Welcome Customer !

Membership

Help

Changsha Lanhong Electric Technology Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Changsha Lanhong Electric Technology Co., Ltd

  • E-mail

    lhdqsw@126.com

  • Phone

  • Address

    Building 7, International Enterprise Center, No. 188 Environmental Protection Middle Road, Yuhua District, Changsha City, Hunan Province

Contact Now

Integrated online monitoring system for partial discharge of transformers (reactors)

NegotiableUpdate on 12/10
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Product Introduction: The online monitoring system for partial discharge of transformers (reactors) integrates vibration sensors, HFCT (high-frequency partial discharge sensors), AE (ultrasonic sensors), UHF (ultra-high frequency partial discharge sensors), and RF partial discharge sensors

Product Details

Product Introduction

The online monitoring system for partial discharge of transformers (reactors) integrates vibration sensors, HFCT (high-frequency partial discharge sensors), AE (ultrasonic sensors), UHF (ultra-high frequency partial discharge sensors), and RF partial discharge sensors. This system can provide user guidance and analysis conclusions by comprehensively analyzing various dynamic and static data, using fault assessment models and experience databases. The comprehensive monitoring system for transformers (reactors) can provide interfaces for data exchange with devices such as iron core and clamp grounding current monitoring system, winding fiber optic temperature measurement system, and transformer neutral point grounding monitoring.

Features

◎ It has the function of automatically, continuously or periodically collecting status monitoring information of ultrasonic partial discharge, high-frequency partial discharge and other equipment, and transmitting standardized data analysis results and warning information to the comprehensive monitoring background, and receiving and transmitting control commands;
◎ Equipped with timing functions for each sensing unit;
◎ It has real-time display function of characteristic parameters such as partial discharge amplitude and partial discharge frequency per unit time, supports single parameter trend analysis, threshold and trend alarm, historical data query, report generation and other functions, and supports remote control functions such as threshold setting, data summoning, parameter setting, etc;
◎ It has configurable characteristic parameters such as partial discharge amplitude, number of partial discharges per unit time, and multi parameter synchronous real-time display function. It supports multi parameter trend analysis, evaluation and diagnosis, and can achieve customized warning function;
◎ It has the function of automatically shortening the sampling period and data upload period for other monitoring parameters after a single monitoring parameter alarm;
◎ It has a system self-test function and should have an active alarm function when the device malfunctions abnormally.

Technical parameters of partial discharge monitoring host

System functions

technical indicators

Collecting host

i7,3.4GHz,8MCache,14nm,65Wpower consumption

High frequency and RF channel acquisition

support5Channel synchronization,100MS/sSampling rate; resolution14bit; Input range: ±2V;DCCoupling,

50Ω input impedance

Ultrasonic channel acquisition

support12Channel synchronous acquisition,50kS/s,16-Bit

Vibration channel acquisition

support6Channel vibration signal acquisition,100kS/s MaxSampling rate; resolution12 bit±10V

sensor

number of channels

Ultrasonic sensor

12

vibration sensor

6

Ultra high frequency partial discharge sensor

3

High frequency partial discharge sensor

4

runtime environment

technical indicators

network connection

electricity4GWireless Private Network

Protection level

IP55

system power supply

AC220V/50Hz

power consumption

300W(Air conditioning off),900W(Air conditioning on)

Operating Temperature

-15℃~+55℃

Operating Humidity

5%~95%RH

Cabinet material

Box cold-rolled sheet spray treatment/mounting plate2.5mmgalvanized sheet

cabinet dimensions

600*600*1200mm

Technical specifications of partial discharge sensing unit

image

model

Main technical parameters

UHF sensing unit

LHJFTGP

◎Amplitude frequency characteristics: The bandwidth covers 200MHz~1.5GHz, and the average effective height within this frequency band should be ≥ 11mm, with a minimum effective height of ≥ 3mm;

◎Detection sensitivity: ≤ 7V/m (17dBV/m);

◎Dynamic range of obstruction: 40dB;

◎Time deviation of different detection channels: ≤ 2us;

◎Input impedance: 50Ω ;

◎NType wood interface output.

HFCT sensing unit

LHJFGP

◎3MHz~30MHz average transmission impedance: 10mV/mA;

◎3MHz~30MHz frequency range sensor bandwidth: 10MHz;

◎Minimum measurable local discharge capacity: 50pC;

◎When the dynamic range of partial discharge signal is 40dB, the detection linearity error is ± 15%;

◎The detection frequency can be adjusted within the frequency range of 3MHz to 30MHz, and the ability to suppress narrowband interference signals is:

20dB ;

◎Sampling rate: 100MS/s;

◎Time deviation of different detection channels: 2us.

◎MRLS-150/54 aperture: 54mm;

◎Frequency: up to 150MHz;

◎Installation method: Open type.

AE sensing unit

LHJFCSB

◎Resonant frequency: 140 ± 20% RH;

◎Peak sensitivity of sensor: 60dB (V/(m/s)), mean sensitivity: 40dB (V/(m/s));

◎Detection sensitivity: 40dB;

◎Sensor detection frequency range: 80~200kHz;

◎Dynamic range: 40dB;

◎Linear error degree: ± 20%;

◎Amplitude deviation of different detection channels: ± 10%, time deviation: ± 5Ms;

◎After one hour of continuous operation of the sensing unit, the relative standard deviation of six measurement results should be ≤ ± 5%;

◎Input impedance: 50 Ω.

RF sensing unit

LHJFSP

◎Detection frequency band range: 100MHz to 1000MHz;

◎Average effective height: ≥ 10mm;

◎Sampling rate: 100MS/s.

Vibration sensing unit

Lhjfzd

◎Measurement range (peak to peak): 0.1Mm~400MmError ≤ 10%;

◎Vibration acceleration measurement range: -10g to+10g, error ≤ 10%;

◎Frequency response: 5Hz~3000Hz, the relative error of frequency response should be ± 5%;

◎Sensor sensitivity: 100mV/g.

No corresponding parameter group found, please add it in the backend property template
Not yet implemented, please stay tuned
Not yet implemented, please stay tuned