Detailed introduction:

Related regulations:

1 DL/T 1054-2007Supervision Regulations for Insulation Technology of High Voltage Electrical Equipment

The operation of gas insulated metal sealed switchgear should be based onDL/T603Execution. regardingSF6For gas insulated high-voltage electrical equipment, the pressure gauge value should be within the normal range, and the cause of the pressure drop must be investigated. It is not allowed to replace the search for leakage points with gas replenishment at any time. Regular inspections should be carried outSF6Micro water measurement and density relay electrical verification. Discover problems and handle them promptly, and carry out necessary actions when necessarySO2H2SDetermination of decomposition product content.

II State Grid Corporation of China implements 18 major anti accident measures for the power grid

After the equipment malfunctions and trips, it should be used firstSF6A rapid gas decomposition testing device is used to detect the gas inside the equipment to determine whether there is discharge inside. Avoid forcing discharge again with faults. ”

III DL/T941-2005Quality standard for sulfur hexafluoride used in transformers during operation

Regarding handover, major repairs, and operationsSF6transformerCO2COHFSO2SF4SOF2andSO2F2The testing. ”

Product Overview

SF6Decomposition product tester(Fault location analyzer)It is a high-precision intelligent portable detector that can quickly measureSF6Circuit breakers, transformers, bushingsGISAnd transformers, etcSF6In insulation equipmentSF6Main decomposition products of gas:HFSO2SOF2H2SCOThe content of waiting.

As a preventive testing protocol, early detection of internal defects and diagnosis of equipment failures are necessarySF6Decomposition product testerSF6Equipment maintenance is correct,HCSseriesSF6The decomposition product tester can effectively detectSF6Electrical equipment discharge or overheating are two major internal faults to prevent major accidents from occurring.

Functional Features

Electrochemical principle, fast testing speed

● Equipped with calibration function to prevent drift

● It has data storage, query, and transmission functions

High precision, good repeatability, and intuitive large screen display

● Built in rechargeable lithium battery, suitable for both AC and DC use

Low gas consumption, equipped with gas collection bags, beneficial for environmental protection

TECHNICAL INDEX

subject

HCS-02Type decomposition product tester

H2S

0~200ppm

SO2+SOF2

0~100ppm

HF

0~10ppm

CO

0~500ppm

resolution

±0.1ppm

Repeatability

≤±0.2ppm

Sample gas flow rate

50~300mL/min

ambient temperature

-20~50

Working power supply

Working power supply:220VAC±10%50HzDual use of AC and DC, overcharge protection

Air intake connection

Imported quick connector

communication interface

USB2.0

display

Color screen(TFT

Dual channel detection

/

External dimensions

339×295×152(mm3)

weight

6.2Kg

enclosure:SF6Reference indicators for normal values of decomposition products of electrical equipment

set up have

Decomposition product concentration μl/L

prepare pour

SO2+SOF2

H2S

CO

HF

Circuit breaker

2.0

1.0

100

1.0

Two weeks after the nearest trip

OTHER EQUIPMENT

1.0

0.5

100

0.5