E-mail
whkairui@163.com
- Phone
-
Address
No. 10-14 Futian Road, Torch High tech Industrial Development Zone, Weihai City, Shandong Province
Weihai Kerry Electric Co., Ltd
whkairui@163.com
No. 10-14 Futian Road, Torch High tech Industrial Development Zone, Weihai City, Shandong Province
Product Description: How to Translate
The power quality monitoring instrument adopts a brand new dual core architecture, with 32-bit floating-point ARM and DSP as the core, to build a new generation of high-end smart meter monitoring platform system. Large screen high-resolution TFT color display, resistive screen, 4G storage capacity, instrument sampling of 512 points per cycle, synchronous sampling rate of up to 25.6kHz, real-time measurement and analysis of voltage, current transient and transient changes, various rich records. By analyzing and comparing the characteristic values of various records, it can help customers sensitively identify and accurately judge potential, instantaneous, or persistent local faults.
Implement relevant standards such as GB/T 17215.321-2008, GB/T 18460-2001, DL/T614-2007, GB/T 19862-2016 General Requirements for Power Quality Monitoring Equipment, etc; Supports RS485 interface and RJ45 network interface, supports Modbus RTU protocol
Product performance:
uMeasurable positive sequence, negative sequence, and zero sequence amplitudes of voltage and current
uActivate fault recording, real-time recording and other functions; Can choose to associate alarms; Record the start and end times of voltage transients, as well as the maximum value of voltage transients, and record the start and end times of voltage transients, as well as the minimum value of voltage transients.
uEquipped with instant transient capture function, capturing transient voltages greater than 200 μ s, initiating fault recording, real-time recording, etc; You can choose to associate DO alarms; Record the time of occurrence and the voltage value at that time,
uThe LCD panel uses a 5.6-inch, 640x480 pixel, Chinese/English color screen display, which displays measurement values, real-time waveforms, harmonic bar graphs, vector graphs, I/O status, playback of recorded waveforms, reproduction of various records, etc
uStandard configuration includes 2 RS485 ports and 1 RJ45 port, RS485 port: 1200-38400bps, Modbus RTU protocol, RJ45 port: Modbus TCP
uSupport parameters such as voltage, current, frequency, power, etc., with alarms for upper, lower, and upper/lower limits
uElectric energy includes total active energy, total reactive energy, total apparent energy, forward and reverse active energy, and combined reactive energy; Total fundamental active energy and total harmonic active energy
Product Parameters:
| Technical Specifications | indicator | |
| Power supply operation | rated voltage | 85~260VAC/DC |
| power consumption | <9W | |
| Voltage input | measurement range | 40-400V (phase voltage), 60-700V (line voltage) (45-65Hz) |
| Extreme voltage | 5~750V(45~65Hz) | |
| power consumption | <0.1VA/phase | |
| Current input | rated current | 5A(45~65Hz) |
| overload capacity | 2 times the rated current, continuous operation; 10 times the rated current, allowing 1 second | |
| power consumption | <0.1VA/phase | |
| input | DI | Power supply: 24VDC internal excitation time resolution: 1ms |
| DO1~DO4 | Normally open 250VAC/30VDC, 1.0A, (cos=0.4, L/R=7ms) | |
| measurement accuracy | voltage | ±0.2% |
| active power | ±0.2% | |
| active energy | 0.2S level | |
| Reactive energy | Level 2 | |
| power factor | ±0.5% | |
| frequency | ±0.02Hz | |
| harmonic | S-level | |
| Voltage/current imbalance | ±0.2% | |
| working environment | Operating Temperature | -20°C~+70°C |
| relative humidity | 5%~90% | |
| Storage temperature | -30°C~+80°C | |
| Electrical insulation performance | Medium strength | 2kV power frequency voltage, 1 minute (GB/T14598) |
| insulation resistance | Not less than 100M Ω (GB/T14598) | |
| impulse voltage | 6kV,1.2/50 μs(GB/T14598) | |
| Module Configuration | standard configuration | 8 passive Di channels, 4 Do channels, 1 RJ45 network communication, 2 RS485 communication channels |
| optional | 4G wireless communication module (currently only 1 RS485 channel); 1-3 transmission modules; GPRS clock | |