E-mail
whkairui@163.com
- Phone
-
Address
No. 10-14 Futian Road, Torch High tech Industrial Development Zone, Weihai City, Shandong Province
Weihai Kerry Electric Co., Ltd
whkairui@163.com
No. 10-14 Futian Road, Torch High tech Industrial Development Zone, Weihai City, Shandong Province
Introduction to System Functions
The ABCLINK comprehensive electrical monitoring system supports environmental monitoring functions such as wind turbine linkage monitoring, transformer temperature detection, cable trench water level detection and water pump linkage monitoring, reactive power compensation data detection, electrical energy monitoring, harmonic monitoring, active and reactive power, cloud control, timed control, one click scene control, access control, video and smoke sensing temperature and humidity monitoring; Realize power monitoring functions such as effective status of vacuum circuit breakers, dual power conversion status, vital signs of surge protectors (backup protection status, thermal trip status, cumulative times, leakage microcurrents), UPS backup power supply, etc; Implement security monitoring functions such as access control, illegal intrusion, and patrol; Support on-site sound and light alarm, SMS Chinese alarm, remote wired and wireless communication functions;
The ABCLINK comprehensive electrical monitoring system includes a power module, an intelligent gateway module, a multifunctional electricity meter module, a fire power monitoring module, an electrical fire monitoring module, an intelligent lighting module, and an input/output module;
Product Overview
HRT3000-C combined electrical fire monitoring detector is a new type of non independent fire prevention equipment. When an electrical leakage accident occurs in the power supply equipment, the detection controller can emit an alarm sound through the matching host to timely remind the staff to check the fault, eliminate possible electrical hazards, and prevent accidents from happening;
HRT3000-C combined electrical fire monitoring detector is suitable for electrical safety and fire protection in residential buildings, offices, shopping malls, public cultural and entertainment venues, restaurants, hostels, collective dormitories, schools, cultural relics protection units, factories, workshops, ordinary warehouses and other areas. But not suitable for flammable, explosive, and highly corrosive environments.
The HRT3000-C combined electrical fire monitoring detector complies with the national standards GB14287.2-2014 "Residual Current Electrical Fire Monitoring Detector" and GB14287.3-2014 "Temperature Measuring Electrical Fire Monitoring Detector".
Product Features
uReal time monitoring: single channel leakage, single channel temperature; Can monitor three-phase overcurrent and three-phase temperature; Meet the Shandong landmark DB37/T2122-2012
uEquipped with segmented LCD display screen;
uAlarm function: leakage current, cable temperature alarm function;
uCommunication function: form an alarm system with the host through two buses;
uInstallation method: rail type or panel type (accessories required);
uEasy installation and maintenance.
Overall dimensions
Equipment parameters
| Product Model | HRT3000-C | |
| Equipment parameters | input voltage | DC24V |
| communication method | Communicate with the host's second bus | |
| Bus medium |
NH-RVS-2 × 1.5 twisted pair cable |
|
| communication range | ≤ 3 kilometers (extendable) | |
| alarm method | light alarm | |
| Device dimensions |
104mm × 85mm × 50mm hole size 110mm × 85mm |
|
| Installation method | Rail or panel type | |
| Usage environment | Work: -10~50 ℃ Storage: 25-70 ℃ |
|
| relative humidity | ≤90%RH, Non condensing, non corrosive gas environment | |
| altitude | ≤2000m | |