the installation and distribution state, the body can be replaced with electricity.
KFP-1100 signal isolator