ISEM2-WRUHS Schneider Intelligent Communication Motor Protector
EOCR-ISEM2-WRUHSIt is an intelligent motor protector under Schneider, which has comprehensive motor protection functions and is widely used in the field of industrial automation.
overcurrent protection
IN (rated current)Set the rated operating current (unit: A) on the motor nameplate to simulate the motor's heating characteristics for thermal protection.
TCC (Overload Inverse Time Curve)Supports timed and inverse timed modes, suitable for motors with different starting characteristics.
OT (overcurrent action delay)Suggest setting it as3-5 secondsTo prevent short-term overcurrent misoperation.
locked-rotor protection
CS (blockage during startup): Set as3-8 times INUsed to detect mechanical jamming during the startup phase.
Ja/Jt (locked rotor during operation)Set the blocking current threshold and delay time to avoid burning out the motor during operation.
Three phase imbalance and phase loss protection
Cu (current imbalance rate): Can be set15%–50%Deviation exceeding triggers an alarm or trip.
PL (Phase Loss Protection)By default, it is enabled to prevent damage to the motor during single-phase operation.
Short circuit and grounding protection
SHD (short circuit action delay)Unit is in milliseconds, achieving fast tripping.
EC (Ground Fault Current)A leakage threshold can be set to detect insulation degradation or leakage faults.
Accessibility
DT (Start Delay)Suggest setting it as the actual measured starting time of the motor+1-2 secondsAvoid starting peak current.
RS (4-20mA analog output)Support remote transmission of current, load, and other data to DCS or PLC systems.
communication function: SupportModbus RTU / RS-485Protocol for remote monitoring and parameter modification.
Installation and power supply
Installation method:rail mountingSave control cabinet space.
Power Supply Voltage: SupportsAC/DC 100–240VStrong adaptability.
All parameter settings and wiring should be done inUnder power-off stateOperated by professional electrical personnel.
After setting up, it is recommended to use a clamp meter to measure the current and verify the sampling accuracy.
To restore factory settings, long press and hold simultaneouslyESC + SETExecute in 5 secondsrFoperation
ISEM2-WRUHS Schneider Intelligent Communication Motor Protector
CT ratio setting (SEC/PAS)
When the main circuit current is less than 0.5A, the cable should be wound around CT 2 or 5 times, corresponding to the settingPAS = 2tOr5tWhen connected to an external CT,SECSet as the secondary side transformation ratio (e.g. 200:5).
Voltage parameter setting (Va/Vb/Vc)
Support direct connection to three-phase voltage systems with a voltage of ≤ 690V (such as 380V, 480V); Exceeding 690V requires voltage reduction through a voltage transformer (PT) before connection.
Grounding protection mode (ET)
Set asINUse the built-in zero sequence transformer.
Set asCTUsing an external zero sequence current transformer, suitable for leakage protection in high current systems.
Communication and Analog Output
SupportModbus RTU protocolUpload operational data through RS-485 interface.
RSThe output can be set as LC (linearly corresponding load current) for remote transmission to DCS or PLC systems.