According to China's power regulations, when the capacitance current of 10kV and 35kV systems is greater than 30A and 10A respectively, arc suppression coils should be installed to compensate for the capacitance current. This requires measuring the capacitance current of the distribution network to determine whether to install arc suppression coils.
In addition, the coordination between the ground capacitance of the distribution network and the parameters of PT can generate PT ferromagnetic resonance overvoltage. In order to verify whether PT resonance will occur in the distribution system and what kind of resonance will occur, it is also necessary to accurately measure the ground capacitance value of the distribution network.
The methods for measuring the capacitance current of the distribution network include direct method with single-phase metal grounding, indirect measurement method with external capacitance, and signal addition method with PT open triangle. However, the most popular and frequently used method on site is still the neutral point capacitance method.
The HTCI-V fully automatic capacitance current tester uses the neutral point capacitance method to measure the distribution network capacitance current. The tester adopts a large screen LCD display and a Chinese menu. After taking safety measures and setting the instrument parameters in advance, there is no need to touch and operate the instrument, making this work safe, simple, and fast. The test results are accurate, stable, and reliable, and are not affected by other operating conditions, especially when the system is unbalanced.
Product nickname: Fully automatic capacitor current tester, microcomputer type capacitor current tester, distribution network capacitor current measuring instrument, distribution network capacitor current tester, distribution network capacitor current testing system, fully automatic capacitor current tester, distribution network microcomputer type capacitor current tester, capacitor leakage current tester
| measuring range | Total capacitance to ground ≤ 120 μ F (three-phase to ground) |
| Capacitor current ≤ 1000A (66kV system) | |
| Capacitor current ≤ 700A (35kV system) | |
| Capacitor current ≤ 200A (10kV system) | |
| Capacitor current ≤ 100A (6kV system) | |
| Accuracy of capacitance measurement | 0.5 μ F to 1 μ F ± 10% ± 5 words |
| 1μF~90μF ±5% | |
| 90μF~120μF ±10% | |
| Capacitor current<10A ± 10% | |
| Capacitor current 10A-500A ± 5% | |
| Capacitor current 500A-1000A ± 10% | |
| ambient temperature | -10~50℃ |
| relative humidity | ≤90% |
| Working power supply | AC220V±10% ,50Hz ±1% |
| External dimensions | 310×300×170mm3 |
| Instrument weight | 10kg |
1. The appearance of the product is subject to the actual product. Technical parameters and models are subject to change without prior notice. If there is any act of theft or copying, legal responsibility will be pursued.
2. To learn more about Huatian products, please enter the product center. Service Hotline: 400-8855-448
Instrument host
Voltage output line
power line
ground wire
fuse
printing paper
Instruction manual, inspection certificate, certificate of conformity
complete set
host
front
display
printer
reset key
Our company's products are strictly produced in accordance with international and national standards and industry regulations. They have passed the testing of national, provincial, and municipal power research institutes, measurement centers, and authoritative power departments, and have fully passed the ISO9001 international quality management system certification, the People's Republic of China manufacturing measuring instrument license, GB/T19001-2016 quality management system requirements, GB/T24001-2016 environmental management system requirements, and GB/T45001-2020 occupational health and safety management system requirements.