Features of KEW 4118A Loop Resistance Tester:
1KEW 4118A Loop Resistance TesterEquipped with microprocessor control circuit, high accuracy and reliability.
2. There are three neon indicator lights that can be used to check the status of the circuit.
3. Can directly read the expected short-circuit current (PSC) (4118A).
4. It has the function of measuring safe voltage.
5. Large digital LCD display.
6. Measurable low loop current (resolution 0.01 Ω).
7. If the test resistor overheats, it will automatically lock and cut off the power supply.
8. Indicate whether the phase is reversed and the condition of the neutral wire in the socket.
Technical specifications of KEW 4118A circuit resistance tester:
This parameter table is provided byKyoritsu FlukeDeltaTRAKDistrict General Agent—Shenzhen Haixu Instrument and Meter Co., Ltd. provides original and authentic products
|
|
MODEL 4116A
|
MODEL 4118A
|
|
|
Loop resistance measurement range
|
20/200/2000Ω
|
20/200/2000Ω
|
|
|
Loop resistance accuracy
|
±2%rdg±4dgt
|
±2%rdg±4dgt
|
|
|
ACTest Current
|
20Ω25A
200Ω2.3A 2000Ω15mA |
20Ω25A
200Ω2.3A 2000Ω15mA |
|
|
ACTest Cycle
|
20Ω(20ms)
200Ω(40ms) 2000Ω(280ms) |
20Ω(20ms)
200Ω(40ms) 2000Ω(280ms) |
|
|
PSCrange
|
---
|
200A(2.3A 40ms)
2000A(25A 20ms) 20kA(25A 20ms) |
|
|
working voltage
|
110V~260V ±2%rdg±4dgt
|
||
|
Safety specifications
|
IEC61010-1CAT.III 300V IEC61557-1/3
IEC61010-2-031Pollution level 2 |
||
|
External dimensions
|
185(L)×167(W)×89(D)mm
|
||
|
weight
|
About 750g
|
||
|
attachment
|
7123(Test line) operation instructions
|
7121(Test line) operation instructions
|
|
|
option
|
7121(Test line)
|
---
|
|
Related instruments: DT-904 leakage switch tester